CSST Bonding: What is it? (And Why is it Necessary?)

Electrical4u
Electrical4u
Field: Basic Electrical
0
China
what is csst bonding

What is CSST Bonding?

CSST (Corrugated Stainless-Steel Tubing) bonding is a technique in which a conductor is electrically connected to CSST metallic gas piping and then connected to the grounding electrode system to provide a low impedance path to the ground. CSST Bonding is used to reduce the possibility and severity of arcing between conductive systems when energized by a lightning strike on a CSST gas pipe or nearby.

The CSST must be permanently bonded to the grounding electrode system of the electrical service of the home in which the CSST is installed. This arrangement provides an electrically continuous path to stray voltage/current safely to the ground.

Proper bonding of CSST may significantly reduce the risk of fire or damage to the CSST gas pipe caused by a lightning strike.

Why CSST Bonding is Necessary?

When CSST is installed without being properly bonded then there is an increased risk of fire or damage to the gas lines when a lightning strike or power surges happens nearby.

Note that lightning is a highly disruptive force and when it happens nearby, it can travel along the CSST gas pipe. This traveling energy can jump to near metal and dissipated its energy.

Now if the CSST is not being properly bonded, the difference in potential between gas pipe and metal can produce arc which can damage to the CSST gas pipe. When CSST is damaged, it can leak gas and cause fire or an explosion.

The CSST bonding will help to achieve an equipotential state between the CSST gas line and bonded metallic conductor. Therefore, CSST Bonding is necessary to reduce the risk of fire or explosion resulting from damaged gas lines in the event of power surges and lightning strikes. The below figure shows the damaged CSST gas line due to lightning strike.



Damaged Gas Line due to Lightning Strike
Damaged Gas Line Due to Lightning Strike





Damaged gas line
Damaged Gas Line



CSST Bonding Diagram

For proper bonding of CSST, a separate bonding wire is connected to the rigid gas piping before the CSST, or directly to one of the CSST nuts. The below figure shows the CSST bonding diagram.



CSST Bonding Diagram
CSST Bonding Diagram



The below figure shows an example of proper CSST Bonding.



Proper CSST Bonding
Proper CSST Bonding



CSST Bonding Code

The CSST bonding, bonding conductor, grounding electrode system, bonding clamp, and grounding conductor must be in accordance with the code. Let’s discuss it one by one.

In accordance with the National Fuel Gas Code, the International Fuel Gas Code, and the Uniform Plumbing Code the direct bonding is provided for CSST gas piping systems for homes and buildings. Bonding of CSST is to be considered an electrification work and it should be installed and inspected by a qualified electrical contractor and electrical inspector.

Bonding Conductor

The bonding conductor must be installed, protected, and connected to the grounding electrode system in accordance with the National Electrical Code, NFPA 70, and Canadian Electrical Code, CSA-C22.1.

The bonding conductor can be a solid or stranded aluminum or copper conductor. The size of the bonding conductor must not be smaller than a 6 AWG (American Wire Gauge) copper wire or the equivalent size of aluminum if the bonding conductor is made of aluminum. The below figure shows an example of a bonding conductor.



Example of Bonding Conductor
Example of Bonding Conductor



The bonding conductor must not be longer than 75 feet (22860 MM) in accordance with the National Fuel Gas Code, the International Fuel Gas Code, and the Uniform Plumbing Code.

Bonding Clamp

The bonding clamp is never attached to the corrugated stainless-steel tubing. It can be attached to any location within the gas piping system.

The location of the bonding clamp on the gas piping system must be selected so that the shortest bonding wire length will improve the effectiveness of the direct-bond. The below figure shows an example of a bonding clamp.



Clamp Attachment on CSST
Example of Bonding Clamp



Bonding clamp must be installed based on UL467 and shall make metal-to-metal contact with a rigid pipe component or CSST fitting. The gas pipe surface must be clean, paint and coatings free to allow a proper metal-to-metal connection.

Grounding Electrode

Grounding electrodes must be a metallic conductor and should be connected to the earth. The following materials are typically used as grounding electrodes.

  • Rods

  • Plates

  • Structural Steel

All electrodes must be bonded together into one common grounding electrode system. A grounding electrode and grounding system can not be installed separately for the gas piping system. The below figure shows a grounding electrode connection.



Grounding Electrode Connection
Proper Grounding Electrode Connection



Grounding Electrode System

The grounding electrode system comprising of grounding electrodes and a grounding electrode conductor. The installation and inspection of the grounding electrodes and grounding systems must be performed by a qualified electrical contractor and electrical inspector.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
What Is THD? How It Affects Power Quality & Equipment
What Is THD? How It Affects Power Quality & Equipment
In the field of electrical engineering, the stability and reliability of power systems are of paramount importance. With the advancement of power electronics technology, the widespread use of nonlinear loads has led to an increasingly serious problem of harmonic distortion in power systems.Definition of THDTotal Harmonic Distortion (THD) is defined as the ratio of the root mean square (RMS) value of all harmonic components to the RMS value of the fundamental component in a periodic signal. It is
Encyclopedia
11/01/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.