• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Transformer Operating Temperature, Voltage Variation, and Parallel Operation Requirements

Encyclopedia
Field: Encyclopedia
0
China

Transformer Operating Temperature

During operation, transformers generate copper losses and iron losses, both of which are converted into heat, causing the transformer’s temperature to rise. Most transformers in China use Class A insulation. Due to heat transfer characteristics, significant temperature differences exist between different components during operation: winding temperature is the highest, followed by the core, and then the temperature of the insulating oil (with upper-layer oil being hotter than lower-layer oil). The allowable operating temperature of a transformer is determined by the temperature of its upper-layer oil. For Class A insulated transformers, under normal operating conditions with an ambient temperature of 40°C, the maximum temperature of the upper-layer oil must not exceed 85°C.

Temperature Rise During Transformer Operation

The temperature difference between the transformer and its surrounding medium is referred to as the transformer’s temperature rise. Due to the notable temperature variations across different components, this can impact the transformer’s insulation. Additionally, as the transformer’s temperature increases, winding losses also rise. Therefore, it is necessary to specify allowable temperature rises for each component under rated load conditions. For Class A insulated transformers, when the ambient temperature is 40°C, the allowable temperature rise for upper-layer oil is 55°C, and for windings, it is 65°C.

Transformer.jpg

Voltage Variation Range During Transformer Operation

In power systems, fluctuations in grid voltage cause corresponding variations in the voltage applied to transformer windings. If the grid voltage is lower than the rated voltage of the transformer’s used tap, no damage to the transformer occurs. However, if the grid voltage exceeds the rated voltage of the used tap, it will lead to increased winding temperatures, higher reactive power consumption by the transformer, and waveform distortion in the secondary coil. Thus, the transformer’s supply voltage should generally not exceed 5% of the tap’s rated voltage.

Requirements for Transformer Parallel Operation

Transformer parallel operation involves connecting the primary windings of two or more transformers to a common power source and their secondary windings in parallel to supply a shared load. In modern power systems, as system capacity grows, parallel operation of transformers has become essential.Power transformers operating in parallel must meet the following requirements:

  • Their transformation ratios must be equal, with an allowable deviation of ±0.5%.

  • Their short-circuit voltages must be equal, with an allowable deviation of ±10%.

  • Their connection groups must be identical.

Give a tip and encourage the author!
Recommended
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.