Why Is Transformer Core Single-Point Grounding Required and Multiple Grounding Prohibited?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

During transformer operation, the core and the metallic structures and components that secure the core and windings are exposed to a strong electric field, inducing a high potential relative to ground. If the core is left ungrounded, a potential difference can develop between the core and grounded parts such as clamps and the tank, leading to intermittent discharges. Additionally, the magnetic field surrounding the windings induces varying electromotive forces (EMF) in different metallic components due to their varying distances from the windings. Even small potential differences can result in continuous partial discharges across minor insulation gaps—discharges that are not only unacceptable but also difficult to detect and locate.

The effective solution is to reliably ground the core and all associated metallic structures, ensuring they are at the same electrical potential as the tank. However, this grounding must be implemented at a single point only. Core laminations are insulated from each other to suppress large eddy currents, which would otherwise cause excessive heating. Therefore, multiple grounding points are strictly prohibited, as they can create closed loops that allow circulating currents, leading to severe core overheating.

Why Multiple Grounding Points Are Prohibited:

If the core is grounded at more than one point, a closed conductive loop may form between the grounding points. When the main magnetic flux passes through this loop, it induces circulating currents, resulting in localized overheating and potentially serious damage. This may manifest as localized core burning or short circuits between laminations, increasing core losses and degrading transformer performance. In severe cases, such faults can lead to complete transformer failure, requiring extensive repair or core replacement.

Transformer ..jpg

Risks of Multiple Grounding:

In the presence of a strong electric field, ungrounded or improperly grounded core and metal parts can develop induced voltages, causing discharges to ground. Single-point grounding prevents the formation of circulating (or "ring") currents that would otherwise flow if multiple grounding points existed. These circulating currents cause localized overheating, degrade insulation, and damage metallic components, posing a significant risk to transformer reliability and safe operation.

Therefore, single-point grounding of the transformer core is essential for safe, stable, and efficient operation.

Give a tip and encourage the author!
Recommended
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
The tap changer operating handle shall be equipped with a protective cover. The flange at the handle shall be well sealed with no oil leakage. Locking screws shall securely fasten both the handle and the drive mechanism, and the handle rotation shall be smooth without binding. The position indicator on the handle shall be clear, accurate, and consistent with the tap voltage regulation range of the winding. Limit stops shall be provided at both extreme positions. The insulating cylinder of the t
Leon
11/04/2025
How to Overhaul a Transformer Conservator (Oil Pillow)?
How to Overhaul a Transformer Conservator (Oil Pillow)?
Overhaul Items for Transformer Conservator:1. Ordinary-Type Conservator Remove the end covers on both sides of the conservator, clean rust and oil deposits from inner and outer surfaces, then apply insulating varnish to the inner wall and paint to the outer wall; Clean components such as the dirt collector, oil level gauge, and oil plug; Check that the connecting pipe between the explosion-proof device and the conservator is unobstructed; Replace all sealing gaskets to ensure good sealing with n
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.