• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Power Transformers 101: Inrush Current, Voltage Regulation, and More

Vziman
Field: Manufacturing
China

What are the types of power transformers, and what are their main components?

Power transformers are available in various types to meet the evolving demands of power systems. They can be classified as single-phase or three-phase based on phase configuration; core-type or shell-type according to the relative arrangement of windings and core; and dry-type, air-cooled, forced oil circulation air-cooled, or water-cooled based on cooling methods. In terms of neutral point insulation, transformers are categorized as fully insulated or partially insulated. Additionally, insulation classes of windings are designated as A, E, B, F, and H based on material type. Each transformer type has specific operational requirements. The main components of a power transformer include the core, windings, bushings, oil tank, conservator (oil pillow), radiator, and associated accessories.

What is inrush current in transformers, and what causes it?

Inrush current refers to the transient current that flows in transformer windings when voltage is initially applied. It occurs when the residual magnetic flux in the core aligns with the magnetic flux produced by the applied voltage, causing the total flux to exceed the core’s saturation level. This results in a large inrush current, which can reach 6 to 8 times the rated current. The magnitude of the inrush current depends on factors such as the voltage phase angle at energization, the amount of residual flux in the core, and the source system impedance. The peak inrush current typically occurs when the voltage is at zero crossing (corresponding to peak flux). The inrush current contains DC and higher harmonic components and decays over time due to circuit resistance and reactance—typically within 5–10 seconds for large transformers and about 0.2 seconds for smaller units.

What are the methods of voltage regulation in transformers?

There are two primary methods of voltage regulation: on-load tap changing (OLTC) and off-load tap changing (DETC).On-load voltage regulation allows tap position adjustments while the transformer is energized and operating, enabling continuous voltage control by altering the turns ratio. Common configurations include line-end tap and neutral-point tap. The neutral-point tap offers reduced insulation requirements but requires the neutral to be solidly grounded during operation.
Off-load voltage regulation involves changing the tap position only when the transformer is de-energized or during maintenance.

What is a fully insulated transformer, and what is a partially insulated transformer?

A fully insulated transformer (also known as uniformly insulated) has consistent insulation levels throughout the winding. In contrast, a partially insulated transformer (or graded insulation) features reduced insulation levels near the neutral point compared to the line ends.

What is the difference in operating principles between voltage transformers and current transformers?

Voltage transformers (VTs) are primarily used for voltage measurement, while current transformers (CTs) are used for current measurement. Key operational differences include:

  • The secondary side of a CT must never be open-circuited but can be short-circuited. Conversely, the secondary of a VT must never be short-circuited but can be open-circuited.

  • A VT has very low primary impedance relative to its secondary load, making it behave like a voltage source. In contrast, a CT has high primary impedance and functions as a current source with effectively infinite internal resistance.

  • Under normal operation, a VT operates with magnetic flux density near saturation, which may decrease during system faults due to voltage drop. A CT, however, operates at low flux density under normal conditions. During short circuits, the increased primary current can drive the core into deep saturation, increasing measurement errors. Therefore, selecting CTs with high saturation resistance is recommended.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
01/29/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.