Key Design Considerations for Enhancing Power Transformer Reliability

Vziman
Vziman
Field: Manufacturing
China

Power transformers are critical components within the power grid. Once quality issues occur, they may not only result in significant economic and property losses but also endanger lives and cause immeasurable negative social impacts.

Generally, the reliability of a power transformer is primarily influenced by its design, technology, materials, and manufacturing standards. Among these, design—being the foundation of product quality—plays a crucial role in determining the overall reliability of power transformers.

Statistics indicate that "design defects" are the primary cause of major quality incidents historically experienced by the industry, accounting for over 80% of such events. Therefore, the reliability of transformer design is both a prerequisite and a fundamental guarantee for achieving overall product reliability. This article discusses several key aspects of transformer reliability design.

Short-Circuit Withstand Capability Design Principle

Short-circuit withstand capability is a key indicator of power transformer reliability. Damage due to insufficient short-circuit strength is not uncommon in power systems, and failures during random short-circuit tests are also frequently reported.

As a special test, only a very small proportion of power transformers—less than 1% of total production—undergo actual short-circuit testing. Hence, design validation remains the most practical approach to ensure adequate short-circuit withstand capability.

The fundamental principle of short-circuit design should focus on minimizing the actual short-circuit stress as much as possible, rather than blindly increasing the allowable stress limits. The latter approach overly depends on material properties and manufacturing processes and represents an uncontrollable design strategy.

Design Considerations for Hot Spot Temperature Rise

The hot spot temperature rise in various components of a power transformer is closely linked to its service life and directly affects long-term operational reliability. As a type test, temperature rise testing is not performed on every unit. Thus, design analysis and verification remain essential to ensure that hot spot temperature rises across all components remain within safe limits.

Transformer hot spot temperature rise design should focus on three critical areas: winding hot spots, core hot spots, and hot spots in metallic structural parts. Accurate calculation of leakage magnetic field distribution and loss density, based on product structure and parameters, provides a vital foundation for the rational selection of component materials, effective implementation of stray flux control measures, and optimized cooling oil circuit design—ensuring that all component hot spot temperature rises remain within safe values.

Give a tip and encourage the author!
Recommended
What causes a transformer to be noisier under no-load conditions?
What causes a transformer to be noisier under no-load conditions?
When a transformer is operating under no-load conditions, it often produces louder noise than under full load. The primary reason is that, with no load on the secondary winding, the primary voltage tends to be slightly higher than nominal. For example, while the rated voltage is typically 10 kV, the actual no-load voltage may reach around 10.5 kV.This elevated voltage increases the magnetic flux density (B) in the core. According to the formula:B = 45 × Et / S(where Et is the designed volts-per-
Noah
11/05/2025
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
When installing an arc suppression coil, it is important to identify the conditions under which the coil should be taken out of service. The arc suppression coil should be disconnected under the following circumstances: When a transformer is being de-energized, the neutral-point disconnector must be opened first before performing any switching operations on the transformer. The energizing sequence is the reverse: the neutral-point disconnector should be closed only after the transformer is energ
Echo
11/05/2025
What fire prevention measures are available for power transformer failures?
What fire prevention measures are available for power transformer failures?
Failures in power transformers are commonly caused by severe overload operation, short circuits due to winding insulation degradation, aging of transformer oil, excessive contact resistance at connections or tap changers, failure of high- or low-voltage fuses to operate during external short circuits, core damage, internal arcing in oil, and lightning strikes.Since transformers are filled with insulating oil, fires can have severe consequences—ranging from oil spraying and ignition to, in extrem
Noah
11/05/2025
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
Transformer Longitudinal Differential Protection: Common Issues and SolutionsTransformer longitudinal differential protection is the most complex among all component differential protections. Misoperations occasionally occur during operation. According to 1997 statistics from the North China Power Grid for transformers rated 220 kV and above, there were 18 incorrect operations in total, of which 5 were due to longitudinal differential protection—accounting for approximately one-third. Causes of
Felix Spark
11/05/2025