What failure modes are possible in a transformer? How to identify and fix these failures?

Edwiin
Edwiin
Field: Power switch
China

Transformers are critical components in power systems, and various failure modes can affect their operation. Timely identification and resolution of these failure modes are essential to prevent costly downtime and ensure system reliability. Below are some common transformer failure modes, along with methods to identify and address them:

  • Insulation Failure
    Identification: Insulation failure leads to decreased insulation resistance, which can be detected through insulation resistance testing (megger testing).
    Repair: Replace or repair damaged insulation materials as necessary, including bushings, leads, or entire windings. Investigate the root cause of insulation failure, which may be due to overheating, moisture ingress, or contamination.

  • Overheating
    Identification: Overheating may result from overloading, inadequate cooling, or loose connections. High temperatures can be detected using temperature sensors and infrared thermography.
    Repair: Reduce load within the transformer’s rated capacity, ensure proper cooling, and tighten loose connections. Consider redesigning the cooling system if necessary.

  • Core Saturation
    Identification: Core saturation occurs when the magnetic core reaches its limit, causing output waveform distortion. This can be observed through harmonic distortion in current and voltage waveforms.
    Repair: Install harmonic filters to mitigate core saturation. Evaluate whether a different core material or design is needed to prevent saturation.

  • Winding and Core Damage
    Identification: Visual inspection may reveal physical damage such as cracks, warping, or deformation in windings or the core.
    Repair: Repair or replace damaged components. Minor winding damage may be repaired locally, while severe damage may require rewinding or core replacement.

  • Oil Contamination and Degradation
    Identification: Oil analysis, including Dissolved Gas Analysis (DGA), can detect contaminants and gases generated during incipient faults. Darkened or foaming oil may also indicate problems.
    Repair: Replace contaminated oil and address the root cause of contamination. Consider upgrading to environmentally friendly and less flammable insulating fluids if applicable.

  • Bushings and Gasket Leaks
    Identification: Oil leaks can be visually observed, especially around bushings and gaskets.
    Repair: Repair or replace damaged bushings and gaskets. Tighten connections and ensure proper sealing.

  • Short Circuits
    Identification: Short circuits cause overcurrent and may produce distinctive sounds. Protective relays should trip due to the short circuit.
    Repair: Investigate the cause of the short circuit, repair damaged components, and replace any affected winding sections.

  • Tap Changer Problems
    Identification: Tap changer failures may cause voltage regulation issues or arcing in No-Load Tap Changers (NLTC). Monitoring voltage variations helps identify tap changer problems.
    Repair: Clean, lubricate, and maintain the tap changer. If significant issues persist, consider repairing or replacing it.

  • Moisture Ingress
    Identification: Moisture ingress can be detected through moisture content analysis. Visual inspection may also reveal signs of moisture damage, such as rust or corrosion.
    Repair: Address the source of moisture ingress, repair or replace damaged components, and maintain proper sealing.

Regular preventive maintenance is crucial, including visual inspections, oil sampling, and insulation resistance testing, to detect potential issues early. Additionally, consider employing condition monitoring techniques such as online monitoring and partial discharge testing to continuously assess transformer health. Timely maintenance and repairs help extend transformer lifespan and prevent costly failures.


Give a tip and encourage the author!
Recommended
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
The tap changer operating handle shall be equipped with a protective cover. The flange at the handle shall be well sealed with no oil leakage. Locking screws shall securely fasten both the handle and the drive mechanism, and the handle rotation shall be smooth without binding. The position indicator on the handle shall be clear, accurate, and consistent with the tap voltage regulation range of the winding. Limit stops shall be provided at both extreme positions. The insulating cylinder of the t
Leon
11/04/2025
How to Overhaul a Transformer Conservator (Oil Pillow)?
How to Overhaul a Transformer Conservator (Oil Pillow)?
Overhaul Items for Transformer Conservator:1. Ordinary-Type Conservator Remove the end covers on both sides of the conservator, clean rust and oil deposits from inner and outer surfaces, then apply insulating varnish to the inner wall and paint to the outer wall; Clean components such as the dirt collector, oil level gauge, and oil plug; Check that the connecting pipe between the explosion-proof device and the conservator is unobstructed; Replace all sealing gaskets to ensure good sealing with n
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.