What is Metal Oxide Surge Arrester?

Edwiin
Edwiin
Field: Power switch
China

What is Metal Oxide Surge Arrester?

Definition:An arrester that utilizes zinc oxide semiconductor as its resistor material is called a metal oxide surge arrester or ZnO Diverter. This type of arrester offers protection against all kinds of AC and DC over - voltages. It is primarily employed for over - voltage protection at all voltage levels within a power system.

Construction & Working of Metal Oxide Surge Arrester:Zinc oxide is an N - type semiconducting material. It is pulverized into a fine - grained state. More than ten doping materials, in the form of fine powders of insulating oxides such as Bismuth (Bi₂O₃), Antimony Trioxide (Sb₂O₃), Cobalt Oxide (CoO), Manganese Oxide (MnO₂), and Chromium Oxide (Cr₂O₃), are added. The powder mixture undergoes certain treatment processes and is then spray - dried to yield a dry powder.

Subsequently, the dry powder is compressed into disc - shaped blocks. These blocks are sintered to obtain a dense poly - crystalline ceramic. The metal oxide resistor disc is coated with a conducting compound to safeguard the disc from adverse environmental impacts.

The conducting coating not only provides proper electrical contacts but also ensures uniform current distribution across the disc. Subsequently, the disc is enclosed within a porcelain housing that is filled with either nitrogen gas or SF6 gas. Silicon rubber is employed to fix the disc in place and also aids in transferring heat from the disc to the porcelain housing. The disc is maintained under pressure using appropriate springs.

The ZnO element in the diverter replaces the need for series spark gaps. Voltage drop in a ZnO diverter occurs at the grain boundaries. At the boundary of each ZnO grain, there exists a potential barrier which controls the flow of current from one grain to the next.

Under normal voltage conditions, this potential barrier prevents current from flowing through. However, during over - voltage situations, the barrier breaks down, leading to a sharp transition of the current from an insulating state to a conducting state. As a result, the current starts to flow, and the surge is safely diverted to the ground.

Once the surge has passed, the voltage across the diverters decreases, and the current reduces to a negligible value in the resistor units. Notably, there is no power follow - current.

Advantages of Metal Oxide Surge Arrester

The metal oxide surge arrester offers the following benefits:

  • It eradicates the risks of spark - over and the associated shock to the system when gaps break down.

  • It eliminates the requirement for a voltage grading system.

  • Under normal operating conditions, the leakage current in the ZnO arrester is significantly lower compared to other types of diverters.

  • There is no power follow - current in a ZnO diverter.

  • It has a high energy - absorbing capacity.

  • ZnO diverters exhibit high stability both during and after prolonged discharge.

  • In a ZnO diverter, it is possible to control not only switching surges but also dynamic over - voltages. This enables cost - effective insulation coordination.

Note: Sintering is the process of creating a solid mass of material. This is achieved either by heating the material or by applying pressure to it without melting the material.

Give a tip and encourage the author!
Recommended
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
Transformer Longitudinal Differential Protection: Common Issues and SolutionsTransformer longitudinal differential protection is the most complex among all component differential protections. Misoperations occasionally occur during operation. According to 1997 statistics from the North China Power Grid for transformers rated 220 kV and above, there were 18 incorrect operations in total, of which 5 were due to longitudinal differential protection—accounting for approximately one-third. Causes of
Felix Spark
11/05/2025
Relay Protection Types in Substations: A Complete Guide
Relay Protection Types in Substations: A Complete Guide
(1) Generator Protection:Generator protection covers: phase-to-phase short circuits in stator windings, stator ground faults, inter-turn short circuits in stator windings, external short circuits, symmetrical overload, stator overvoltage, single- and double-point grounding in the excitation circuit, and loss of excitation. Tripping actions include shutdown, islanding, limiting fault impact, and alarm signaling.(2) Transformer Protection:Power transformer protection includes: phase-to-phase short
Echo
11/05/2025
What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?
What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?
1. Induced Lightning OvervoltageInduced lightning overvoltage refers to the transient overvoltage generated on overhead distribution lines due to nearby lightning discharges, even when the line is not directly struck. When a lightning flash occurs in the vicinity, it induces a large amount of charge on the conductors—opposite in polarity to the charge in the thundercloud.Statistical data shows that lightning-related faults caused by induced overvoltages account for approximately 90% of total fau
Echo
11/03/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin