What is Induction Voltage Regulators?

Edwiin
Edwiin
Field: Power switch
China

What is Induction Voltage Regulators?

Definition: An induction voltage regulator is a kind of electrical machine. Its output voltage can be adjusted, ranging from zero up to a specific maximum value. This range depends on the turn ratio between the primary and secondary windings. The primary winding is linked to the circuit that requires voltage regulation, while the secondary winding is connected in series with the same

 

Types of Induction Voltage Regulators

Induction voltage regulators are primarily categorized into two types: the single - phase induction voltage regulator and the three - phase induction voltage regulator.

Single - phase Induction Voltage Regulator

The schematic diagram of a single - phase induction voltage regulator is presented in the figure below. The primary winding is connected across the single - phase power supply, and the secondary winding is connected in series with the outgoing lines.


In this system, an alternating magnetic flux is induced. When the axes of the two windings align, all of the magnetic flux from the primary winding links with the secondary winding. As a result, the maximum voltage is induced in the secondary winding.

 

 

When the rotor is rotated by 90º, no part of the primary flux is linked with the secondary windings; thus, no flux is present in the secondary windings. If the rotor continues to rotate beyond this point, the direction of the induced electromotive force (emf) in the secondary becomes negative. Consequently, the regulator either adds to or subtracts from the circuit voltage, depending on the relative orientation of the two windings within the regulator.


The single - phase voltage regulator does not introduce any phase shift. The primary windings are installed in slots on the surface of the laminated cylindrical core. Since they carry relatively small currents, they have a small conductor cross - sectional area. The rotor of the regulator incorporates compensating windings, also referred to as tertiary windings.


The magnetic axis of the compensating windings is always oriented 90º away from that of the primary windings. This configuration serves to counteract the detrimental series reactance effect of the secondary windings. The secondary windings, which are connected in series with the outgoing line, are located in the stator slots because of their larger conductor area requirements.

Three - Phase Induction Voltage Regulator

Three - phase induction voltage regulators feature three primary windings and three secondary windings, which are spaced 120º apart from one another. The primary windings are placed in the slots of a laminated rotor core and are connected across a three - phase AC power supply. The secondary windings are housed in the slots of a laminated stator core and are connected in series with the load.

The regulator does not necessitate separate primary and compensating windings. This is because each secondary winding of the regulator is magnetically linked to one or more primary windings within the regulator. In this type of regulator, a rotating magnetic field of consistent magnitude is generated. As a result, the voltage induced in the secondary winding also has a constant magnitude. However, the phases of the regulator change in accordance with the variation in the rotor's position relative to the stator.

 

The phasor diagram of the induction regulator is depicted in the figure above. Here, (V1) represents the supply voltage, (Vr) is the voltage induced in the secondary, and (V2) denotes the output voltage per phase. The output voltage is derived as the phasor sum of the supply voltage and the induced voltage for any rotor displacement angle θ.


Consequently, the locus of the resultant is a circle. This circle is drawn with its center located on the tip of the supply voltage vector and has a radius equal to (Vr). The maximum output voltage is achieved when the induced voltage is in - phase with the supply voltage. Conversely, the minimum output voltage is obtained when the induced voltage is in anti - phase with the supply voltage.


The complete phasor diagram for the three - phase case is shown in the figure below. The terminals labeled AB, and C are the input terminals, while ab, and c are the output terminals of the induction regulator. The supply and the output line voltages are in - phase only at the maximum boost and minimum buck positions. For all other positions, there exists a phase displacement between the supply line voltage and the output voltage.

 

 

Give a tip and encourage the author!
Recommended
What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?
What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?
1. Induced Lightning OvervoltageInduced lightning overvoltage refers to the transient overvoltage generated on overhead distribution lines due to nearby lightning discharges, even when the line is not directly struck. When a lightning flash occurs in the vicinity, it induces a large amount of charge on the conductors—opposite in polarity to the charge in the thundercloud.Statistical data shows that lightning-related faults caused by induced overvoltages account for approximately 90% of total fau
Echo
11/03/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.