• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Bus-Bar Protection

Edwiin
Edwiin
Field: Power switch
China

When a fault occurs on the bus bars, the entire power supply is interrupted, and all the non - faulty feeders are disconnected. The majority of bus bar faults are single - phase and often temporary in nature. Bus zone faults can occur due to various factors, such as the failure of support insulators, malfunctions in circuit breakers, or foreign objects accidentally falling across the bus bars. To clear a bus fault, all circuits connected to the faulty section must be opened.

The most commonly used bus zone protection schemes include:

  • Backup protection

  • Differential Overcurrent Protection

  • Circulating current protection

  • Voltage Overvoltage Protection

  • Frame leakage protection

Backup Protection for Bus - Bars

Backup protection represents a straightforward approach to safeguarding bus bars against faults. Faults on the bus bar often originate from the supplying system, making backup protection for the supply system essential. The diagram below illustrates a basic setup for bus - bar protection. Here, bus A is protected by the distance protection mechanism of bus B. In the event of a fault on bus A, the protective device on bus B will activate, with the relay operating within 0.4 seconds.

When a fault occurs on the bus bars, the entire power supply is interrupted, and all the non - faulty feeders are disconnected. The majority of bus bar faults are single - phase and often temporary in nature. Bus zone faults can occur due to various factors, such as the failure of support insulators, malfunctions in circuit breakers, or foreign objects accidentally falling across the bus bars. To clear a bus fault, all circuits connected to the faulty section must be opened.

The most commonly used bus zone protection schemes include:

  • Backup protection

  • Differential Overcurrent Protection

  • Circulating current protection

  • Voltage Overvoltage Protection

  • Frame leakage protection

Backup Protection for Bus - Bars

Backup protection represents a straightforward approach to safeguarding bus bars against faults. Faults on the bus bar often originate from the supplying system, making backup protection for the supply system essential. The diagram below illustrates a basic setup for bus - bar protection. Here, bus A is protected by the distance protection mechanism of bus B. In the event of a fault on bus A, the protective device on bus B will activate, with the relay operating within 0.4 seconds.

Circulating Current Protection and Voltage Differential Protection Relay

Circulating Current Protection

In the circulating current protection scheme, the summation current of the current transformers (CTs) flows through the operating coil of the relay. When current passes through the relay coils, it indicates the presence of short - circuit current in the CTs' secondaries. Consequently, the relay sends a signal to the circuit breakers, prompting them to open their contacts and isolate the faulty section of the electrical system.

However, a significant drawback of this protection scheme is that iron - cored current transformers can cause the relay to malfunction during external faults. The magnetic characteristics of iron - cored CTs may lead to unequal current transformation ratios under abnormal conditions, resulting in false tripping of the relay.

Voltage Differential Protection Relay

The voltage differential protection relay scheme employs coreless CTs, which offer improved linearity compared to their iron - cored counterparts. Linear couplers are utilized to increase the number of turns on the secondary sides of these CTs, enhancing the sensitivity and accuracy of the protection system.

In this setup, the secondary relays are connected in series via pilot wires. Additionally, the relay coil is also connected in series with the second terminal of the relevant circuit. This configuration allows for a more precise comparison of electrical quantities, enabling the protection system to accurately detect and respond to internal faults while remaining immune to the effects that cause false operations in traditional iron - cored CT - based schemes.

In a fault - free electrical system or when an external fault occurs, the algebraic sum of the secondary currents of the current transformers (CTs) equals zero. This balance is due to the normal flow of current through the system's healthy components, with the CTs accurately reflecting the current distribution. However, when an internal fault develops within the protected zone, the normal current flow is disrupted. Fault current then passes through the differential relay, disrupting the previously balanced current state.

Upon detecting this abnormal current flow, the differential relay activates. It promptly issues a command to the associated circuit breakers, instructing them to open their contacts. By quickly isolating the faulty section of the system, the differential protection mechanism effectively prevents further damage to equipment and ensures the stability of the overall electrical system. This rapid response helps minimize downtime and potential hazards, safeguarding the integrity of the power grid.

Give a tip and encourage the author!
Recommended
Relay Protection Types in Substations: A Complete Guide
Relay Protection Types in Substations: A Complete Guide
(1) Generator Protection:Generator protection covers: phase-to-phase short circuits in stator windings, stator ground faults, inter-turn short circuits in stator windings, external short circuits, symmetrical overload, stator overvoltage, single- and double-point grounding in the excitation circuit, and loss of excitation. Tripping actions include shutdown, islanding, limiting fault impact, and alarm signaling.(2) Transformer Protection:Power transformer protection includes: phase-to-phase short
Echo
11/05/2025
What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?
What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?
1. Induced Lightning OvervoltageInduced lightning overvoltage refers to the transient overvoltage generated on overhead distribution lines due to nearby lightning discharges, even when the line is not directly struck. When a lightning flash occurs in the vicinity, it induces a large amount of charge on the conductors—opposite in polarity to the charge in the thundercloud.Statistical data shows that lightning-related faults caused by induced overvoltages account for approximately 90% of total fau
Echo
11/03/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.