Transformers Fire Protection System – Causes, Types & Requirements

Edwiin
Field: Power switch
China

Causes of Transformer Fires

Transformers can catch fire due to several critical issues, including excessive overheating, severe short circuits, faults in the insulating oil, and lightning strikes. While transformer fires are relatively uncommon, their consequences can be devastating. As depicted in the figure below, a transformer engulfed in fire is often irreparably damaged within minutes. However, it is crucial to address the potential impact of such fires on adjacent equipment and structures, as proper mitigation measures can limit collateral damage.

Fire Risks and Protection for Transformers

An uncontained transformer fire can cause extensive damage and lead to prolonged, unscheduled power outages. For high-rated power transformers with voltages exceeding 123 kV, it is standard practice to install dedicated fire protection systems. One common solution is fixed water spray systems, often referred to as transformer "deluge" or "fire water" systems, as illustrated in Figure 1.

These systems are designed to rapidly suppress fires by dousing the transformer with a controlled, high-volume water spray, mitigating the risk of fire spreading to adjacent equipment or structures and minimizing downtime.

Transformer Fire Protection Systems

This system is activated by flame detectors if the transformer is installed outdoors, or by smoke detectors if indoors.

Types of Transformer Fire Protection Systems

Transformer fire protection systems can be categorized into:

Water-Based and Mist Systems

  • Components: Fire pumps, fixed water spray systems/nozzles, valves, valve components, and piping.

  • Function: Rapidly suppress fires by dousing the transformer with water, leveraging high-pressure sprays or fine mists to cool surfaces and smother flames.

Fire Detection Systems

  • Components: Fire detectors (thermal, smoke, or flame sensors), control panels, and cabling.

  • Function: Detect fire hazards early and trigger suppression systems or alarms to minimize response time.

Mitigation Considerations

Fire suppression may be less critical if:

  • The transformer is remotely located from structures and other equipment.

  • Burning oil can be contained effectively (e.g., via fire-resistant barriers or drainage systems).

However, in most cases, protecting plant structures, adjacent equipment, and personnel necessitates fire suppression measures.

Alternative Solutions

Using less-flammable insulating fluids (e.g., high flashpoint oils or synthetic esters) can reduce fire risks and may eliminate the need for active suppression systems, making them a viable alternative in some installations.

Requirements for Transformer Fire Protection

The following are the fundamental principles for transformer fire protection:

New Facilities with Mineral-Oil-Filled Transformers

  • New installations featuring large mineral-oil-filled transformers located near plant structures or other equipment must incorporate active fire suppression systems to safeguard the structure, adjacent equipment, and the environment.

  • Additionally, they require properly designed containment systems (e.g., oil retention dikes) to prevent environmental contamination from spilled oil.

  • For new facilities—and where practical in existing plants—mineral-oil-filled transformers should be sited away from buildings, other equipment, and waterways to minimize fire and environmental risks. In such cases, active fire suppression may be unnecessary if separation distances and other risk mitigation measures are sufficient.

Existing Facilities

  • Functional fire suppression systems in operation should continue to protect plant structures and equipment but must be periodically reviewed for adequacy and compliance with current codes and standards.

  • Inactive or non-functional fire suppression systems must be assessed for compliance with modern standards and restored to operational status where required.

  • Existing facilities without fire suppression systems must install them where necessary to protect critical structures or equipment, as determined by risk assessments.

Transformer Maintenance and Assessment

  • Transformers require periodic condition assessments in addition to routine inspections, testing, and maintenance. Units with low condition indices should be prioritized for rehabilitation or replacement to reduce failure risks.

Fire Containment Structures

  • Fire walls or barriers should be installed between adjacent transformers, between transformers and plant structures, between single-phase units, or between transformers and other equipment where feasible. These barriers limit fire and explosion spread, minimizing collateral damage.

System Operation and Compliance

  • Fire suppression systems must be regularly operated, maintained, and tested to ensure reliability during emergencies.

  • Oil containment and oil-water separation structures (e.g., spill berms, interceptor tanks) must comply with all relevant environmental laws, regulations, and industry standards to prevent pollution.

Access and Public Safety

  • Access to transformer areas must be restricted to authorized personnel only. Measures should be taken to physically limit public proximity to transformers, reducing the risk of injury or unauthorized interference.

  • All fire protection and containment measures must align with applicable environmental laws to prevent regulatory non-compliance and ecological harm.

By adhering to these principles, facilities can effectively mitigate fire risks, protect infrastructure, safeguard personnel, and minimize environmental impact from transformer incidents.

Give a tip and encourage the author!

Recommended

Analysis of Lightning Protection Measures for Distribution Transformers
Analysis of Lightning Protection Measures for Distribution TransformersTo prevent lightning surge intrusion and ensure the safe operation of distribution transformers, this paper presents applicable lightning protection measures that can effectively enhance their lightning withstand capability.1. Lightning Protection Measures for Distribution Transformers1.1 Install surge arresters on the high-voltage (HV) side of the distribution transformer.According to SDJ7–79 Technical Code for Overvol
12/24/2025
Transformer Protection Settings: Zero-Sequence & Overvoltage Guide
1. Zero-Sequence Overcurrent ProtectionThe operating current for zero-sequence overcurrent protection of grounding transformers is typically determined based on the transformer's rated current and the maximum allowable zero-sequence current during system ground faults. The general setting range is approximately 0.1 to 0.3 times the rated current, with operating time usually set between 0.5 to 1 second to quickly clear ground faults.2.Overvoltage ProtectionOvervoltage protection is a critical com
12/17/2025
Electrical Protection: Grounding Transformers and Bus Charging
1. High-Resistance Grounding SystemHigh-resistance grounding can limit ground fault current and appropriately reduce ground overvoltage. However, there is no need to connect a large high-value resistor directly between the generator neutral point and ground. Instead, a small resistor can be used together with a grounding transformer. The primary winding of the grounding transformer is connected between the neutral point and ground, while the secondary winding is connected to a small resistor. Ac
12/17/2025
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an