• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Automatic Reclosing Modes: Single, Three-Phase & Composite

Edwiin
Edwiin
Field: Power switch
China

General Overview of Automatic Reclosing Modes

Typically, automatic reclosing devices are categorized into four modes: single-phase reclosing, three-phase reclosing, composite reclosing, and disabled reclosing. The appropriate mode can be selected based on load requirements and system conditions.

1. Single-Phase Reclosing

Most 110kV and higher transmission lines employ three-phase single-shot reclosing. According to operational experience, over 70% of short-circuit faults in high-voltage overhead lines within solidly grounded systems (110kV and above) are single-phase-to-ground faults. For 220kV and higher lines, due to larger phase spacing, single-phase ground faults can account for up to 90% of all faults. In such cases, disconnecting only the faulty phase and performing single-phase reclosing—while keeping the two healthy phases energized during the reclosing cycle—significantly improves power supply reliability and enhances the stability of parallel system operation. Therefore, single-phase reclosing is widely used in solidly grounded systems of 220kV and above.

It is generally applied to:

  • 220kV and below single-circuit tie lines;

  • Lines with weak interconnection between two power sources (including electromagnetic loop networks weakly connected via lower-voltage lines);

  • High-voltage outgoing lines from large steam turbine generator units.

2. Composite Reclosing

Composite reclosing applies single-phase reclosing for single-phase-to-ground faults and three-phase reclosing for phase-to-phase faults.

It is typically used on lines where three-phase reclosing is permitted, but single-phase reclosing offers better performance in maintaining system stability or restoring power supply.

3. Three-Phase Reclosing

Three-phase reclosing refers to a method where, regardless of whether a single-phase or phase-to-phase fault occurs on transmission or distribution lines, the protective relay trips all three phases of the circuit breaker simultaneously, followed by the automatic reclosing device re-closing all three phases at once.

This mode is generally used on lines with strong interconnection between a power source and a load, or between two robust power systems.

There are two main methods to initiate automatic reclosing:

I. Non-Correspondence Initiation (Position Mismatch Start)

Non-correspondence initiation occurs when the control status of the circuit breaker does not match its actual position.

The protection device uses a breaker position input (typically the "trip position" contact) to determine the breaker's status. If this input is closed, it indicates the breaker is open. If the control switch is in the "closed" position at this time, it implies the breaker was previously closed. This mismatch between control and actual position triggers the reclosing function—known as "position mismatch initiation."

This method can initiate reclosing both for protective relay trips and for unintended breaker tripping ("stealth tripping").

Advantages: Simple and reliable.
Disadvantages: May fail to operate if position relay contacts are faulty or auxiliary breaker contacts are defective.

II. Protection-Based Initiation

Protection-based initiation refers to starting the reclosing process after the protective relay issues a trip command.

After a protective trip, the device detects loss of line current and initiates reclosing. Typically, the protection device also includes a digital input labeled "external trip to initiate reclosing," allowing the second protection set in a dual-redundant configuration to trigger reclosing in the first set.

This method simplifies reclosing configuration, as the protection software determines a fixed reclosing mode, making it simple and reliable.

It can effectively correct false trips caused by protection maloperation, but cannot correct unintended "stealth tripping" caused by the circuit breaker itself.

III. Summary

Protection-based initiation and non-correspondence initiation serve as complementary methods. Modern microprocessor-based protection relays typically incorporate both methods. Some advanced designs omit external mismatch contacts and instead initiate reclosing directly when, in the absence of an external trip command (e.g., manual or remote trip), the device detects a change from "closed" to "open" position.

Give a tip and encourage the author!
Recommended
What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?
What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?
1. Induced Lightning OvervoltageInduced lightning overvoltage refers to the transient overvoltage generated on overhead distribution lines due to nearby lightning discharges, even when the line is not directly struck. When a lightning flash occurs in the vicinity, it induces a large amount of charge on the conductors—opposite in polarity to the charge in the thundercloud.Statistical data shows that lightning-related faults caused by induced overvoltages account for approximately 90% of total fau
Echo
11/03/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
What Are the Handling Procedures After Transformer Gas (Buchholz) Protection Activation?
What Are the Handling Procedures After Transformer Gas (Buchholz) Protection Activation?
What Are the Handling Procedures After Transformer Gas (Buchholz) Protection Activation?When the transformer gas (Buchholz) protection device operates, a thorough inspection, careful analysis, and accurate judgment must be carried out immediately, followed by appropriate corrective actions.1. When the Gas Protection Alarm Signal is ActivatedUpon activation of the gas protection alarm, the transformer should be inspected immediately to determine the cause of operation. Check whether it was caused
Felix Spark
11/01/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.