Inter Turn Fault Protection of Stator Winding of Generator

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Is Inter Turn Fault Protection

Inter turn stator winding fault can easily be detected by stator differential protection or stator earth fault protection. Hence, it is not very essential to provide special protection scheme for inter turn faults occurred in stator winding. This type of faults is generated if the insulation between conductors (with different potential) in the same slot is punctured. This type of fault rapidly changes to earth fault.
The high
voltage generator contains a large number of conductors per slot in the stator winding hence, in these cases the additional inter turn fault protection of the stator winding may be essential. Moreover in modern practice, inter turn protection is becoming essential for all large generating units.
Several methods can be adopted for providing inter turn protection to the stator winding of generator. Cross differential methods is most common among them. In this scheme the winding for each phase is divided into two parallel paths.

Each of the paths is fitted with identical current transformer. The secondary of these current transformers are connected in cross. The current transformer secondary’s are cross connected because currents at the primary of both CTs are entering unlike the case of differential protection of transformer where current entering from one side and leaving to other side of the transformer.
The
differential relay along with series stabilizing resistor are connected across the CT secondary loop as shown in the figure. If any inter turn fault occurs in any path of the stator winding, there will be an unbalanced in the CT secondary circuits thereby actuates 87 differential relay. Cross differential protection scheme should be applied in each of the phases individually as shown.
stator inter turn protection

An alternative scheme of inter turn fault protection of stator winding of generator is also used. This scheme provides complete protection against internal faults of all synchronous machines irrespective of the type of the winding employed or the kind of methods for connection. An internal fault in the stator winding generates second harmonic current, included in the field winding and exciter circuits of the generator. This current can be applied to a sensitive polarized relay via a CT and filter circuit.

The scheme operation is controlled by a direction of negative phase sequence relay, in order to prevent operation during external unbalanced faults or asymmetrical load conditions. Should there be any asymmetry external to the generator unit zone, the negative phase sequence relay prevents a complete shutdown, only allowing the main circuit breaker to be tripped, to prevent the rotor damage due to the over rating effects of second harmonic currents.

stator inter turn protection
stator inter turn protection

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?
What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?
1. Induced Lightning OvervoltageInduced lightning overvoltage refers to the transient overvoltage generated on overhead distribution lines due to nearby lightning discharges, even when the line is not directly struck. When a lightning flash occurs in the vicinity, it induces a large amount of charge on the conductors—opposite in polarity to the charge in the thundercloud.Statistical data shows that lightning-related faults caused by induced overvoltages account for approximately 90% of total fau
Echo
11/03/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.