Trip Circuit Supervision

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Is Trip Circuit Supervision

There are different contacts connected in series along a trip circuit of an electrical circuit breaker. There must be some situation when the circuit breaker should not trip even a faulty current passes through its power contacts. Such situations are low gas pressure in SF6 circuit breaker, low air pressure in pneumatic operated circuit breaker etc. In this situation the trip coil of the CB must not be energized to trip the CB. So there must be NO contacts associated with gas pressure and air pressure relays, connected in series with breaker trip coil. Another scheme of trip coil is that it should not be re energized once the circuit breaker is opened. That is done by providing one NO contact of breaker auxiliary switch in series with trip coil. In addition to that the trip circuit of a CB has to pass through considerable numbers of intermediate terminal contacts in relay, control panel and circuit breaker kiosk.

So if any of the intermediate contacts is detached, the circuit breaker fails to trip. Not only that, if DC supply to the trip circuit fails, the CB will not trip. To overcome this abnormal situation, trip circuit supervision becomes very necessary. The figure below shows the simplest form of trip circuit healthy scheme. Here a series combination of one lamp, one push bottom and one resistor is connected across the protective relay contact as shown. In healthy situation all the contacts except protective relay contact are in close position. Now if push bottom (PB) is pressed, the trip circuit supervision network is completed and lamp glows indicating that the breaker is ready for tripping.

trip circuit supervisionThe above scheme is for supervision while circuit breaker is closed. This scheme is called post close supervision. There is another supervision scheme which is called pre and post close supervision.

This trip circuit supervision scheme is also quite simple. The only difference is that here in this scheme, one NC contact of same auxiliary switch is connected across the auxiliary NO contact of the trip circuit. The auxiliary NO contact is closed when CB is closed and auxiliary NC contact is closed when CB is open and vice versa. Hence, as shown in the figure below when the circuit breaker is closed the trip circuit supervision network is completed via auxiliary NO contact but when the circuit breaker is open the same supervision network is completed via NC contact. The resistor is used series with the lamp for preventing unwanted tripping of circuit breaker due to internal short circuit caused by failure of the lamp.
Trip Circuit SupervisionSo far whatever we have discussed it is only for locally controlled installation but for a distance control installation, relay system is necessary. The figure below shows the trip circuit supervision scheme wherever a remote signal is required.
Trip Circuit SupervisionWhen trip circuit is healthy and circuit breaker is closed, relay A is energized which closes the NO contact A1 and hence relay C is energized. Energized relay C keeps NC contact in open position. Now if the circuit breaker is open, relay B is energized which closes No contact B1 hence relay C is energized. As C is energized, it keeps the NC contact C1 in open position. While CB is closed, if there is any discontinuity in the trip circuit relay A is de-energized which opens contact A1 and consequently relay C is de-energized and which make the NC contact C1 in close position and hence alarm circuit is actuated. Trip circuit supervision is experienced by relay B with the circuit breaker is open in a similar manner as relay A with the circuit breaker is closed. Relays A and C are time-delayed by copper slugs to prevent spurious alarms during tripping or closing operations. The resistors are mounted separately from the relays and their values are chosen such that if any one component is inadvertently short-circuited, a tripping operation will not take place.

The alarm circuit supply should be separated from main trip supply so that the alarm can be actuated even the trip supply failed.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
Transformer Longitudinal Differential Protection: Common Issues and SolutionsTransformer longitudinal differential protection is the most complex among all component differential protections. Misoperations occasionally occur during operation. According to 1997 statistics from the North China Power Grid for transformers rated 220 kV and above, there were 18 incorrect operations in total, of which 5 were due to longitudinal differential protection—accounting for approximately one-third. Causes of
Felix Spark
11/05/2025
Relay Protection Types in Substations: A Complete Guide
Relay Protection Types in Substations: A Complete Guide
(1) Generator Protection:Generator protection covers: phase-to-phase short circuits in stator windings, stator ground faults, inter-turn short circuits in stator windings, external short circuits, symmetrical overload, stator overvoltage, single- and double-point grounding in the excitation circuit, and loss of excitation. Tripping actions include shutdown, islanding, limiting fault impact, and alarm signaling.(2) Transformer Protection:Power transformer protection includes: phase-to-phase short
Echo
11/05/2025
What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?
What Are the Factors Influencing the Impact of Lightning on 10kV Distribution Lines?
1. Induced Lightning OvervoltageInduced lightning overvoltage refers to the transient overvoltage generated on overhead distribution lines due to nearby lightning discharges, even when the line is not directly struck. When a lightning flash occurs in the vicinity, it induces a large amount of charge on the conductors—opposite in polarity to the charge in the thundercloud.Statistical data shows that lightning-related faults caused by induced overvoltages account for approximately 90% of total fau
Echo
11/03/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.