What Is a Power System Bushing and Its Types for Transformers?

Edwiin
Edwiin
Field: Power switch
China

In electrical power systems, a bushing is an insulating device that allows an electrical conductor to pass safely through a grounded conductive barrier, as in the case of transformers or circuit breakers. All transformer windings are connected to high-voltage lines, so special attention must be paid to the terminal connections to prevent flashover between the high-voltage terminals and the transformer body. In low-voltage distribution transformers, cable connections are made within a terminal box on the secondary side.

However, in power transformers, both sides operate at high voltage, necessitating specially designed devices known as bushings. A bushing typically consists of a central current-carrying conductor (a rod, busbar, or cable) and a porcelain housing mounted in the opening of the transformer cover, which insulates the live part. The simplest type is a molded high-quality glazed porcelain insulator with a central conductor. This type is used for voltages up to 33 kV and features a smooth or slightly ribbed surface for indoor applications.

For outdoor transformers, the external (upper) part of the bushing includes sheds to protect the lower ribs from water during rain. For transformers operating above 36 kV, oil-filled or capacitor-type bushings are used. An oil-filled bushing consists of a hollow, two-part porcelain cylinder with a conductor passing through its axis. The space between the conductor and the inner surface of the porcelain is filled with oil, which is separate from the oil in the transformer tank. The top of the bushing connects to a small expansion chamber to accommodate volume changes due to oil temperature variations. Provision is made at the lower end for current transformers, allowing the bushing to be removed without disturbing the current transformer.

A capacitor bushing is constructed with layers of synthetic resin-bonded paper interleaved with thin metallic foils impregnated with conductive material. This forms a series of capacitors, where each pair of metal foils and the intervening resin-bonded paper cylinder acts as a capacitor. By varying the length of the metallic foils and the thickness of the resin-bonded paper layers, the dielectric stress is evenly distributed across the radial depth—i.e., along the radius of the bushing.

Give a tip and encourage the author!
Recommended
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
The tap changer operating handle shall be equipped with a protective cover. The flange at the handle shall be well sealed with no oil leakage. Locking screws shall securely fasten both the handle and the drive mechanism, and the handle rotation shall be smooth without binding. The position indicator on the handle shall be clear, accurate, and consistent with the tap voltage regulation range of the winding. Limit stops shall be provided at both extreme positions. The insulating cylinder of the t
Leon
11/04/2025
How to Overhaul a Transformer Conservator (Oil Pillow)?
How to Overhaul a Transformer Conservator (Oil Pillow)?
Overhaul Items for Transformer Conservator:1. Ordinary-Type Conservator Remove the end covers on both sides of the conservator, clean rust and oil deposits from inner and outer surfaces, then apply insulating varnish to the inner wall and paint to the outer wall; Clean components such as the dirt collector, oil level gauge, and oil plug; Check that the connecting pipe between the explosion-proof device and the conservator is unobstructed; Replace all sealing gaskets to ensure good sealing with n
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.