• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


How to Overhaul a Transformer Conservator (Oil Pillow)?

Felix Spark
Felix Spark
Field: Failure and maintenance
China

Overhaul Items for Transformer Conservator:

1. Ordinary-Type Conservator

  • Remove the end covers on both sides of the conservator, clean rust and oil deposits from inner and outer surfaces, then apply insulating varnish to the inner wall and paint to the outer wall;

  • Clean components such as the dirt collector, oil level gauge, and oil plug;

  • Check that the connecting pipe between the explosion-proof device and the conservator is unobstructed;

  • Replace all sealing gaskets to ensure good sealing with no leakage; withstand a pressure of 0.05 MPa (0.5 kg/cm²) without leakage;

  • Check that the Buchholz relay connecting pipe extends into the conservator and protrudes 20 mm above the bottom surface;

  • Check that the glass of the oil level gauge is intact, clean, and transparent; the temperature indication lines should be clear—if not, re-mark them.

2. Capsule-Type Conservator

The overhaul procedure for a capsule-type conservator is basically the same as that for an ordinary conservator. The installation procedure is as follows:

  • Check the capsule’s sealing performance by conducting a pressure test: at a pressure of 0.02 MPa (0.2–0.3 kg/cm²), there should be no leakage for 72 hours; alternatively, submerge it in a water tank and check for absence of air bubbles;

  • Secure the capsule to the hook using a nylon rope, connect the outlet properly, and reinstall it onto the manhole flange. To prevent oil from entering the capsule, the capsule outlet pipe must be positioned higher than the oil level gauge and explosion-proof device outlets, and all three should be interconnected.

3. Diaphragm-Type Conservator

  • Prior to disassembly and overhaul, perform a sealing test by filling with oil: the diaphragm should withstand a pressure of 0.02–0.04 MPa (0.2–0.3 kg/cm²) without leakage for no less than 72 hours;

  • Disconnect all connecting pipes, remove the middle flange bolts, take off the upper section of the conservator tank, and remove the diaphragm;

  • Other overhaul procedures are basically the same as those for an ordinary conservator;

  • Reassemble the conservator in the reverse order of disassembly.

Give a tip and encourage the author!
Recommended
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
The tap changer operating handle shall be equipped with a protective cover. The flange at the handle shall be well sealed with no oil leakage. Locking screws shall securely fasten both the handle and the drive mechanism, and the handle rotation shall be smooth without binding. The position indicator on the handle shall be clear, accurate, and consistent with the tap voltage regulation range of the winding. Limit stops shall be provided at both extreme positions. The insulating cylinder of the t
Leon
11/04/2025
Why is it difficult to increase the voltage level?
Why is it difficult to increase the voltage level?
The solid-state transformer (SST), also known as a power electronic transformer (PET), uses voltage level as a key indicator of its technological maturity and application scenarios. Currently, SSTs have reached voltage levels of 10 kV and 35 kV on the medium-voltage distribution side, while on the high-voltage transmission side, they remain in the stage of laboratory research and prototype validation. The table below clearly illustrates the current status of voltage levels across different appli
Echo
11/03/2025
Standards and Calculation of LTAC Test for Power Transformers
Standards and Calculation of LTAC Test for Power Transformers
1 IntroductionAccording to the provisions of the national standard GB/T 1094.3-2017, the primary purpose of the line terminal AC withstand voltage test (LTAC) for power transformers is to evaluate the AC dielectric strength from the high-voltage winding terminals to ground. It does not serve to assess inter-turn insulation or phase-to-phase insulation.Compared with other insulation tests (such as full lightning impulse LI or switching impulse SI), the LTAC test imposes a relatively more stringen
Oliver Watts
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.