• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What are the requirements for inspecting and maintaining a transformer's no-load tap changer?

Leon
Leon
Field: Fault Diagnosis
China
  1. The tap changer operating handle shall be equipped with a protective cover. The flange at the handle shall be well sealed with no oil leakage. Locking screws shall securely fasten both the handle and the drive mechanism, and the handle rotation shall be smooth without binding. The position indicator on the handle shall be clear, accurate, and consistent with the tap voltage regulation range of the winding. Limit stops shall be provided at both extreme positions.

  2. The insulating cylinder of the tap changer shall be intact and undamaged, with good insulation properties, and its support bracket shall be firmly secured. The allowable exposure time of the tap changer to air shall be the same as that of the core assembly. If the tap changer is disassembled during maintenance and cannot be reinstalled promptly, it shall be immersed in qualified transformer oil.

  3. All tap changer insulation shall be in good condition, securely bound, neatly arranged, and all joints shall be well soldered with no signs of desoldering or overheating.

  4. The surfaces of all fixed contact posts and moving contact rings shall be smooth, free of oil deposits, oxidation films, or burn marks. The silver-plated layer on the contact surfaces shall show no signs of peeling.

  5. Rotate the tap changer through all tap positions to inspect the contact condition between each moving contact ring and moving contact post, as well as the spring condition. Check the contact pressure—when tested with a feeler gauge, it should not be possible to insert the gauge between the contact surfaces. The contact resistance between any two fixed contact posts shall not exceed 500 μΩ. After inspection, the tap changer shall be returned to its original operating position.

  6. If the tap changer is removed during maintenance, clear markings and records must be made. After reinstallation, the voltage ratio shall be measured and verified.

  7. As part of preventive maintenance, the tap changer shall be rotated annually: move it 10–15 times back and forth from its operating position to remove oil sludge, oxidation films, or other deposits from the contact surfaces through friction. Then return it to the operating position and measure the DC resistance, which must be acceptable (i.e., not higher than the previous measurement result).

Give a tip and encourage the author!
Recommended
UHV Transformer Production: Slow, Precise, Essential
UHV Transformer Production: Slow, Precise, Essential
1. Overview Ultra-high-voltage (UHV) transformers are core equipment in modern power systems. Understanding their voltage ratings, complex structure, precision manufacturing processes, and critical production techniques reveals why they represent the pinnacle of a nation’s power equipment manufacturing capability. Voltage Level DefinitionThe term "ultra-high-voltage transformer" typically refers to transformers used in AC transmission lines rated at 1,000 kV or higher, or DC transmission lines r
Echo
11/11/2025
What causes a transformer to be noisier under no-load conditions?
What causes a transformer to be noisier under no-load conditions?
When a transformer is operating under no-load conditions, it often produces louder noise than under full load. The primary reason is that, with no load on the secondary winding, the primary voltage tends to be slightly higher than nominal. For example, while the rated voltage is typically 10 kV, the actual no-load voltage may reach around 10.5 kV.This elevated voltage increases the magnetic flux density (B) in the core. According to the formula:B = 45 × Et / S(where Et is the designed volts-per-
Noah
11/05/2025
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
When installing an arc suppression coil, it is important to identify the conditions under which the coil should be taken out of service. The arc suppression coil should be disconnected under the following circumstances: When a transformer is being de-energized, the neutral-point disconnector must be opened first before performing any switching operations on the transformer. The energizing sequence is the reverse: the neutral-point disconnector should be closed only after the transformer is energ
Echo
11/05/2025
What fire prevention measures are available for power transformer failures?
What fire prevention measures are available for power transformer failures?
Failures in power transformers are commonly caused by severe overload operation, short circuits due to winding insulation degradation, aging of transformer oil, excessive contact resistance at connections or tap changers, failure of high- or low-voltage fuses to operate during external short circuits, core damage, internal arcing in oil, and lightning strikes.Since transformers are filled with insulating oil, fires can have severe consequences—ranging from oil spraying and ignition to, in extrem
Noah
11/05/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.