12kV 13.2kV 13.8kV 14.5kV 15kV MV outdoor Three phase Smart recloser/reclosure Source Manufacturer

  • 12kV 13.2kV 13.8kV 14.5kV 15kV MV outdoor Three phase Smart recloser/reclosure Source Manufacturer
  • 12kV 13.2kV 13.8kV 14.5kV 15kV MV outdoor Three phase Smart recloser/reclosure Source Manufacturer
  • 12kV 13.2kV 13.8kV 14.5kV 15kV MV outdoor Three phase Smart recloser/reclosure Source Manufacturer

Key attributes

Brand ROCKWILL
Model NO. 12kV 13.2kV 13.8kV 14.5kV 15kV MV outdoor Three phase Smart recloser/reclosure Source Manufacturer
Rated voltage 15kV
Rated normal current 800A
Rated short circuit breaking current 20kA
Power frequency withstand voltage 28kV/min
Rated lightning impulse voltage 95kV
manual closing Yes
Mechanical lock No
Series RCW

Product descriptions from the supplier

Description

Description:

Pioneer of China’s recloser track and the first specialized source manufacturer — that’s who we are after decades of focused efforts. We’ve strengthened our foundation via tech breakthroughs, guided the industry through standard-setting, and built a fully independent full-chain system from core R&D to mass production and delivery.

The RCW  series automatic circuit reclosers can use on overheaddistribution lines as well as distribution substation applications for all voltage classes 11kV up to 38kV at 50/60Hz power system.  and it’s rated current can reach 1250A.The RCW   series automatic circuit reclosers integrates the functions of control, protection, measurement, communication, fault detection, on-line monitoring of closing or opening.The RCW   series vacuum recloser is mainly combined with integration terminal, current transformer, permanent magnetic actuator and it’srecloser controller.

Features:

  • Optional grades available in rated current range.

  • With optional relay protection and logic for user selection.

  • With optional communication protocols and I/O ports for users to choose.

  • PC software for controller testing, setup, programming, updates.

Parameters

The voltage classes of some of these Automatic Reclosers include 6kV, 6.3kV, 6.6kV, 6.9kV, 7.2kV, 10kV, 10.5kV, 11kV, 11.5kV, 12kV, 13.2kV, 13.8kV, 14.5kV, 14.4kV, 15kV, 15.5kV, 15.6kV, 17.5kV, 20kV, 21.9kV, 22kV, 24kV, 30kV, 33kV, 33.5kV, 34.5kV, 35kV, 36kV, 38kV, 38.5kV, 40.5kV, 44kV, 45kV, 46kV, 66kV and 69kV. Rated Short-Circuit Breaking Current includes 8kA, 12.5kA, 16kA, 20kA, 25kA, 31.5kA and customization is available.

Item

Specification

Rated maximum voltage

15kV

Rated maximum current

1250A

Rated frequency

50Hz

Rated short circuit breaking current

16kA

Rated peak value withstand current

40kA

Rated 1min power frequency withstand voltage (Three-phase Epoxy resin pole)

28kV

Rated lightning impulse voltage (Three-phase Epoxy resin pole)

95kV

Operation sequence

C-0.5-CO-2-CO-5-CO (Magnetic actuator)

Mechanical life

n:30000 (Magnetic actuator)

Power supply and operating voltage

110/220V (Customized)

Ratio of current transformer

400/1A (Customized)

Number of voltage sensors (Three-phase Epoxy resin pole)

≤3

Opening time

≤30ms (Magnetic actuator)

Closing time

≤40ms (Magnetic actuator)

Minimum creepage distance

31, level 4 (mm/kV)

Minimum distance between phases

360mm

Potential transformer

110/220V (Customized)

Cable length

6,8,12m (Customized)

Cable clamp (Three-phase Epoxy resin pole)

2-hole NEMA

Lightning arrester

≤6

Mounting type

Single / double column


With optional relay protection & logics for user choice

Instantaneous over-current protection

Timing over-current protection

Negative sequence over-current protection

Directional over-current protection(⁽¹⁾)

Over-voltage protection / Under voltage protection

Programmable protection relay curves (total 10 nos ANSI/IEC curves)

Cold load pickup protection TCC + Hot line tag

Earth protection E/F SEF + Zone- Sequence Co-ordination

More relay functions can be customized

With optional communication protocols & I/O port for user choice

RS-232 and RS-485 ports supporting

DNP3.0 communication protocol support

Modbus communication protocol is optional

IEC 60870-501 communication protocol support

IEC 60870-5-104 communication protocol support

The recloser can communicate through GPRS(or) GSM(or) GPRS/GSM module with English or Specified language

With optional functions for use

Rated currents, System phase current,

Rated voltages, System phase voltage and secondary low voltage power supply voltage Frequency

power (kWh), reactive power (kVarh), power factor

With optional reclosing interval for user pre-program

reclosing times setting support

Dead time setting support

With events recording function

SOE 10000 operations record

Fault record and normal operation record

Note:mean should customized by manufacturer if needed

Environmental requirement:

Maximum temperature:

+40°C

Minimum temperature:

-30°C

Monthly average humidity

95%

Humidity:

90%

Above sea level:

2500m or higher

Ambient air Not apparently polluted by corrosive and flammable gas, vapor


Product show:

不代手合正方形硅橡胶永磁.png

带手合正方形 硅橡胶永磁带手合.png

What is the vacuum arc extinguishing fault of outdoor vacuum recloser and its solution?

Vacuum Arc Quenching Chamber Faults:

  • Decreased Vacuum Level: This is a common issue with vacuum arc quenching chambers. The vacuum arc quenching chamber relies on a high-vacuum environment to extinguish arcs. If the vacuum level decreases, its insulation performance and arc-quenching ability will significantly deteriorate. The causes of decreased vacuum levels can include poor sealing, such as aging or damaged sealing materials, or tiny leaks present during the manufacturing process. When the vacuum level drops to a certain extent, incomplete arc extinction may occur during current interruption, leading to arc reignition and subsequent line faults.

  • Contact Wear: During frequent opening and closing operations, the contacts of the vacuum arc quenching chamber can wear down due to arc erosion. Contact wear increases contact resistance, which can lead to severe heating of the contacts when normal current passes through, affecting the normal operation of the equipment. Additionally, during fault current interruption, the contacts may not withstand the high current, resulting in contact welding or failure to interrupt the current.

Solutions for Vacuum Arc Quenching Chamber Faults:

Vacuum Level Decrease:

  • Detect Vacuum Level: Use specialized vacuum level detection instruments, such as vacuum level testers, to regularly check the vacuum level of the vacuum arc quenching chamber. Once the vacuum level is found to be below the specified value, the vacuum arc quenching chamber should be replaced promptly.

  • Replace Seals: If you suspect that poor sealing is causing the decrease in vacuum level, inspect and replace the seals. When replacing seals, ensure that you use high-quality, compatible sealing materials and follow the correct installation procedures to prevent further leakage.

Contact Wear:

  • Regular Inspection: Regularly inspect the wear condition of the contacts through observation windows or by disassembling the device. Based on the degree of wear, if the wear exceeds the specified limit, the contacts should be replaced promptly.

  • Optimize Operating Parameters: Analyze the causes of contact wear, such as whether it is due to frequent operations or excessive operating current. If the issue is frequent operation, consider optimizing the recloser's reclosing strategy to reduce unnecessary opening and closing operations. If the issue is excessive operating current, check the line load conditions, adjust the protection settings, and avoid subjecting the contacts to excessive current impacts.


Documentation Resource Library
Restricted
BREB 11kV Automatic Circuit Reclose Specification Submission Sheet
Other
English
Consulting
Consulting
Restricted
11kV Automatic Circuit Reclose Standard for Class III in Bangladesh
Other
English
Consulting
Consulting
Restricted
15 kV Pole Mount Auto Recloser Technical Specifications for Guyana Power & Light Incorporated (GPL)
Other
English
Consulting
Consulting
Restricted
15kV Switching Station requirements in Ethiopia
Other
English
Consulting
Consulting
Restricted
15kV/27kV/38kV outdoor auto break vacuum recloser brochure
Brochure
English
Consulting
Consulting
Restricted
10 to 38kV auto vacuum break recloser Catalog
Catalogue
English
Consulting
Consulting
Restricted
15kV automatic recloser technology specification
Technical Data Sheet
English
Consulting
Consulting
FAQ
Q: What are the main technological alternatives for SF6 gas free circuit breakers?
A:

1. Environmentally friendly gas mixed insulation technology
CO ₂ and perfluoroketone/nitrile mixture gases: such as CO ₂/C ₅ - PFK (perfluoroketone) or CO ₂/C ₄ - PFN (perfluoronitrile) mixture gases. These mixed gases combine the arc extinguishing ability of CO ₂ and the high dielectric strength of perfluorinated ketones/nitriles, making them a substitute for SF ₆ in high-voltage applications. For example, CO ₂/C ₄ - PFN mixed gas has been commercially applied in high-voltage circuit breakers, with insulation and breaking performance close to SF ₆, and significantly reduced global warming potential (GWP).
Air and perfluoroketone mixed gas: In medium pressure applications, the mixture of air and C ₅ - PFK can be used as an insulation medium. By optimizing the mixing ratio and pressure, insulation performance comparable to SF ₆ can be achieved while reducing environmental impact.
2. Vacuum circuit breaker technology
Vacuum arc extinguishing chamber: Utilizing the high insulation strength and fast arc extinguishing ability in a vacuum environment, it replaces the arc extinguishing function of SF ₆. Vacuum circuit breakers are widely used in the medium and low voltage fields, especially in scenarios with high environmental requirements. Its advantages are no greenhouse gas emissions and excellent arc extinguishing performance, but it needs to solve problems such as vacuum sealing and contact materials.
Combination of vacuum circuit breaker and gas insulation: In some medium voltage switchgear, vacuum circuit breakers are used as breaking elements, combined with dry air or nitrogen as insulation media, to form environmentally friendly gas insulated switchgear (GIS) that balances insulation and arc extinguishing performance.

Q: What is the difference between vacuum circuit breaker and SF6 circuit breaker?
A:
  1. Their core difference is arc-extinguishing media: Vacuum breakers use high vacuum (10⁻⁴~10⁻⁶Pa) for insulation and arc extinction; SF₆ breakers rely on SF₆ gas, which adsorbs electrons well to quench arcs.
  2. In voltage adaptation: Vacuum breakers fit medium-low voltages (10kV, 35kV; some up to 110kV), rarely 220kV+. SF₆ breakers suit high-ultra high voltages (110kV~1000kV), mainstream for ultra-high voltage grids.
  3. For performance: Vacuum breakers extinguish arcs fast (<10ms), have 63kA~125kA breaking capacity, suit frequent use (e.g., power distribution) with long life (>10,000 cycles). SF₆ breakers excel in stable large/inductive current breaking but work less frequently, needing insulation recovery time post-extinction.
  4. Compared to SF6 gas circuit breakers, vacuum circuit breakers can achieve zero greenhouse gas emissions and are more environmentally friendly because the arc extinguishing device does not contain any gas
Know your supplier
Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m²m² Total staff: 700+ Highest Annual Export(usD): 150000000
Workplace: 108000m²m²
Total staff: 700+
Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: High Voltage Electrical Apparatus/Electric transformer
Whole life care manager
Whole-life care management services for equipment procurement, use, maintenance, and after-sales, ensuring safe operation of electrical equipment, continuous control, and worry-free electricity consumption.
The equipment supplier has passed platform qualification certification and technical evaluation, ensuring compliance, professionalism, and reliability from the source.

Related Products

Related Knowledges

Related Solutions

Haven't found the right supplier yet? Let matching verified suppliers find you. Get Quotation Now
Haven't found the right supplier yet? Let matching verified suppliers find you.
Get Quotation Now
-->
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.