69kV 72.5kV 84kV 88kV Three-phase AC Dead tank type SF6 circuit breaker source manufacturer

  • 69kV 72.5kV 84kV 88kV Three-phase AC Dead tank type SF6 circuit breaker source manufacturer
  • 69kV 72.5kV 84kV 88kV Three-phase AC Dead tank type SF6 circuit breaker source manufacturer

Key attributes

Brand ROCKWILL
Model NO. 69kV 72.5kV 84kV 88kV Three-phase AC Dead tank type SF6 circuit breaker source manufacturer
Rated voltage 72.5kV
Rated normal current 1600A
Rated frequency 50/60Hz
Rated short circuit breaking current 25kA
Series RHD

Product descriptions from the supplier

Description

Description

69kV 72.5kV 84kV 88kV Three-phase AC Dead tank type SF6 circuit breaker is suitable for the rated voltage of 66kV, the rated frequency of 50Hz of the high-voltage transmission and transformation system, through the distribution and combined load current, interrupt the fault current, to achieve the control, measurement and protection of the transmission line, the product structure is compact, the area is small, especially suitable for earthquake-prone areas, polluted areas and areas with relatively small space size. The circuit breaker has excellent breaking performance, and the rated short-circuit breaking current can reach 63kA; The product is easy to install and maintain.

Main Features

  • Excellent breaking performance and long electrical life (>20 operations).

  • Long mechanical life (10,000 cycles), reliable operation, frequent operability, low noise, simple structure, and long maintenance-free period.

  • Low center of gravity, suitable for seismic-prone areas.

  • Out-of-step breaking capability, usable as a tie circuit breaker.

  • Configurable built-in CTs per user requirements, with up to 15 current transformers for measurement or protection.

System Architecture

The gas-insulated metal composite combined electrical appliance (HGIS) is composed of several standard functional modules, such as circuit breaker GCB (single and double busbars), isolation-grounding switch TPS, voltage transformer PT, current transformer CT, etc. These modules have the same interface form and size. Various modules can be combined to meet the design and layout requirements of various substations.

Single-busbar single-isolation scheme

Single-busbar double -isolation scheme

 

Main characteristics:

electrical

 Voltage Ratings: 3.6kV, 4.76kV, 7.2kV, 8.25kV, 11kV, 12kV, 13.2kV, 13.8kV, 15kV, 15.5kV, 17.5kV, 22kV, 22.9kV, 24kV, 25.8kV, 27kV, 33kV, 36kV, 38kV, 40.5kV, 44kV, 60kV, 63kV, 66kV, 69kV, 88kV, 115kV, 123kV, 125kV, 126kV, 132kV, 138kV, 145kV, 150kV, 170kV, 184kV, 204kV, 220kV, 225kV, 230kV, 245kV, 275kV, 330kV, 345kV, 400kV, 765kV, 800kV with a rated short-circuit breaking current of 50kA or 63kA, and we offer customization services.

Item Unit Parameters
Rated maximum voltage kV 72.5
Rated maximum current A 1600/2500/3150/4000
Rated frequency Hz 50/60
1min Power frequency withstand voltage kV 185
Lightning impulse withstand voltage kV 450
First open pole factor
1.5/1.5/1.3
Rated short circuit breaking current kA 25/31.5/40/50/63
Rated short - circuit duration s 4/3
Rated out - of - phase breaking current
10
Rated cable charging current
10/50/125
Rated peak value withstand current kA 80/100/125
Rated making current (peak) kA 80/100/125
Creepage distance mm/kV 25 - 31
SF6 gas leakage rate (per year)
≤1%
Rated SF6 gas pressure(20℃ gauge pressure) Mpa 0.5
Alarm/blocking pressure(20℃ gauge pressure) Mpa 0.45
SF6 annual gas leakage rate
≤0.5
Gas moisture content Ppm(v) ≤150
Heater voltage
AC220/DC220
Voltage of control circuit DC DC110/DC220/DC230
Voltage of energy - store motor V DC 220/DC 110/AC 220/DC230
Applied standards
GB/T 1984/IEC 62271 - 100

mechanical

Name unit Parameters
Opening time ms 27±3
Closing time ms 90±9
Minute and conjunction time ms 300
Together--ivide the time ms ≤60
Simultaneity of opening ms ≤3
Closing simultaneity ms ≤5
Moving contact stroke mm 150+2-4
Contact contact stroke mm 27±4
Opening speed m/s 4.5±0.5
Closing speed m/s 2.5±0.4
Mechanical life times 6000
Operation sequence
O - 0.3s - CO - 180s - CO
Note: The opening and closing speed and time are the characteristic values of the circuitbreaker when it is single divided and closed under rated conditions. The closing speed is theaverage speed of the moving contact from the rigid closing point to 10 ms before closing, andthe opening speed is the average speed of the moving contact within 10 ms from the justequinox to 10 ms after the separation.

Product use environment

  • Place of use: outdoor.

  •  Ambient air temperature: -40℃~ +40℃

  • Altitude: no more than 1000m.

  • Air pollution level: Class IV.

  • Wind pressure: not more than 700Pa (equivalent to wind speed 34 m/s).

  • Earthquake level: no more than 9 degrees.

  • Relative humidity: the average daily relative humidity is not more than 95%; The average monthly relative humidity is not more than 90%.

Note: When the use conditions of the circuit breaker exceed the above provisions, it shall be determined by the user and the manufacturer through negotiation.

Documentation Resource Library
Restricted
RHB Hybird Switchgear Catalog
Catalogue
English
Consulting
Consulting
FAQ
Q: How to choose the voltage level of high-voltage sulfur hexafluoride circuit breaker?
A:

1. Select the circuit breaker corresponding to the voltage level based on the power grid level
The standard voltage (12/24/40.5/72.5/126/170/245/363/420/550/800/1100kV) is matched with the corresponding nominal voltage of the power grid. For example, for a 35kV power grid, a 40.5kV circuit breaker is selected. According to standards such as GB/T 1984/IEC 62271-100, the rated voltage is ensured to be ≥ the maximum operating voltage of the power grid.
2. Applicable scenarios for non-standard customized voltage
Non standard customized voltage (11/22/44/52/132/230/275/300/345/400/380/765kV) is used for special power grids, such as the renovation of old power grids and specific industrial power scenarios. Due to the lack of suitable standard voltage, manufacturers need to customize according to power grid parameters, and after customization, insulation and arc extinguishing performance must be verified.
3. The consequences of selecting the wrong voltage level
Choosing a low voltage level can cause insulation breakdown, leading to SF leakage and equipment damage; Choosing a high voltage level significantly increases costs, increases operational difficulties, and may also result in performance mismatch issues.

Q: What are the core differences between live tank circuit breakers and tank circuit breakers?
A:
  1. The core differences between porcelain column circuit breakers and tank circuit breakers—two main structural types of high-voltage circuit breakers—lie in six key aspects.
  2. Structurally, porcelain column types are supported by porcelain insulation pillars, with open-layout components like arc extinguishing chambers and operating mechanisms. Tank types use metal-sealed tanks to encapsulate and highly integrate all core parts.
  3. For insulation, the former relies on porcelain pillars, air, or composite insulating materials; the latter combines SF₆ gas (or other insulating gases) with metal tanks.
  4. Arc extinguishing chambers are mounted on the top or pillars of porcelain columns for the former, while built inside metal tanks for the latter.
  5. In application, porcelain column types suit outdoor high-voltage distribution with a dispersed layout; tank types adapt flexibly to indoor/outdoor scenarios, especially space-constrained environments.
  6. Maintenance-wise, the former’s exposed components enable targeted repairs; the latter’s sealed structure reduces overall maintenance frequency but requires full inspections for local faults.
  7. Technically, porcelain column types offer intuitive structure and strong anti-pollution flashover performance, while tank types boast excellent sealing, high SF₆ insulation strength, and superior resistance to external interference.
Know your supplier
Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m²m² Total staff: 700+ Highest Annual Export(usD): 150000000
Workplace: 108000m²m²
Total staff: 700+
Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: High Voltage Electrical Apparatus/Electric transformer
Whole life care manager
Whole-life care management services for equipment procurement, use, maintenance, and after-sales, ensuring safe operation of electrical equipment, continuous control, and worry-free electricity consumption.
The equipment supplier has passed platform qualification certification and technical evaluation, ensuring compliance, professionalism, and reliability from the source.

Related Products

Related Knowledges

  • Main Transformer Accidents and Light Gas Operation Issues
    1. Accident Record (March 19, 2019)At 16:13 on March 19, 2019, the monitoring background reported a light gas action of No. 3 main transformer. In accordance with the Code for Operation of Power Transformers (DL/T572-2010), operation and maintenance (O&M) personnel inspected the on-site condition of No. 3 main transformer.On-site confirmation: The WBH non-electrical protection panel of No. 3 main transformer reported a Phase B light gas action of the transformer body, and the reset was ineff
    02/05/2026
  • Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
    Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
    01/30/2026
  • Neutral point grounding operation mode for 110kV~220kV power grid transformers
    The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
    01/29/2026
  • Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
    Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
    01/29/2026
  • Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
    Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
    01/29/2026
  • Understanding Transformer Neutral Grounding
    I. What is a Neutral Point?In transformers and generators, the neutral point is a specific point in the winding where the absolute voltage between this point and each external terminal is equal. In the diagram below, pointOrepresents the neutral point.II. Why Does the Neutral Point Need Grounding?The electrical connection method between the neutral point and earth in a three-phase AC power system is called theneutral grounding method. This grounding method directly affects:The safety, reliabilit
    01/29/2026

Related Solutions

  • Intelligent Operation Solution for 12kV Vacuum Circuit Breakers: Integrating Real-time Monitoring & Lifetime Optimization
    Ⅰ. Equipment Operation & MaintenanceIntelligent Monitoring System Integration​Multi-parameter Real-time Monitoring: Embedded sensors (temperature, displacement, Hall effect current sensors) track contact temperature rise, mechanical characteristics (opening/closing speed, overtravel), coil current, and partial discharge signals. Data undergoes preprocessing via edge computing prior to cloud upload.​Lifetime Prediction Model: Dynamically evaluates remaining lifespan using electrical wear data
    06/10/2025
  • SF6 Circuit Breaker Solutions for Outdoor Installation (Anti-Pollution & Seismic Resistance)
    I.Core Challenges in Outdoor Installation​In high-voltage transmission and distribution systems, SF6 circuit breakers are exposed to complex outdoor environments for extended periods, facing the following critical issues:​Pollution & Insulation Degradation​Dust, salt fog, and industrial pollutants in outdoor environments easily adhere to equipment surfaces. In coastal or industrial areas, pollution levels may reach ​Class IV, resulting in insufficient creepage distance and triggering ​flasho
    05/12/2025
  • 12kV Indoor Vacuum Circuit Breaker Southeast Asia Solution: Anti-Corrosion Compact Design
    12kV Indoor Vacuum Circuit Breaker Southeast Asia Solution: Anti-Corrosion Compact DesignⅠ. Executive Summary​Southeast Asia faces rapidly growing electricity demand alongside environmental challenges including high temperatures, humidity, salt spray corrosion, and grid instability. This solution recommends ​Solid Insulated Pole-Mounted Vacuum Circuit Breakers (VCB)​​ featuring ​high reliability, ​compact design, and ​smart monitoring. Tailored for tropical climates and industrial scenarios, it
    06/10/2025
Haven't found the right supplier yet? Let matching verified suppliers find you. Get Quotation Now
Haven't found the right supplier yet? Let matching verified suppliers find you.
Get Quotation Now
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.