• IEC Rear Connector With Surge Arrester
  • IEC Rear Connector With Surge Arrester
  • IEC Rear Connector With Surge Arrester
IEC Rear Connector With Surge Arrester
discuss personally
Model
RW-HBLQ-51kV
RW-HBLQ-24kV
RW-HBLQ-17kV
Basic info
Brand Switchgear parts
Model NO. IEC Rear Connector With Surge Arrester
Rated voltage 17kV
Series RW-HBLQ
Product Detail

Summary
IEC Rear connector with surge arrester can provide reliable over-voltage protection for the electrical system. The external semi conductive Layers of screened type IEC Rear connector with surge arrester to ensure protect the operators when installation and maintenance,and also ensure the equipments in safetyAt the same time, its anti ultraviolet,anti-aging, waterproof, moisture-proof unique properties to ensure that the product in a harsh environment safe and reliable operation.

Standard packing
Body of surge arrester                                   Test report
Silicone grease、towels                               Bolt stud
Instruction Manual                                         Dust cap
Conductive rod                                                Conformity certificat

Technical specification

Item

Units

RW-HBLQ-17/45

RW-HBLQ-17/50

RW-HBLQ-10/27

RW-HBLQ-10/30

RW-HBLQ-13/36

Product model

-

RW-HBLQ-17/45

RW-HBLQ-17/50

RW-HBLQ-10/27

RW-HBLQ-10/30

RW-HBLQ-13/36

Nominal voltage of a system

kV

10

10

6

6

10

Rated voltage of arrester

kV

17

17

10

10

13

Continuous running voltage

kV

13.6

13.6

8

8

10.4

Nominal discharge current In

kA

5

5

5

5

5

Dc 1mA reference voltage

kV

≥24

≥25

≥14.4

≥15

≥19.3

0.75U1mA leakage current

μA

≤10

≤10

≤10

≤10

≤10

Steep current impulse residual voltage

kV

≤57.8

≤57.5

≤31

≤34.6

≤41.3

Lightning impulse residual voltage

kV

≤45

≤50

≤27

≤30

≤36

Operating impulse residual voltage

kV

≤35

≤42.5

≤23

≤25.6

≤30.7

Partial discharge at 15kV

pC

≤10

≤10

≤10

≤10

≤10

2ms square wave impulse current tolerance

kA

150

150

150

150

150

High current shock tolerance

kA

65

65

65

65

65

Units RW-HBLQ-26/66 RW-HBLQ-32/85 RW-HBLQ-34/85 RW-HBLQ-34/90  
Product model - RW-HBLQ-26/66 RW-HBLQ-32/85 RW-HBLQ-34/85 RW-HBLQ-34/90
Nominal voltage of a system kV 20 20 20 20
Rated voltage of arrester kV 26 32 34 34
Continuous running voltage kV 20.8 25.6 27.2 27.2
Nominal discharge current In kA 5 5 5 5
Dc 1mA reference voltage kV ≥37 ≥47 ≥48 ≥50
0.75U1mA leakage current μA ≤10 ≤10 ≤10 ≤10
Steep slope impact residual voltage kV ≤76 ≤95 ≤95 ≤104
Lightning impulse residual voltage kV ≤66 ≤85 ≤85 ≤90
Operating impulse residual voltage kV ≤56 ≤75 ≤75 ≤80
25.4kV Partial discharge pC ≤10 ≤10 ≤10 ≤10
2ms square wave impact current tolerance A 150 150 150 150
High current shock tolerance kA 65 65 65 65
Item Units RW-HBLQ-51/134/400 RW-HBLQ-51/134/600 RW-HBLQ-51/134/800
Product model - RW-HBLQ-51/134/400 RW-HBLQ-51/134/600 RW-HBLQ-51/134/800
Nominal voltage of a system kV 35 35 35
Rated voltage of arrester kV 51 51 51
Continuous running voltage kV 40.8 40.8 40.8
Nominal discharge current kA 5 5 5
Dc 1mA reference voltage kV ≥73 ≥73 ≥73
0.75U1mA leakage current μA ≤10 ≤10 ≤10
Steep slope impact residual voltage kV ≤154 ≤154 ≤154
Lightning impulse residual voltage kV ≤134 ≤134 ≤134
Operating impulse residual voltage kV ≤114 ≤114 ≤114
Partial discharge at 45kV pC ≤10 ≤10 ≤10
2ms square wave impact current tolerance A 400 600 800
High current shock tolerance kA 100 100 100

 

Note: When Selection,Please indicate the lightning impulse residual voltage value.

 

Know your supplier
Switchgear parts
VoltEdge Solutions​​ specializes in manufacturing premium ​​MV switchgear accessories​​ for global power distribution systems. Our product range includes circuit breaker modules, disconnector spares, and surge arrestors, engineered for ​​24kV+ substations​​ and renewable energy plants. With ISO-certified production and 24/7 technical support, we ensure ​​reliability, compliance​​ with IEC standards, and rapid global supply.
Main Categories
Electrical fittings/Equipment Parts
Business Type
Sales
Highest Annual Export (USD)
$300000000
Professional Experience
1 years
Workplace
1000m²
占位
占位
Related Products
Related Knowledges
What are the accident scenarios in a substation?
What are the accident scenarios in a substation?
Handling of Minor Action of Transformer Gas RelayImmediately check and record the protective relay action signals, and report to the dispatcher and station manager.Closely monitor the transformer’s voltage, current, temperature, oil level, oil color, sound, and cooler operation, and assign personnel to conduct an external inspection of the transformer.If significant abnormalities are found during the inspection, report to the dispatcher and take the faulty transformer offline. If no obviou
Leon
07/30/2025
Power System Voltage Level Classification
Power System Voltage Level Classification
What Is a Voltage Class?Definition of Voltage Class:Voltage classes (or voltage levels) refer to a set of standardized rated voltages used in power systems and electrical equipment. A rated voltage is the nominal voltage at which equipment is designed to operate under normal conditions; essentially, a voltage class defines the intended working voltage range for a system or device.Analogy to Consumer Appliances:Household appliances (e.g., refrigerators, TVs) operate at a nominal voltage—typ
Vziman
07/30/2025
What is the reason for conducting five impulse tests before commissioning a transformer?
What is the reason for conducting five impulse tests before commissioning a transformer?
Verification of Insulation IntegrityWhen a new or overhauled transformer is energized under open-circuit (no-load) conditions, switching surges—caused by operations such as opening or closing the no-load transformer circuit—can generate overvoltages. These reach 4.0–4.5 times the phase voltage if the neutral point is isolated or earthed through a Petersen coil, and up to 3.0 times the phase voltage when the neutral is solidly grounded. The full-voltage, no-load impact test deli
Rockwell
07/30/2025
Analysis of the Causes of Large - scale Failures of Surge Arresters in 10 kV Distribution Lines
Analysis of the Causes of Large - scale Failures of Surge Arresters in 10 kV Distribution Lines
1. IntroductionDuring power system operation, main equipment faces threats from internal and atmospheric overvoltages. Surge arresters, especially metal oxide arresters (MOAs) with excellent nonlinear volt - ampere characteristics, are key for protection due to their good performance, large current - carrying capacity, and strong pollution resistance. However, long - term exposure to power frequency voltages, along with component quality, manufacturing processes, and external environments, makes
Leon
07/30/2025
Key Points of Online Monitoring Technology for Zinc Oxide Surge Arresters
Key Points of Online Monitoring Technology for Zinc Oxide Surge Arresters
1 Architecture of the Online Monitoring System for Zinc Oxide Surge ArrestersThe online monitoring system for zinc oxide surge arresters comprises three layers: the station control layer, bay layer, and process layer.Station Control Layer: Includes a monitoring center, a Global Positioning System (GPS) clock, and a B - code clock source.Bay Layer: Consists of online monitoring Intelligent Electronic Devices (IEDs).Process Layer: Features monitoring terminals for Potential Transformers (PTs) and
Oliver Watts
07/30/2025
Improvement and Application of the Test Device for Surge Arrester Online Monitor
Improvement and Application of the Test Device for Surge Arrester Online Monitor
1 Significance of Surge Arrester Online Monitors1.1 Enhance Power System Safety, Reduce Lightning DamageDuring lightning strikes, surge arresters play a core role in discharging overvoltage. Online monitors ensure arrester stability, detect potential faults in real - time, and trigger alarms for timely intervention—effectively reducing lightning - induced damage to power equipment and systems, and maintaining stable operation.1.2 Real - Time Status Monitoring, Improve Maintenance Efficienc
Edwiin
07/30/2025
×
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!