Isolation operating mechanism on 12kV environmental protection cabinet (air insulated without SF6 gas)

  • Isolation operating mechanism on 12kV environmental protection cabinet (air insulated without SF6 gas)

Key attributes

Brand Xinyouxiang
Model NO. Isolation operating mechanism on 12kV environmental protection cabinet (air insulated without SF6 gas)
Rated voltage 12kV
Rated normal current 630A
Rated frequency 50/60Hz
Series GHK-J12
Description

Theisolation operating mechanism on the GHK-J12 environmental protection cabinet is equipped with a GHK-J12 circuit breaker reclosing spring operating mechanism, and the isolation part is equipped with a RNHSG-07 compression spring isolation operating mechanism. The isolation machinery is a forward type, and the V operating mechanism is a reverse type. It adopts a single rod mechanical structure to achieve interlocking with the lower door. Only when the main circuit is in the open state and reliably grounded, can the interlocking return position open the lower door. The overall structure of the mechanism is compact, and the operation interlocking meets the five prevention requirements. The operating mechanism complies with the relevant requirements of standards such as GB1984-2014, GB/T1022-2020, GB3804-2017, GB3906-2020, etc.

Operation of opening and closing the mechanism

Power transmission operation:
①. Close the door; ②. Insert the handle into the grounding operation hole of the G mechanism and operate counterclockwise to separate the locking/grounding of the lower door; ③. Insert the handle into the isolation operation hole of the G mechanism and operate counterclockwise to close the isolation switch; ④. Insert the handle into the energy storage operation hole of the V mechanism and operate clockwise to store energy in the circuit breaker; ⑤. Press the green button on the V mechanism to close the circuit breaker switch.
Power outage operation:
①. Press the red button on the V mechanism to open the circuit breaker switch; ②. Insert the handle into the isolation operation hole of the G mechanism and operate clockwise to open the isolation switch; ③. Insert the handle into the grounding operation hole of the G mechanism and operate clockwise to close the grounding switch; ④. Insert the handle into the energy storage operation hole of the V mechanism and operate clockwise to store energy in the circuit breaker; ⑤. Press the green button on the V mechanism to close the circuit breaker switch, and only then can the lower door be opened.

Product Parameters

Serial Number

Item

Unit

Parameter

1

Voltage Level

V

AC/DC220; AC/DC110; DC48; DC24

2

Rated Power

W

40

3

Operating Environment

-40~+40

4

Power Frequency Withstand Voltage

kv

2/1min

5

Normal Operating Voltage Range of Closing Coil

UL

85%~110%

6

Normal Operating Voltage Range of Opening Coil

UL

65%~110%

7

Low Voltage Operating Range

UL

≤30% (no operation for 3 times of closing and opening)

8

Salt Spray Resistance Grade

h

96

Installation dimensions

FAQ for Spring operating mechanism

Q: What is an eco-cabinet top-mounted isolation mechanism and its core role?
A:

 It is a key electrical component installed on the upper part of SF6-free air-insulated eco-cabinets, integrating isolation switch and operating mechanism functions. Its core roles include three aspects: ① Reliable isolation: Create a visible insulation gap between the live busbar and maintenance components to ensure the safety of equipment inspection and maintenance; ② Safety interlocking: Realize mechanical interlock with cabinet doors, main circuit breakers and earthing switches to avoid misoperations such as live isolation and closing with earthing; ③ Space optimization: Installed on the upper part of the cabinet, it does not occupy the lower functional module space, which is suitable for compact eco-cabinet design. It is widely used in 10kV/12kV medium-voltage distribution systems and fully complies with environmental protection policies of SF6 restriction.

Q: Why does the top-mounted isolation mechanism of eco-cabinet adopt air insulation instead of SF6?
A:

The choice of air insulation is based on environmental protection policies and application scenarios, with three core reasons: ① Environmental protection compliance: SF6 is a strong greenhouse gas (GWP is 23900 times that of CO₂), and its use is strictly restricted by international policies such as the Paris Agreement. Air insulation has zero greenhouse effect and no toxic decomposition products; ② Maintenance-free feature: Air insulation has a simple structure, no gas leakage risk, and no need for regular gas pressure detection and replenishment, reducing operation and maintenance costs by more than 30% compared with SF₆-insulated products; ③ Cost advantage: Air insulation does not require SF6 gas recovery and treatment equipment, which reduces the overall cost of the cabinet. For 10kV/12kV medium-voltage systems, the insulation performance of air can fully meet the standard requirements

Know your supplier

Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 1000m² Total staff: 100 Highest Annual Export(usD): 300000000
Services
Business Type: Sales