Methods of Voltage Control in Power System

Edwiin
03/26/2025

Methods of Voltage Control in Power System

The voltage within a power system is subject to variation in accordance with load fluctuations. Typically, the voltage is elevated during light - load periods and reduced under heavy - load conditions. To maintain the system voltage within acceptable limits, additional equipment is necessary. This equipment serves to increase the voltage when it is low and decrease it when it is overly high. The following are the methods employed in power systems for voltage control:​

  • On - Load Tap Changing Transformer​
  • Off - Load Tap Changing Transformer​
  • Shunt Reactors​
  • Synchronous Phase Modifiers​
  • Shunt Capacitor​
  • Static VAR System (SVS)​

Controlling the system voltage with the aid of a shunt inductive element is referred to as shunt compensation. Shunt compensation is categorized into two types: static shunt compensation and synchronous compensation. In static shunt compensation, shunt reactors, shunt capacitors, and static VAR systems are utilized, while synchronous compensation makes use of synchronous phase modifiers. The methods for voltage control are elaborated in detail below.​

Off - Load Tap Changing Transformer: In this approach, voltage control is achieved by altering the turns ratio of the transformer. Before changing the tap, the transformer must be disconnected from the power supply. Tap - changing of the transformer is predominantly carried out manually.​

On - Load Tap Changing Transformer: This configuration is used to adjust the turns ratio of the transformer for regulating the system voltage while the transformer is delivering load. The majority of power transformers are equipped with on - load tap changers.​

Shunt Reactor: A shunt reactor is an inductive current element connected between the line and the neutral. It compensates for the inductive current originating from transmission lines or underground cables. Shunt reactors are primarily used in long - distance Extra - High - Voltage (EHV) and Ultra - High - Voltage (UHV) transmission lines for reactive power control.​

Shunt reactors are installed in the sending - end substation, receiving - end substation, and intermediate substations of long EHV and UHV lines. In long - distance transmission lines, shunt reactors are connected at intervals of approximately 300 km to limit the voltage at intermediate points.​

Shunt Capacitors: Shunt capacitors are capacitors connected in parallel with the line. They are installed at receiving - end substations, distribution substations, and switching substations. Shunt capacitors inject reactive volt - amperes into the line and are typically arranged in three - phase banks.​

Synchronous Phase Modifier: A synchronous phase modifier is a synchronous motor operating without a mechanical load. It is connected to the load at the receiving end of the line. By varying the excitation of the field winding, the synchronous phase modifier can either absorb or generate reactive power. It maintains a constant voltage under all load conditions and also improves the power factor.​
Static VAR Systems (SVS): The static VAR compensator injects or absorbs inductive VAR into the system when the voltage deviates from the reference value, either higher or lower. In a static VAR compensator, thyristors are used as switching devices instead of circuit breakers. In modern systems, thyristor switching has replaced mechanical switching due to its faster operation and the ability to provide transient - free operation through switching control.

Edwiin

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

Working Voltage in Power System
Working Voltage in Power System
Working VoltageThe term "working voltage" refers to the maximum voltage that a device can withstand without sustaining damage or burning out, while ensuring the reliability, safety, and proper operation of both the device and associated circuits.For long-distance power transmission, the use of high voltage is advantageous. In AC systems, maintaining a load power factor as close to unity as possible is also economically necessary. Practically, heavy currents are more challenging to handle than hi
Encyclopedia
07/26/2025
Difference Between Shunt and Series Voltage Regulator
Difference Between Shunt and Series Voltage Regulator
Linear voltage regulators are mainly classified into two types: shunt voltage regulators and series voltage regulators. The key difference between them lies in the connection of the control element: in a shunt voltage regulator, the control element is connected in parallel with the load; in contrast, in a series voltage regulator, the control element is connected in series with the load. These two types of voltage regulator circuits operate on different principles and thus have their own advanta
Edwiin
07/25/2025
Frequency division method for measuring grid-to-ground insulation parameters
Frequency division method for measuring grid-to-ground insulation parameters
The frequency division method enables the measurement of grid-to-ground parameters by injecting a current signal of a different frequency into the open delta side of the potential transformer (PT).This method is applicable to ungrounded systems; however, when measuring the grid-to-ground parameters of a system where the neutral point is grounded via an arc suppression coil, the arc suppression coil must be disconnected from operation beforehand. Its measurement principle is shown in Figure 1.As
Leon
07/25/2025
The insulation parameters of the power grid to ground are measured by the tuning method
The insulation parameters of the power grid to ground are measured by the tuning method
The tuning method is suitable for measuring the ground parameters of systems where the neutral point is grounded via an arc suppression coil, but not applicable to ungrounded neutral point systems. Its measurement principle involves injecting a current signal with continuously varying frequency from the secondary side of the Potential Transformer (PT), measuring the returned voltage signal, and identifying the system's resonant frequency.During the frequency sweeping process, each injected heter
Leon
07/25/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!