• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Sequence Network

Encyclopedia
Field: Encyclopedia
0
China

Sequence Network

Definition

The sequence impedance network is defined as an equivalent balanced network for a balanced power system under a hypothetical operating condition, where only a single sequence component of voltage and current exists within the system. Symmetrical components play a crucial role in calculating unsymmetrical faults at various nodes of a power system network. Additionally, the positive sequence network is fundamental for load flow studies in power systems. 

Every power system comprises three sequence networks: the positive, negative, and zero sequence networks, each carrying distinct sequence currents. These sequence currents interact in specific ways to model different unbalanced fault scenarios. By calculating these sequence currents and voltages during a fault, the actual currents and voltages in the system can be accurately determined.

Characteristics of Sequence Networks

During the analysis of symmetrical faults, the positive sequence network takes precedence. It is identical to the sequence reactance or impedance network. The negative sequence network shares a similar structure with the positive sequence network; however, its impedance values have opposite signs compared to those of the positive sequence network. In the zero sequence network, the internal part is isolated from the fault point, and the current flow is solely driven by the voltage at the fault location.

Sequence Network for Fault Calculation

A fault in the power system disrupts its balanced operation, plunging it into an unbalanced state. This unbalanced condition can be represented by a combination of a balanced positive sequence set, a symmetrical negative sequence set, and a single - phase zero sequence set. When a fault occurs, it is conceptually equivalent to injecting these three sequence sets into the system simultaneously. The post - fault voltages and currents are then determined by the system's response to each of these component sets.

To analyze the system's response accurately, the three sequence components are indispensable. Assume that each sequence network can be replaced by a Thevenin's equivalent circuit between two key points. Through simplification, each sequence network can be reduced to a single - voltage source in series with a single impedance, as illustrated in the figure below. The sequence network is typically depicted as a box, where one terminal represents the fault point, and the other corresponds to the zero potential of the reference bus N.

image.png

In the positive sequence network, the Thevenin voltage is equivalent to the open - circuit voltage VF at point F. This voltage VF represents the pre - fault voltage of phase a at the fault location F, and is also denoted by Eg. In contrast, the Thevenin voltages in the negative and zero sequence networks are zero. This is because, within a balanced power system, the negative and zero sequence voltages at the fault point are inherently zero.

The current Ia flows from the power system into the fault. Consequently, its symmetrical components Ia0, Ia1, and Ia2 flow away from the fault point F. The symmetrical components of the voltage at the fault point can be expressed as follows:

image.png

Where Z0, Z1 and the Z2 are the total equivalent impedance of the zero, positive and negative sequence network up to the fault point.

Give a tip and encourage the author!

Recommended

Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
01/29/2026
Understanding Transformer Neutral Grounding
I. What is a Neutral Point?In transformers and generators, the neutral point is a specific point in the winding where the absolute voltage between this point and each external terminal is equal. In the diagram below, pointOrepresents the neutral point.II. Why Does the Neutral Point Need Grounding?The electrical connection method between the neutral point and earth in a three-phase AC power system is called theneutral grounding method. This grounding method directly affects:The safety, reliabilit
01/29/2026
Voltage Imbalance: Ground Fault, Open Line, or Resonance?
Single-phase grounding, line break (open-phase), and resonance can all cause three-phase voltage unbalance. Correctly distinguishing among them is essential for rapid troubleshooting.Single-Phase GroundingAlthough single-phase grounding causes three-phase voltage unbalance, the line-to-line voltage magnitude remains unchanged. It can be classified into two types: metallic grounding and non-metallic grounding. Inmetallic grounding, the faulted phase voltage drops to zero, while the other two phas
11/08/2025
Composition and Working Principle of Photovoltaic Power Generation Systems
Composition and Working Principle of Photovoltaic (PV) Power Generation SystemsA photovoltaic (PV) power generation system is primarily composed of PV modules, a controller, an inverter, batteries, and other accessories (batteries are not required for grid-connected systems). Based on whether it relies on the public power grid, PV systems are divided into off-grid and grid-connected types. Off-grid systems operate independently without relying on the utility grid. They are equipped with energy-s
10/09/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.