Symmetrical & Unsymmetrical Faults

Encyclopedia
04/25/2025

Under normal operating conditions, a power system functions in a balanced state, with electrical parameters such as voltage and current distributed evenly across all phases. However, when insulation fails at any point within the system or live wires come into unintended contact, the system's balance is disrupted, leading to a short - circuit or fault in the line. Faults in power systems can be triggered by a multitude of factors. Natural phenomena like lightning strikes, powerful high - speed winds, and earthquakes can physically damage electrical infrastructure and cause insulation breakdown. Additionally, external events such as trees falling onto power lines, birds creating electrical shorts by bridging conductors, or the degradation of insulation materials over time can also initiate faults.

Faults that occur in transmission lines are typically categorized into two broad types:

Symmetrical Faults

Symmetrical faults involve the simultaneous short - circuiting of all phases within a multi - phase electrical system, often with a connection to the earth as well. What characterizes these faults is their balanced nature; even after the fault occurs, the system maintains its symmetry. In a three - phase setup, for example, the electrical relationships between the phases remain consistent, with the lines effectively displaced by an equal angle of 120°. Despite being relatively rare, symmetrical faults are the most severe type of electrical faults in power systems, as they generate extremely high fault currents. These large - magnitude currents can cause significant damage to equipment and disrupt power supply if not properly managed. Due to their severity and the challenges they pose, engineers perform balanced short - circuit calculations specifically designed to accurately determine the magnitude of these large currents. This information is crucial for designing protective devices, such as circuit breakers, that can safely interrupt the flow of current during a symmetrical fault and safeguard the integrity of the power system.

image.png

Unsymmetrical Faults

Unsymmetrical faults are characterized by their involvement of only one or two phases within a power system, leading to an imbalance among the three - phase lines. These faults typically manifest as connections either between a line and the ground (line - to - ground) or between two lines (line - to - line). An unsymmetrical series fault occurs when there is an abnormal connection between phases or between a phase and the ground, while an unsymmetrical shunt fault is identified by an imbalance in the line impedances.

In a three - phase electrical system, shunt faults can be further classified as follows:

  • Single Line - to - Ground Fault (LG): This fault occurs when one of the conductors makes contact with the ground or the neutral conductor.

  • Line - to - Line Fault (LL): Here, two conductors are short - circuited, disrupting the normal current flow.

  • Double Line - to - Ground Fault (LLG): In this scenario, two conductors come into contact with the ground or the neutral conductor simultaneously.

  • Three - Phase Short - Circuit Fault (LLL): All three phases are short - circuited to each other.

  • Three - Phase - to - Ground Fault (LLLG): All three phases are short - circuited to the ground.

It's important to note that LG, LL, and LLG faults are unsymmetrical, while LLL and LLLG faults fall under the category of symmetrical faults. Given the significant currents generated during symmetrical faults, engineers perform balanced short - circuit calculations to accurately determine these high - magnitude currents, which is essential for designing effective protective measures.

Effect of Faults on Transmission Lines

Faults can have a detrimental impact on power systems in multiple ways. When a fault occurs, it often causes a significant increase in voltages and currents at specific points within the system. These elevated electrical values can damage the insulation of equipment, thereby reducing its lifespan and potentially leading to costly repairs or replacements. Moreover, faults can undermine the stability of the power system, causing three - phase equipment to operate inefficiently or even malfunction. To prevent the spread of damage and ensure the uninterrupted operation of the overall system, it is crucial to promptly isolate the faulty section as soon as a fault is detected. By disconnecting the affected area, the normal operation of the remaining parts of the power system can be maintained, minimizing the impact on power supply and reducing the risk of further failures.

Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

Working Voltage in Power System
Working Voltage in Power System
Working VoltageThe term "working voltage" refers to the maximum voltage that a device can withstand without sustaining damage or burning out, while ensuring the reliability, safety, and proper operation of both the device and associated circuits.For long-distance power transmission, the use of high voltage is advantageous. In AC systems, maintaining a load power factor as close to unity as possible is also economically necessary. Practically, heavy currents are more challenging to handle than hi
Encyclopedia
07/26/2025
Frequency division method for measuring grid-to-ground insulation parameters
Frequency division method for measuring grid-to-ground insulation parameters
The frequency division method enables the measurement of grid-to-ground parameters by injecting a current signal of a different frequency into the open delta side of the potential transformer (PT).This method is applicable to ungrounded systems; however, when measuring the grid-to-ground parameters of a system where the neutral point is grounded via an arc suppression coil, the arc suppression coil must be disconnected from operation beforehand. Its measurement principle is shown in Figure 1.As
Leon
07/25/2025
The insulation parameters of the power grid to ground are measured by the tuning method
The insulation parameters of the power grid to ground are measured by the tuning method
The tuning method is suitable for measuring the ground parameters of systems where the neutral point is grounded via an arc suppression coil, but not applicable to ungrounded neutral point systems. Its measurement principle involves injecting a current signal with continuously varying frequency from the secondary side of the Potential Transformer (PT), measuring the returned voltage signal, and identifying the system's resonant frequency.During the frequency sweeping process, each injected heter
Leon
07/25/2025
Effect of Transition Resistance at the Grounding Point on the Rising Speed of Zero - sequence Voltage
Effect of Transition Resistance at the Grounding Point on the Rising Speed of Zero - sequence Voltage
In an arc - suppression coil grounding system, the rising speed of the zero - sequence voltage is greatly affected by the value of the transition resistance at the grounding point. The larger the transition resistance at the grounding point, the slower the rising speed of the zero - sequence voltage.In an ungrounded system, the transition resistance at the grounding point has basically no impact on the rising speed of the zero - sequence voltage.Simulation Analysis: Arc - suppression Coil Ground
Leon
07/24/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!