• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Symmetrical & Unsymmetrical Faults

Encyclopedia
Field: Encyclopedia
0
China

Under normal operating conditions, a power system functions in a balanced state, with electrical parameters such as voltage and current distributed evenly across all phases. However, when insulation fails at any point within the system or live wires come into unintended contact, the system's balance is disrupted, leading to a short - circuit or fault in the line. Faults in power systems can be triggered by a multitude of factors. Natural phenomena like lightning strikes, powerful high - speed winds, and earthquakes can physically damage electrical infrastructure and cause insulation breakdown. Additionally, external events such as trees falling onto power lines, birds creating electrical shorts by bridging conductors, or the degradation of insulation materials over time can also initiate faults.

Faults that occur in transmission lines are typically categorized into two broad types:

Symmetrical Faults

Symmetrical faults involve the simultaneous short - circuiting of all phases within a multi - phase electrical system, often with a connection to the earth as well. What characterizes these faults is their balanced nature; even after the fault occurs, the system maintains its symmetry. In a three - phase setup, for example, the electrical relationships between the phases remain consistent, with the lines effectively displaced by an equal angle of 120°. Despite being relatively rare, symmetrical faults are the most severe type of electrical faults in power systems, as they generate extremely high fault currents. These large - magnitude currents can cause significant damage to equipment and disrupt power supply if not properly managed. Due to their severity and the challenges they pose, engineers perform balanced short - circuit calculations specifically designed to accurately determine the magnitude of these large currents. This information is crucial for designing protective devices, such as circuit breakers, that can safely interrupt the flow of current during a symmetrical fault and safeguard the integrity of the power system.

image.png

Unsymmetrical Faults

Unsymmetrical faults are characterized by their involvement of only one or two phases within a power system, leading to an imbalance among the three - phase lines. These faults typically manifest as connections either between a line and the ground (line - to - ground) or between two lines (line - to - line). An unsymmetrical series fault occurs when there is an abnormal connection between phases or between a phase and the ground, while an unsymmetrical shunt fault is identified by an imbalance in the line impedances.

In a three - phase electrical system, shunt faults can be further classified as follows:

  • Single Line - to - Ground Fault (LG): This fault occurs when one of the conductors makes contact with the ground or the neutral conductor.

  • Line - to - Line Fault (LL): Here, two conductors are short - circuited, disrupting the normal current flow.

  • Double Line - to - Ground Fault (LLG): In this scenario, two conductors come into contact with the ground or the neutral conductor simultaneously.

  • Three - Phase Short - Circuit Fault (LLL): All three phases are short - circuited to each other.

  • Three - Phase - to - Ground Fault (LLLG): All three phases are short - circuited to the ground.

It's important to note that LG, LL, and LLG faults are unsymmetrical, while LLL and LLLG faults fall under the category of symmetrical faults. Given the significant currents generated during symmetrical faults, engineers perform balanced short - circuit calculations to accurately determine these high - magnitude currents, which is essential for designing effective protective measures.

Effect of Faults on Transmission Lines

Faults can have a detrimental impact on power systems in multiple ways. When a fault occurs, it often causes a significant increase in voltages and currents at specific points within the system. These elevated electrical values can damage the insulation of equipment, thereby reducing its lifespan and potentially leading to costly repairs or replacements. Moreover, faults can undermine the stability of the power system, causing three - phase equipment to operate inefficiently or even malfunction. To prevent the spread of damage and ensure the uninterrupted operation of the overall system, it is crucial to promptly isolate the faulty section as soon as a fault is detected. By disconnecting the affected area, the normal operation of the remaining parts of the power system can be maintained, minimizing the impact on power supply and reducing the risk of further failures.

Give a tip and encourage the author!

Recommended

Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
01/29/2026
Understanding Transformer Neutral Grounding
I. What is a Neutral Point?In transformers and generators, the neutral point is a specific point in the winding where the absolute voltage between this point and each external terminal is equal. In the diagram below, pointOrepresents the neutral point.II. Why Does the Neutral Point Need Grounding?The electrical connection method between the neutral point and earth in a three-phase AC power system is called theneutral grounding method. This grounding method directly affects:The safety, reliabilit
01/29/2026
Voltage Imbalance: Ground Fault, Open Line, or Resonance?
Single-phase grounding, line break (open-phase), and resonance can all cause three-phase voltage unbalance. Correctly distinguishing among them is essential for rapid troubleshooting.Single-Phase GroundingAlthough single-phase grounding causes three-phase voltage unbalance, the line-to-line voltage magnitude remains unchanged. It can be classified into two types: metallic grounding and non-metallic grounding. Inmetallic grounding, the faulted phase voltage drops to zero, while the other two phas
11/08/2025
Composition and Working Principle of Photovoltaic Power Generation Systems
Composition and Working Principle of Photovoltaic (PV) Power Generation SystemsA photovoltaic (PV) power generation system is primarily composed of PV modules, a controller, an inverter, batteries, and other accessories (batteries are not required for grid-connected systems). Based on whether it relies on the public power grid, PV systems are divided into off-grid and grid-connected types. Off-grid systems operate independently without relying on the utility grid. They are equipped with energy-s
10/09/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.