Critical Clearing Angle

Encyclopedia
05/12/2025

The critical clearing angle is defined as the maximum allowable variation in the load angle curve during a fault, beyond which system synchronism is lost if the fault is not cleared. In essence, when a fault occurs in an electrical system, the load angle begins to increase, putting the system at risk of instability. The specific angle at which clearing the fault restores system stability is referred to as the critical clearing angle.

For a given initial load condition, there exists a specific critical clearing angle. If the actual angle at which the fault is cleared exceeds this critical value, the system will become unstable; conversely, if it remains within the critical threshold, the system will maintain its stability. As illustrated in the diagram below, curve A represents the power - angle relationship under normal, healthy operating conditions. Curve B depicts the power - angle curve during a fault, while curve C shows the power - angle behavior after the fault has been isolated.

image.png

Here, γ1represents the ratio of the system reactance during normal (healthy) operation to the reactance when a fault occurs. Meanwhile, γ2 denotes the ratio of the steady - state power limit of the system after the fault has been isolated to that of the system under its initial operating condition.Regarding the transient stability limit, a key criterion is that two specific areas are equal, i.e., A1 = A2. To elaborate, the area under the curve adec (shaped like a rectangle) must match the area under the curve da'b'bce. This equality of areas serves as a fundamental condition for assessing whether the power system can maintain stability during and after a transient fault event, ensuring that the energy imbalances introduced by the fault can be properly managed to prevent system collapse.

image.png

Thus if γ1, γ2, and δ0 are known, the critical clearing angle δc can be determined.

Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

Working Voltage in Power System
Working Voltage in Power System
Working VoltageThe term "working voltage" refers to the maximum voltage that a device can withstand without sustaining damage or burning out, while ensuring the reliability, safety, and proper operation of both the device and associated circuits.For long-distance power transmission, the use of high voltage is advantageous. In AC systems, maintaining a load power factor as close to unity as possible is also economically necessary. Practically, heavy currents are more challenging to handle than hi
Encyclopedia
07/26/2025
Frequency division method for measuring grid-to-ground insulation parameters
Frequency division method for measuring grid-to-ground insulation parameters
The frequency division method enables the measurement of grid-to-ground parameters by injecting a current signal of a different frequency into the open delta side of the potential transformer (PT).This method is applicable to ungrounded systems; however, when measuring the grid-to-ground parameters of a system where the neutral point is grounded via an arc suppression coil, the arc suppression coil must be disconnected from operation beforehand. Its measurement principle is shown in Figure 1.As
Leon
07/25/2025
The insulation parameters of the power grid to ground are measured by the tuning method
The insulation parameters of the power grid to ground are measured by the tuning method
The tuning method is suitable for measuring the ground parameters of systems where the neutral point is grounded via an arc suppression coil, but not applicable to ungrounded neutral point systems. Its measurement principle involves injecting a current signal with continuously varying frequency from the secondary side of the Potential Transformer (PT), measuring the returned voltage signal, and identifying the system's resonant frequency.During the frequency sweeping process, each injected heter
Leon
07/25/2025
Effect of Transition Resistance at the Grounding Point on the Rising Speed of Zero - sequence Voltage
Effect of Transition Resistance at the Grounding Point on the Rising Speed of Zero - sequence Voltage
In an arc - suppression coil grounding system, the rising speed of the zero - sequence voltage is greatly affected by the value of the transition resistance at the grounding point. The larger the transition resistance at the grounding point, the slower the rising speed of the zero - sequence voltage.In an ungrounded system, the transition resistance at the grounding point has basically no impact on the rising speed of the zero - sequence voltage.Simulation Analysis: Arc - suppression Coil Ground
Leon
07/24/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!