What is Line Regulation?

Edwiin
05/20/2025

Definition: Voltage regulation (or line regulation) refers to the variation in voltage at the receiving end of a transmission line when the full load at a specified power factor is removed, with the sending-end voltage maintained constant. In simpler terms, it is the percentage change in the load-end voltage when transitioning from no-load to full-load conditions. This parameter is expressed as a fraction or percentage of the receiving-end voltage, serving as a critical metric for assessing the stability and performance of electrical power systems.

The line regulation is given by the equation shown below.

Here, Vrnl represents the magnitude of the receiving-end voltage at no load, and |Vrfl| represents the magnitude of the receiving-end voltage at full load.
Line voltage regulation is influenced by the load's power factor:
  • Lagging Power Factor: The sending-end voltage exceeds the receiving-end voltage at full load, resulting in positive regulation.
  • Leading Power Factor: The receiving-end voltage becomes higher than the sending-end voltage at full load, causing the line regulation to be negative (as the receiving-end voltage rises when the load is removed).

This phenomenon underscores how reactive power flow—dictated by power factor—alters voltage distribution along the transmission line.

Line Regulation for Short Lines:
For a short transmission line, the receiving-end voltage at no load Vrnl equals the sending-end voltage VS (assuming no significant reactive power effects). At full load,
The simplest method for measuring line regulation involves connecting three parallel resistors to the supply. Two resistors are linked to a switch, while the third is directly connected to the supply. The resistor values are selected such that the directly connected resistor has a high resistance, whereas the other two (connected in parallel via the switch) have nominal values. A voltmeter placed in parallel with each resistor measures the voltage across each line, providing data for calculating line voltage regulation.
Edwiin

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

Working Voltage in Power System
Working Voltage in Power System
Working VoltageThe term "working voltage" refers to the maximum voltage that a device can withstand without sustaining damage or burning out, while ensuring the reliability, safety, and proper operation of both the device and associated circuits.For long-distance power transmission, the use of high voltage is advantageous. In AC systems, maintaining a load power factor as close to unity as possible is also economically necessary. Practically, heavy currents are more challenging to handle than hi
Encyclopedia
07/26/2025
Frequency division method for measuring grid-to-ground insulation parameters
Frequency division method for measuring grid-to-ground insulation parameters
The frequency division method enables the measurement of grid-to-ground parameters by injecting a current signal of a different frequency into the open delta side of the potential transformer (PT).This method is applicable to ungrounded systems; however, when measuring the grid-to-ground parameters of a system where the neutral point is grounded via an arc suppression coil, the arc suppression coil must be disconnected from operation beforehand. Its measurement principle is shown in Figure 1.As
Leon
07/25/2025
The insulation parameters of the power grid to ground are measured by the tuning method
The insulation parameters of the power grid to ground are measured by the tuning method
The tuning method is suitable for measuring the ground parameters of systems where the neutral point is grounded via an arc suppression coil, but not applicable to ungrounded neutral point systems. Its measurement principle involves injecting a current signal with continuously varying frequency from the secondary side of the Potential Transformer (PT), measuring the returned voltage signal, and identifying the system's resonant frequency.During the frequency sweeping process, each injected heter
Leon
07/25/2025
Effect of Transition Resistance at the Grounding Point on the Rising Speed of Zero - sequence Voltage
Effect of Transition Resistance at the Grounding Point on the Rising Speed of Zero - sequence Voltage
In an arc - suppression coil grounding system, the rising speed of the zero - sequence voltage is greatly affected by the value of the transition resistance at the grounding point. The larger the transition resistance at the grounding point, the slower the rising speed of the zero - sequence voltage.In an ungrounded system, the transition resistance at the grounding point has basically no impact on the rising speed of the zero - sequence voltage.Simulation Analysis: Arc - suppression Coil Ground
Leon
07/24/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!