What is Insulation Co-ordination?

Edwiin
05/21/2025

Definition: Insulation coordination refers to the process of determining the insulation levels of power system components. In essence, it is about establishing the insulation strength of equipment. The internal and external insulation of electrical equipment is subjected to both continuous normal voltage and temporary abnormal voltage.
Equipment insulation is engineered to withstand the highest power - frequency system voltage, occasional temporary power - frequency overvoltages, and occasional lightning surges. Power system equipment is assigned a rated insulation level, and its performance can be verified through various types of tests. The insulation requirements are determined by taking into account the following factors:
Highest Power - Frequency System Voltage
AC power networks feature different nominal power - frequency voltage levels, such as 400V, 3.3KV, 6.6kV, etc. When the system is lightly loaded, the power - frequency voltage at the receiving end of the line increases. Power system equipment is designed and tested to endure the highest power - frequency system voltage (440V, 3.6KV, 7.2KV, etc.) without experiencing internal or external insulation breakdown.
Temporary Power - Frequency Overvoltages
Temporary overvoltages in the power system can be triggered by load rejection, faults, resonance, etc. These overvoltages typically have a frequency of around 50 Hz, with relatively lower peaks, a slower rate of rise, and a longer duration (ranging from seconds to even minutes). Protection against temporary power - frequency overvoltages is provided by an Inverse Definite Minimum Time (IDMT) relay.
The IDMT relay is connected to the secondary of the bus potential transformer and circuit breakers. The relay and circuit breaker respond within milliseconds, safeguarding the system from temporary overvoltages.

Transient Overvoltage Surges
Transient overvoltage surges in the power system can be induced by phenomena such as lightning, switching operations, restrikes, and travelling waves. These surges in the power system are characterized by high peak values, a rapid rate of rise, and a duration lasting for a few tens to hundreds of microseconds, which is why they are referred to as transients.
Such surges have the potential to cause spark - over voltages and flash - overs at sharp corners, between phases and the earth, or at the weakest points in the system. They can also lead to the breakdown of gaseous, liquid, or solid insulation, as well as the failure of transformers and rotating electrical machines.
Through proper insulation coordination and the use of surge arresters, the failure rates caused by lightning and switching operations have been significantly reduced. Various protective devices are installed on the power network. These devices are designed to intercept lightning strikes and to decrease the peak rate of rise of surges that reach the equipment, thereby safeguarding it from potential damage.
Equipment Withstand Levels
The basic insulation level (BIL) is a reference level, represented by the impulse crest voltage of a standard wave not exceeding 1.2/50 μs. Apparatus and equipment must be able to withstand test waves with amplitudes greater than the BIL.
Insulation coordination involves choosing appropriate insulation for equipment based on its intended use. This is done to minimize unwanted events within the system that result from voltage stresses (caused by system overvoltages). Insulation breakdown refers to the relationship between the insulation breakdown of various power system components and the insulation of protective devices employed to safeguard that equipment against overvoltages.
For the safe operation of equipment, its insulation strength shall be equal to or higher than the basic standard insulation level. Protective equipment for station substations should be selected to provide effective insulation protection corresponding to these levels while being as economical as possible.
Edwiin

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

Working Voltage in Power System
Working Voltage in Power System
Working VoltageThe term "working voltage" refers to the maximum voltage that a device can withstand without sustaining damage or burning out, while ensuring the reliability, safety, and proper operation of both the device and associated circuits.For long-distance power transmission, the use of high voltage is advantageous. In AC systems, maintaining a load power factor as close to unity as possible is also economically necessary. Practically, heavy currents are more challenging to handle than hi
Encyclopedia
07/26/2025
Frequency division method for measuring grid-to-ground insulation parameters
Frequency division method for measuring grid-to-ground insulation parameters
The frequency division method enables the measurement of grid-to-ground parameters by injecting a current signal of a different frequency into the open delta side of the potential transformer (PT).This method is applicable to ungrounded systems; however, when measuring the grid-to-ground parameters of a system where the neutral point is grounded via an arc suppression coil, the arc suppression coil must be disconnected from operation beforehand. Its measurement principle is shown in Figure 1.As
Leon
07/25/2025
The insulation parameters of the power grid to ground are measured by the tuning method
The insulation parameters of the power grid to ground are measured by the tuning method
The tuning method is suitable for measuring the ground parameters of systems where the neutral point is grounded via an arc suppression coil, but not applicable to ungrounded neutral point systems. Its measurement principle involves injecting a current signal with continuously varying frequency from the secondary side of the Potential Transformer (PT), measuring the returned voltage signal, and identifying the system's resonant frequency.During the frequency sweeping process, each injected heter
Leon
07/25/2025
Effect of Transition Resistance at the Grounding Point on the Rising Speed of Zero - sequence Voltage
Effect of Transition Resistance at the Grounding Point on the Rising Speed of Zero - sequence Voltage
In an arc - suppression coil grounding system, the rising speed of the zero - sequence voltage is greatly affected by the value of the transition resistance at the grounding point. The larger the transition resistance at the grounding point, the slower the rising speed of the zero - sequence voltage.In an ungrounded system, the transition resistance at the grounding point has basically no impact on the rising speed of the zero - sequence voltage.Simulation Analysis: Arc - suppression Coil Ground
Leon
07/24/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!