Synchronizing Power and Torque Coefficient

Edwiin
Field: Power switch
China

Definition of Synchronizing Power

Synchronizing power, denoted as Psyn, is defined as the variation in synchronous power P with respect to changes in the load angle δ. Also referred to as the stiffness of couplingstability factor, or rigidity factor, it quantifies a synchronous machine’s (generator or motor) inherent tendency to maintain synchronism when connected to infinite busbars.

Principle of Synchronism Maintenance

Consider a synchronous generator transmitting a steady power Pa at a load angle δ0. A transient disturbance causing rotor acceleration (e.g., an increase in δ by dδ) shifts the operating point to a new constant-power curve, increasing the load to Pa+δP. Since the mechanical input power remains unchanged, the additional electrical load decelerates the rotor, restoring synchronism.

Conversely, if a disturbance retards the rotor (decreasing δ), the load drops toa Pa−δP. The constant input power then accelerates the rotor, reinstating synchronism.

Synchronizing Power Coefficient: A Measure of Corrective Efficiency

The effectiveness of this self-correcting mechanism hinges on the rate of power transfer change with respect to load angle variation. This is quantified by the synchronizing power coefficient, which mathematically represents how power adjusts to restore equilibrium after a disturbance.

  • Key Characteristics:

    • Inherently tied to the machine’s dynamic response to angular deviations.

    • Determines the system’s resilience against transient instability.

    • Higher Psyn values signify stiffer coupling and faster synchronism recovery.

This principle underscores the fundamental role of synchronizing power in maintaining grid stability, enabling synchronous machines to autonomously counteract disturbances and sustain steady-state operation.

Power output per phase of the cylindrical rotor generator synchronizing torque coefficient

In many synchronous machines Xs >> R. Therefore, for a cylindrical rotor machine, neglecting saturation and stator resistance equation (3) and (5) become

Unit of Synchronizing Power Coefficient Psyn

The synchronizing power coefficient is expressed in watts per electrical radian.

If P is the total number of pair of poles of the machine.

Synchronising Power Coefficient per mechanical radian is given by the equation shown below:

Synchronising Power Coefficient per mechanical degree is given as:

Synchronising Torque Coefficient

The synchronising torque coefficient is defined as the torque generated at synchronous speed, where synchronising torque specifically corresponds to the torque yielding synchronising power at this speed. Denoted by τsy, the coefficient is expressed by the equation:

Where,

  • m is the number of phases of the machine

  • ωs = 2 π ns

  • nis the synchronous speed in revolution per second

Significance of Synchronous Power Coefficient

The synchronous power coefficient Psyn quantifies the stiffness of the magnetic coupling between a synchronous machine's rotor and stator. A higher Psyn signifies a stiffer coupling, but excessive rigidity can expose the machine to mechanical shocks from abrupt load or supply variations—potentially damaging the rotor or windings.

The above two equations (17) and (18) indicate that Psyn is inversely proportional to synchronous reactance. A machine with larger air gaps exhibits relatively lower reactance, making it stiffer than one with smaller air gaps. Since Psyn is directly proportional to Ef, an overexcited machine demonstrates greater stiffness than an underexcited one.

The restoring capability is maximized when δ = 0 (i.e., at no load), while it diminishes to zero when δ = ±90. At this point, the machine reaches an unstable equilibrium and the steady-state stability limit. Thus, operating a machine at this stability limit is infeasible due to its zero resistance to small disturbances—unless equipped with a specialized fast-acting excitation system.

Give a tip and encourage the author!

Recommended

Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
01/29/2026
Understanding Transformer Neutral Grounding
I. What is a Neutral Point?In transformers and generators, the neutral point is a specific point in the winding where the absolute voltage between this point and each external terminal is equal. In the diagram below, pointOrepresents the neutral point.II. Why Does the Neutral Point Need Grounding?The electrical connection method between the neutral point and earth in a three-phase AC power system is called theneutral grounding method. This grounding method directly affects:The safety, reliabilit
01/29/2026
Voltage Imbalance: Ground Fault, Open Line, or Resonance?
Single-phase grounding, line break (open-phase), and resonance can all cause three-phase voltage unbalance. Correctly distinguishing among them is essential for rapid troubleshooting.Single-Phase GroundingAlthough single-phase grounding causes three-phase voltage unbalance, the line-to-line voltage magnitude remains unchanged. It can be classified into two types: metallic grounding and non-metallic grounding. Inmetallic grounding, the faulted phase voltage drops to zero, while the other two phas
11/08/2025
Composition and Working Principle of Photovoltaic Power Generation Systems
Composition and Working Principle of Photovoltaic (PV) Power Generation SystemsA photovoltaic (PV) power generation system is primarily composed of PV modules, a controller, an inverter, batteries, and other accessories (batteries are not required for grid-connected systems). Based on whether it relies on the public power grid, PV systems are divided into off-grid and grid-connected types. Off-grid systems operate independently without relying on the utility grid. They are equipped with energy-s
10/09/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.