Currently, the company operates two electric arc furnace (EAF) transformers. The secondary voltage ranges from 121 V to 260 V, with a rated current of 504 A / 12,213 A. The high-voltage side has a total of eight tap positions, utilizing motor-driven off-circuit voltage regulation. The equipment is equipped with a reactor of corresponding capacity, connected in series to designated taps on the high-voltage side. These transformers have been in operation for over 20 years. Throughout this period, to meet the evolving demands of the steelmaking process, several technical upgrades have been implemented on the electrode control system and transformer protection system, aiming to ensure safe and stable equipment operation. However, achieving this goal critically depends on the completeness and reliability of the interlocking circuit between the secondary protection circuit of the EAF transformer and the arc furnace's electrode control system. In recent years, several incidents of high-voltage tap changer burnout have occurred, raising concerns about the reliability of the associated interlocking circuits.
1 Accident Phenomenon
Core inspections of the transformers revealed that all failures involved burnout of the high-voltage side tap changer. In each incident, the secondary protection on the high-voltage side operated reliably. The instantaneous overcurrent protection setting for the high-voltage switch was 6,000 A on the primary side, meaning the protection would only activate if the short-circuit current through the tap changer exceeded 6,000 A instantaneously. However, the rated current of the tap changer itself is only 630 A.
2 Root Cause Analysis
The steelmaking process consists of three stages: melting, oxidation, and reduction. During the melting stage, the three-phase load fluctuates dramatically, generating large inrush currents that are often unbalanced. Even during the refining stage, continuous changes in the arc discharge path and arc gap ionization lead to constantly unbalanced load currents, resulting in zero-sequence components. When these zero-sequence components are reflected onto the star-connected high-voltage winding, they cause neutral point voltage displacement.
Based on the observed failure phenomena, various contributing conditions were analyzed. Detailed studies were conducted on the electrical circuits of the arc furnace electrode control system, the interlock relationship between the high-voltage secondary protection circuit, and the positions of the tap changer during gear shifting. Field tests were repeatedly performed to simulate whether the conditions leading to failure could occur during steelmaking. Ultimately, the following deficiencies in the interlocking protection circuit on the high-voltage side of the EAF transformer were identified. During steelmaking, the occurrence of any one of the following conditions could lead to tap changer burnout:
3 Improvement Measures
Compared to conventional power transformers, EAF transformers have the following characteristics: higher overload capacity, greater mechanical strength, larger short-circuit impedance, multiple secondary voltage levels, higher transformation ratios, low secondary voltage (tens to hundreds of volts), and high secondary current (thousands to tens of thousands of amperes). Current control in the arc furnace is achieved by changing the tap connections on the high-voltage side of the transformer and adjusting the electrode positions.
During steelmaking, according to process requirements and the operational nature of the EAF transformer, the two high-voltage switchgear units installed at the furnace front operate dozens or even hundreds of times per day. This places rigorous demands on the performance of vacuum switches and the reliability of protective operations. Therefore, the design incorporates a "one-in-use, one-on-standby" configuration, controlled from the furnace front operator station. Power is supplied via high-voltage power cables from the company's 66 kV central substation.
Given the deficiencies in the interlocking protection control circuit, it is essential to prevent the conditions that lead to tap changer burnout during steelmaking operations. Through analysis of the interlocking circuit, simulation testing, structural study of the tap changer, and understanding of the steelmaking process, the following corrective measures were developed:
4 Conclusion
By implementing the above solutions to address the deficiencies in the EAF transformer's interlocking protection control circuit, the reliability of the interlock system has been significantly enhanced. This effectively prevents operational errors by personnel from causing equipment damage, ensuring the safe, stable, and reliable operation of the EAF transformers. It also guarantees the successful completion of the company's steelmaking production tasks and substantially reduces equipment maintenance costs.
Focused on the design of electrical equipment, proficient in electrical principles and relevant specifications, and skilled in using design software. From intelligent substations to various types of electrical equipment, I am adept at optimizing design solutions, integrating new technologies. With practical experience and collaborative management capabilities, I deliver outstanding electrical design achievements.