Common faults of insulators and preventive measures

Felix Spark
Field: Failure and maintenance
China

An insulator is a special type of insulating component that serves the dual purpose of supporting conductors and preventing current from grounding in overhead transmission lines. It is widely used at the connection points between transmission towers and conductors, as well as between substation structures and power lines. Based on the dielectric material, insulators are classified into three types: porcelain, glass, and composite. Analyzing common insulator faults and preventive maintenance measures is primarily aimed at preventing insulation failure caused by various mechanical and electrical stresses due to environmental and electrical load changes, thereby safeguarding the operation and service life of power lines.

Fault Analysis

Insulators are exposed to the atmosphere year-round and are susceptible to various accidents due to factors such as lightning strikes, pollution, bird damage, ice and snow, high temperatures, extreme cold, and elevation differences.

  • Lightning Strike Accidents: Overhead line corridors often pass through hilly areas, mountains, open fields, and industrially polluted zones, making the lines highly vulnerable to lightning strikes, which can lead to insulator puncture or shattering.

  • Bird Damage Accidents: Research shows that a significant portion of insulator flashovers are caused by birds. Compared to porcelain and glass insulators, composite insulators have a higher probability of flashover due to bird activity. Such incidents mostly occur on transmission lines of 110 kV and above, while flashovers due to bird damage are rare in 35 kV and lower urban distribution networks. This is because bird populations are relatively smaller in urban areas, line voltages are lower, the air gap that can be bridged is small, and insulators typically do not require corona rings; their shed structure effectively prevents bird-induced flashovers.

  • Corona Ring Accidents: During operation, the electric field near the metal fittings at the ends of insulators is highly concentrated, with high field strength near the flange. To improve field distribution, corona rings are commonly installed on grids of 220 kV and above. However, corona rings reduce the effective air clearance of the insulator string, lowering its withstand voltage. Additionally, the low corona inception voltage at the corona ring's fixing bolts can lead to corona discharge under adverse weather conditions, affecting the safety of the insulator string.

  • Pollution Accidents: These occur when conductive contaminants accumulated on the insulator surface become damp in humid weather, significantly reducing insulation performance and causing flashover under normal operating voltage.

  • Accidents of Unknown Cause: Some insulator flashover incidents have undetermined causes, such as zero-value porcelain insulators, shattered glass insulators, or tripped composite insulators. Despite post-incident inspections by operating units, the exact cause of flashover often remains unidentified. These incidents commonly occur from late night to early morning, especially during rainy or overcast weather, and many can be successfully auto-reclosed.

Maintenance Measures

The main causes of lightning-induced flashover include insufficient dry-arc distance, single-end corona ring configuration, and excessive tower grounding resistance. Preventive measures include using extended-length composite insulators, installing double corona rings, and reducing tower grounding resistance.

To effectively prevent bird damage, operating units should install bird-spiking nets, bird needles, or bird guards in sections prone to frequent bird-related incidents.

For lines equipped with corona rings, an equal spacing design between large and small sheds should be adopted, with shed spacing meeting technical requirements. If not, the creepage distance of insulators should be increased to reduce flashover risks caused by ice and snow. Regular inspections and patrols should be strengthened, with periodic sampling of insulators operating in different regions and environments for tensile strength, electrical performance, and insulation aging tests to prevent flashovers due to insufficient mechanical strength or shed aging.

To prevent pollution flashovers, the following measures are generally adopted:

  • Regular cleaning of insulators. A comprehensive cleaning should be conducted before the high-pollution flashover season, with increased frequency in heavily polluted areas.

  • Increasing creepage distance and enhancing insulation level. This includes adding more insulator units in polluted areas or using anti-pollution insulators. Operational experience shows that anti-pollution insulators perform well in heavily polluted sections.

  • Applying anti-pollution coatings, such as paraffin wax, petroleum jelly, or silicone organic coatings, to improve the insulator's surface pollution resistance.

  • For flashover incidents of unknown cause, new insulators of the same model and old ones that have been in service for over three years should undergo power-frequency dry flashover and mechanical failure tests. Aging tests should also be conducted on insulators from different service periods. Insulators should be cleaned regularly according to scheduled cycles, and salt deposit density (SDD) should be measured promptly. During the production of new insulators, advanced anti-aging agents should be incorporated to enhance material durability.

Give a tip and encourage the author!
Recommended
Ultimate Guide to AC Contactor Abnormal Noise: From Electromagnetic Noise to Mechanical Vibration, Accurate Diagnosis and Handling
In electrical control systems, AC contactors are among the commonly used electrical components, and they are also a common source of various electrical faults. After long-term use—especially in harsh environments with high levels of dust—AC contactors may sometimes emit squeaking or rattling noises after being pulled in and held. The causes of this phenomenon are analyzed as follows.Squeaking Noise After Pull-In and HoldingA fully functional AC contactor makes no noise when energized and pulled
Felix Spark
09/11/2025
Comprehensive Guide to High-Frequency Fault Handling of AC Contactors: 90% of Problems Solved with One Method
1. Fault Phenomena, Cause Analysis and Handling MethodsContactor does not operate or operates abnormally after coil energization Open circuit in coil control circuit; Check if there is wire breakage or loosening at the terminal blocks. If there is a wire breakage, replace the corresponding wire; if there is loosening, fasten the corresponding terminal block. Coil damage; Measure the coil resistance with a multimeter. If the resistance is ∞, replace the coil. Thermal relay not reset after operati
Felix Spark
09/11/2025
Application and Maintenance of AC Contactors | Comprehensive Analysis of Common Fault Handling, Master It in One Article
1 Analysis of Key Components of AC ContactorsAn AC contactor is an automated electromagnetic switch used for long-term, high-frequency switching of AC main circuits and control circuits. It features advantages such as automatic operation, under-voltage and no-voltage protection, high-capacity operation, strong stability, and low maintenance requirements. In the electrical control circuits of machine tools, AC contactors are mainly used to control electric motors and other loads.The key component
Felix Spark
09/11/2025
Dielectric Withstand Capability of AC Vacuum Contactors and Countermeasures
During operation, AC vacuum contactors are often subjected to various overvoltages such as lightning overvoltage and switching overvoltage. Therefore, AC vacuum contactors must have a certain voltage withstand capacity.An AC vacuum contactor is composed of a vacuum interrupter (its structure is shown in Figure 1), a housing, an electromagnetic system, a secondary circuit, and other components. Among these, the vacuum interrupter is the "heart" of the AC vacuum contactor, and its performance dire
Felix Spark
09/09/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.