Short Circuit Ratio of a Synchronous Machine

Edwiin
06/04/2025

The Short Circuit Ratio (SCR) of a Synchronous Machine
The Short Circuit Ratio (SCR) of a synchronous machine is defined as the ratio of the field current needed to generate rated voltage under open-circuit conditions to the field current required to sustain rated armature current during a short-circuit condition. For a three-phase synchronous machine, the SCR can be derived from its Open-Circuit Characteristic (O.C.C) at rated speed and Short-Circuit Characteristic (S.C.C), as illustrated in the figure below:
From the above figure, the short circuit ratio is given by the equation shown below.
Since the triangles Oab and Ode are similar. Therefore,
Direct Axis Synchronous Reactance (Xd)
The direct axis synchronous reactance Xd is defined as the ratio of the open-circuit voltage corresponding to a specific field current to the armature short-circuit current under the same field current condition.
For a field current of magnitude Oa, the direct axis synchronous reactance (in ohms) is expressed by the following equation:
Relationship Between SCR and Synchronous Reactance
From equation (7), it is evident that the Short Circuit Ratio (SCR) equals the reciprocal of the per-unit direct axis synchronous reactance Xd. In a saturated magnetic circuit, the value of Xd is contingent upon the degree of magnetic saturation.
Significance of the Short Circuit Ratio (SCR)
The SCR is a critical parameter for synchronous machines, influencing their operational characteristics, physical dimensions, and cost. Key implications include:
  • Voltage Regulation Impact
    • Synchronous generators with lower SCR values exhibit more pronounced terminal voltage fluctuations with load changes. Maintaining constant terminal voltage requires wide-ranging adjustments to the field current If).
  • Stability Limitations
    • A smaller SCR corresponds to reduced synchronizing power, which is essential for maintaining synchronism. This results in a lower stability limit, meaning machines with low SCR are less stable when operating in parallel with other generators.
  • Trade-offs in Design
    • High-SCR machines offer superior voltage regulation and enhanced steady-state stability but entail higher armature short-circuit fault currents. Additionally, they influence machine size and cost due to design trade-offs.
The excitation voltage of a synchronous machine is described by the equation:
For the same value of Tph Excitation voltage is directly proportional to the field flux per pole.
The synchronous inductance is given as:
Relationship Between SCR and Air Gap
Thus, the Short Circuit Ratio (SCR) is directly proportional to the air gap reluctance or air gap length. Increasing the air gap length elevates the SCR, though this requires a higher field magnetomotive force (MMF) to maintain the same excitation voltage (). To increase the field MMF, either the field current or the number of field turns must be augmented, necessitating taller field poles and an enlarged machine diameter.
Impact on Machine Design
This leads to a key conclusion: a higher SCR inherently increases the size, weight, and cost of the synchronous machine.
Typical SCR Values by Machine Type
  • Cylindrical Rotor Machines: SCR ranges from 0.5 to 0.9.
  • Salient-Pole Machines: SCR falls between 1.0 and 1.5.
  • Synchronous Compensators: SCR is typically 0.4.
These values reflect the design trade-offs between stability, voltage regulation, and physical dimensions in different synchronous machine configurations.
Edwiin

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
For users, when purchasing a 35kV new energy transformer, choosing between dry-type, mineral oil-filled, or vegetable oil-filled types involves multiple considerations. These include user habits, maintenance-free performance, safety and fire resistance, volume and weight, among others. However, cost differences are undoubtedly one of the most crucial factors.To illustrate the issue intuitively, this paper selects a three-level energy efficiency dual-winding new energy transformer with a rated ca
Ron
07/26/2025
What is the connection group of a transformer?
What is the connection group of a transformer?
Transformer Connection GroupThe connection group of a transformer refers to the phase difference between the primary and secondary voltages or currents. It is determined by the winding directions of the primary and secondary coils, the labeling of their start and end terminals, and the connection mode. Expressed in a clock-like format, there are 12 groups in total, numbered from 0 to 11.The DC method is commonly used to measure the transformer's connection group, mainly to verify whether the con
Vziman
07/26/2025
What is the sequence for powering down the transformer?
What is the sequence for powering down the transformer?
The sequence for shutting down a main transformer is as follows: when de-energizing, the load side should be shut down first, followed by the power supply side. For energizing operations, the reverse order applies: the power supply side is energized first, then the load side. This is because: Energizing from the power supply side to the load side makes it easier to identify the fault range and take prompt judgment and handling measures in case of a fault, preventing the fault from spreading or e
Rockwell
07/26/2025
What are the methods for switching operations of station transformers?
What are the methods for switching operations of station transformers?
Let's take an auxiliary power system with two station transformers as an example. When one station transformer needs to be out of service, there are two operation methods: non-interruptive power supply and instantaneous power interruption. Generally, the method of instantaneous power interruption on the low-voltage side is preferred.The operation method for instantaneous power interruption on the low-voltage side is as follows:Open the 380V power incoming circuit breaker of the corresponding sec
Vziman
07/26/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!