Dry-Type vs Oil-Filled 35kV New Energy Transformers: Cost and Performance Comparison

Ron
Ron
Field: Modeling and Simulation
Cameroon

For users, when purchasing a 35kV new energy transformer, choosing between dry-type, mineral oil-filled, or vegetable oil-filled types involves multiple considerations. These include user habits, maintenance-free performance, safety and fire resistance, volume and weight, among others. However, cost differences are undoubtedly one of the most crucial factors.

To illustrate the issue intuitively, this paper selects a three-level energy efficiency dual-winding new energy transformer with a rated capacity of 3150kVA and a rated voltage of 37kV as an example for quantitative calculation and qualitative analysis.

Basic Parameters of the Product

  • Rated Capacity: 3150 / 3150kVA

  • Voltage Ratio: 37±2×2.5%/0.8kV

  • Connection Group: Dyn1

  • Short-Circuit Impedance: 7%

  • Energy Efficiency Class: Class 3

Differences in Material Costs

Based on the same basic technical parameters and energy efficiency class mentioned above, and combined with current market prices of raw materials (copper at 80,000 yuan/ton), the differences in tax-included material costs of 3150 kVA / 37kV dual-winding new energy transformers—for dry-type, mineral oil-filled, and vegetable oil-filled types—are calculated as follows.

It should be specially noted that for dry-type and oil-immersed transformers with the same capacity, voltage class, and energy efficiency class, their respective limits for no-load loss and load loss are different.

Cost Comparison Conclusion:For the 3150 kVA / 37 kV dual-winding new energy transformer, under the same level 3 energy efficiency, the dry-type transformer has the highest cost—about 45% higher than the mineral oil-filled transformer. In contrast, the vegetable oil-filled transformer offers better cost - effectiveness, with a cost only about 7.5% higher than that of the mineral oil-filled transformer.

Comprehensive Performance Comparison

To help users reasonably select the product type of 35kV - class new energy transformers based on the budgets and technical requirements of actual engineering projects, the qualitative comparison conclusions are presented in the following table.

That is, dry-type transformers have significant advantages in terms of floor space, maintenance-free property, safety and fire resistance, short-circuit withstand capability, etc., while oil-immersed transformers have obvious advantages in aspects such as actual operation energy consumption, one-time purchase cost, and whole-life-cycle operation cost.

Give a tip and encourage the author!
Recommended
How to Identify Internal Faults in a Transformer?
How to Identify Internal Faults in a Transformer?
Measure DC resistance: Use a bridge to measure the DC resistance of each high- and low-voltage winding. Check whether the resistance values among phases are balanced and consistent with the manufacturer’s original data. If phase resistance cannot be measured directly, line resistance may be measured instead. The DC resistance values can indicate whether the windings are intact, whether there are short circuits or open circuits, and whether the contact resistance of the tap changer is normal. If
Felix Spark
11/04/2025
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
What are the requirements for inspecting and maintaining a transformer's no-load tap changer?
The tap changer operating handle shall be equipped with a protective cover. The flange at the handle shall be well sealed with no oil leakage. Locking screws shall securely fasten both the handle and the drive mechanism, and the handle rotation shall be smooth without binding. The position indicator on the handle shall be clear, accurate, and consistent with the tap voltage regulation range of the winding. Limit stops shall be provided at both extreme positions. The insulating cylinder of the t
Leon
11/04/2025
How to Overhaul a Transformer Conservator (Oil Pillow)?
How to Overhaul a Transformer Conservator (Oil Pillow)?
Overhaul Items for Transformer Conservator:1. Ordinary-Type Conservator Remove the end covers on both sides of the conservator, clean rust and oil deposits from inner and outer surfaces, then apply insulating varnish to the inner wall and paint to the outer wall; Clean components such as the dirt collector, oil level gauge, and oil plug; Check that the connecting pipe between the explosion-proof device and the conservator is unobstructed; Replace all sealing gaskets to ensure good sealing with n
Felix Spark
11/04/2025
Why is it difficult to increase the voltage level?
Why is it difficult to increase the voltage level?
The solid-state transformer (SST), also known as a power electronic transformer (PET), uses voltage level as a key indicator of its technological maturity and application scenarios. Currently, SSTs have reached voltage levels of 10 kV and 35 kV on the medium-voltage distribution side, while on the high-voltage transmission side, they remain in the stage of laboratory research and prototype validation. The table below clearly illustrates the current status of voltage levels across different appli
Echo
11/03/2025