What are the methods for switching operations of station transformers?

Vziman
07/26/2025

Let's take an auxiliary power system with two station transformers as an example. When one station transformer needs to be out of service, there are two operation methods: non-interruptive power supply and instantaneous power interruption. Generally, the method of instantaneous power interruption on the low-voltage side is preferred.

The operation method for instantaneous power interruption on the low-voltage side is as follows:

  • Open the 380V power incoming circuit breaker of the corresponding section of the auxiliary power for the station transformer to be out of service.
  • Open the 380V incoming isolating switch of the station transformer to be out of service.
  • Close the auxiliary power section circuit breaker.
  • Open the bus isolating switch of the station transformer to be out of service.
  • Open the high-voltage fuse of the station transformer to be out of service.

The operation method for non-interruptive power supply on the low-voltage side is as follows:

  • Apply to the dispatching for paralleling the high-voltage side of the station transformers (for example, close the 35kV bus tie circuit breaker).
  • Measure that the voltage difference between the busbars of section Ⅰ and section Ⅱ of the auxiliary power is qualified, then close the auxiliary power section circuit breaker to make section Ⅰ and section Ⅱ of the auxiliary power operate in parallel.
  • Open the 380V power incoming circuit breaker of the corresponding section of the auxiliary power for the station transformer to be out of service.
  • Open the 380V incoming isolating switch of the station transformer to be out of service.
  • Open the bus isolating switch of the station transformer to be out of service.
  • Open the high-voltage fuse of the station transformer to be out of service.

electrical transformer.jpg

Vziman

Zhejiang Vziman Electric Group Co., Ltd. is a high-tech enterprise specializing in R&D, manufacturing, and service of power electrical equipment. Committed to innovation, quality, and customer satisfaction, it supplies smart solutions for global power sectors, covering grid construction, new energy, and industrial distribution. Core Business • Switchgear (GIS, circuit breakers, Recloser, Load break switch) • Distribution equipment (transformers, RMU, smart terminals) • Power automation systems • Engineering services (installation, maintenance, consulting) Technical Strength • Provincial R&D center, multiple patents • Modern production, ISO/GB/IEC/CE/UL certified • High capacity, large-scale delivery support Market & Vision Serves State Grid, Southern Grid, and global projects (Asia, Africa, Europe, etc.). Aims to lead in smart grids and new energy, promoting sustainable energy development.

Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
For users, when purchasing a 35kV new energy transformer, choosing between dry-type, mineral oil-filled, or vegetable oil-filled types involves multiple considerations. These include user habits, maintenance-free performance, safety and fire resistance, volume and weight, among others. However, cost differences are undoubtedly one of the most crucial factors.To illustrate the issue intuitively, this paper selects a three-level energy efficiency dual-winding new energy transformer with a rated ca
Ron
07/26/2025
What is the connection group of a transformer?
What is the connection group of a transformer?
Transformer Connection GroupThe connection group of a transformer refers to the phase difference between the primary and secondary voltages or currents. It is determined by the winding directions of the primary and secondary coils, the labeling of their start and end terminals, and the connection mode. Expressed in a clock-like format, there are 12 groups in total, numbered from 0 to 11.The DC method is commonly used to measure the transformer's connection group, mainly to verify whether the con
Vziman
07/26/2025
What is the sequence for powering down the transformer?
What is the sequence for powering down the transformer?
The sequence for shutting down a main transformer is as follows: when de-energizing, the load side should be shut down first, followed by the power supply side. For energizing operations, the reverse order applies: the power supply side is energized first, then the load side. This is because: Energizing from the power supply side to the load side makes it easier to identify the fault range and take prompt judgment and handling measures in case of a fault, preventing the fault from spreading or e
Rockwell
07/26/2025
Design and Implementation of Special Transformer with Automatic Capacity Regulation
Design and Implementation of Special Transformer with Automatic Capacity Regulation
1. IntroductionEnergy is essential for societal operation and development. To meet national energy - conservation and emission - reduction policies, improving resource utilization—critical for power enterprises—is necessary. Multi - stage rural grid upgrades drive distribution transformer development. Despite high efficiency, widespread transformers still face significant overall losses due to capacity and usage issues; 70% of medium - and low - voltage grid losses come from distribu
Ron
07/26/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!