• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


On Off Control Controller: What is it? (Working Principle)

Electrical4u
Field: Basic Electrical
0
China

What Is An On Off Controller

What is an On Off Controller?

Sometimes, the control element has only two positions either it is fully closed or fully open. This control element does not operate at any intermediate position, i.e. partly open or partly closed position. The control system made for controlling such elements is known as the on-off control theory. In this control system, when process variable changes and crosses a certain preset level, the output value of the system is suddenly fully opened and gives 100 % output.

Generally, in the on-off control system, the output causes a change in the process variable. Hence due to the effect of output, the process variable again starts changing but in the reverse direction.

During this change, when the process variable crosses a certain predetermined level, the output value of the system is immediately closed and output is suddenly reduced to 0%.

As there is no output, the process variable again starts changing in its normal direction. When it crosses the preset level, the output valve of the system is again fully open to give 100% output. This cycle of closing and opening of the output valve continues until the said on-off control system is in operation.

A very common example of on-off control theory is a fan controlling scheme of the transformer cooling system. When transformer runs with such a load, the temperature of the electrical power transformer rises beyond the preset value at which the cooling fans start rotating with their full capacity.

As the cooling fans run, the forced air (output of the cooling system) decreases the temperature of the transformer. When the temperature (process variable) comes down below a preset value, the control switch of fans trip and fans stop supplying forced air to the transformer.



on off control system



After that, as there is no cooling effect of fans, the temperature of the transformer again starts rising due to load. Again when during rising, the temperature crosses the preset value, the fans again start rotating to cool down the transformer.

Theoretically, we assume that there is no lag in the control equipment. That means, there is no time day for on and off operation of control equipment. With this assumption, if we draw a series of operations of an ideal on-off control system, we will get the graph given below.

But in practical on-off control, there is always a non zero time delay for closing and opening action of controller elements.

This time delay is known as dead time. Because of this time delay, the actual response curve differs from the above shown ideal response curve.

Let us try to draw the actual response curve of an on off control system.



on off control system



Say at time T O the temperature of the transformer starts rising. The measuring instrument of the temperature does not respond instantly, as it requires some time delay for heating up and expansion of mercury in temperature sensor bulb say from instant T1 the pointer of the temperature indicator starts rising.

This rising is exponential in nature. Let us at point A, the controller system starts actuating for switching on cooling fans, and finally, after the period of T2 the fans start delivering force air with its full capacity. Then the temperature of the transformer starts decreasing in an exponential manner.

At point B, the controller system starts actuating for switching off the cooling fans, and finally after a period of T3 the fans stop delivering force air. Then the temperature of the transformer again starts rising in the same exponential manner.

N.B.: Here during this operation, we have assumed that the loading condition of the electrical power transformer, ambient temperature and all other conditions of surrounding are fixed and constant.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.