• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Fire Detection and Alarm System

Electrical4u
Field: Basic Electrical
0
China

WechatIMG1830.jpeg

Introduction of Fire Detection and Alarm System

Fire detectors are designed to detect one or more of the three characteristics of fire-smoke, heat and flame. Besides it every fire detection system must include manual call points (break glass), so that in the event of fire can be of immediate help.
During a fire importance of activation of the occupants through alarm or bell is of at most vital and this can performed through alarm system.
fire alarm panel
Fire alarm system shall be designed to provide round the clock security against fire in the complete power plant area.

Microprocessor based addressable analogue type fire alarm and detection system to be used for various building/areas to detect and provide alarm signal in the main fire alarm panel to be located in the central control room. Fire alarm will be repeated in a repeater alarm panel in the fire station.
Main fire alarm panel annunciation shall be located in the control building. A repeater panel shall be provided in the fire station. Total no of annunciation shall be based on the specific plant requirement.
One (1) siren of 10 Km range is envisaged to provide warning in the event of fire.
In addition to it, PLC panel shall be provided at fire pump house and foam pump house.

Why Fire Detection and Alarm System Required

Fire detection and protection system is required for the following reasons:

  • To detect fire in the area during the initial stage.

  • To alert occupants, so that they escape the building safely.

  • Summon trained personnel to take charge of controlling the fire as quickly as possible.

  • To initiate automatic fire control and suppression system.

  • To support and supervise the fire control and suppression system.

Type of Fire Detectors

  1. Smoke Detectorsmoke detector

  2. Fire Detectorfire detector

  3. Heat Detectorheat detector

Area to be Covered under Fire Detection and Protection System

Sl. No.

Fire Detection System

Area to be Covered

1

Smoke Detection System

  • Main plant control room

  • Control equipment rooms

  • Switch gear and battery rooms (including MCC/Control rooms of SG, Turbine and Generator switch yard

  • MCC/Control rooms of all the auxiliaries of BTG and BOP auxiliaries like Coal handling plant, Ash handling plant, Compressed air plant, Fuel oil plant, Raw water/fire water pump house, CW pump house, Water treatment plant, Effluent treatment plant, HVAC system, Chemical treatment plant and other miscellaneous pump house.

  • Switch gear/MCC control rooms

2

Linear heat sensing cable detection system

  • Cable galleries

  • Coal Conveyors

  • Fuel oil tanks

3

Quartzoid bulb heat detection system

  • Equipment protected by HVW spray system and fuel oil tanks

  • Fuel oil tanks

  • Fuel skids and pump houses protected by MVW spray system.

4

Infra-red Detectors

  • For all conveyors (one near the head end of each conveyor and the other mid way between the head and tail pulley shall be provided)


Design Philosophy of Fire Detection and Alarm System

  1. The PLC based control panel at pump houses shall indicate the status of each pump, system pressure, operation of hydrant or spray system, failure of starting of pumps, healthiness and failure of batteries/chargers, main supply, low level/very low level of water in the water supply system, status of compressors, selection station of batteries and chargers of panels and diesel engines etc. Alarms from these panels shall also be available at fire station in a repeater panel and at main fire panel alarm in control room.

  2. The PLC based addressable type panels at central Control rooms shall receive signal from sensor from various areas/equipments of the respective units.

  3. The Microprocessor based addressable panel shall evaluate the signals received from detectors, transmit the fire or trouble alarms (audio-visual) to prearranged points, supervise and monitor the complete fire detection and extinguishing circuits, initiate control functions like closure of fire doors, shutdown of draft fans, air conditioning and ventilation plant/equipment, closure of fire dampers in A/C and ventilation system etc. Opening smoke extraction vents, switching on smoke extraction equipment emergency lighting, tripping of transformer lockout relays etc.

  4. All the circuits from the detectors to the panels and the circuits from the panels to the actuating devices (such as solenoid valves, deluge valves, push buttons etc) shall be in closed loop type and in close watch for open-and-short-circuiting.

  5. Facilities shall be provided on the main fire alarm panel for sensitivity adjustment, isolation of detectors etc from the panel.

  6. Panel of fire detection, alarm monitoring and annunciation system shall operate on DC-supply, along with associated rectifier bank. Further each panel shall have the provision for batteries for charging.

  7. Each set of battery shall have the capacity for a period of 12 hours from the instant of charger/AC failure.

  8. Exit signs shall be painted o 18 gauge cold rolled sheet steel. This sheet should be suitable for fixing on walls or hanging from ceiling. Fire Exit/No Fire Exit shall be displayed on both sides of the Exit signs.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.