Types of Electrical Protection Relays or Protective Relays

Electrical4u
03/26/2024

What Is A Protection Relay

Definition of Protective Relay

A relay is automatic device which senses an abnormal condition of electrical circuit and closes its contacts. These contacts in turns close and complete the circuit breaker trip coil circuit hence make the circuit breaker tripped for disconnecting the faulty portion of the electrical circuit from rest of the healthy circuit.

Now let’s have a discussion on some terms related to protective relay.
Pickup Level of Actuating Signal:

The value of actuating quantity (voltage or current) which is on threshold above which the relay initiates to be operated.

If the value of actuating quantity is increased, the electromagnetic effect of the relay coil is increased, and above a certain level of actuating quantity, the moving mechanism of the relay just starts to move.

Reset Level:
The value of
current or voltage below which a relay opens its contacts and comes in original position.

Operating Time of Relay:
Just after exceeding pickup level of actuating quantity the moving mechanism (for example rotating disc) of relay starts moving and it ultimately closes the relay contacts at the end of its journey. The time which elapses between the instant when actuating quantity exceeds the pickup value to the instant when the relay contacts close.

Reset Time of Relay:
The time which elapses between the instant when the actuating quantity becomes less than the reset value to the instant when the relay contacts return to its normal position.

Reach of Relay:
A distance relay operates whenever the distance seen by the relay is less than the pre-specified impedance. The actuating impedance in the relay is the function of distance in a distance protection relay. This impedance or corresponding distance is called the reach of relay.

Power system protection relays can be categorized into different types of relays.

Types of Relays

Types of protection relays are mainly based on their characteristic, logic, on actuating parameter and operation mechanism.

Based on operation mechanism protection relay can be categorized as electromagnetic relay, static relay and mechanical relay. Actually, a relay is nothing but a combination of one or more open or closed contacts. These all or some specific contacts the relay change their state when actuating parameters are applied to the relay. That means open contacts become closed and closed contacts become open. In an electromagnetic relay, these closing and opening of relay contacts are done by the electromagnetic action of a solenoid.

In the mechanical relay, these closing and opening of relay contacts are done by mechanical displacement of different gear level system.

In static relay it is mainly done by semiconductor switches like thyristor. In digital relay on and off state can be referred as 1 and 0 state.

Based on Characteristic the protection relay can be categorized as:

  1. Definite time relays

  2. Inverse time relays with definite minimum time(IDMT)

  3. Instantaneous relays.

  4. IDMT with inst.

  5. Stepped characteristic.

  6. Programmed switches.

  7. Voltage restraint over current relay.

Based on of logic the protection relay can be categorized as-

  1. Differential.

  2. Unbalance.

  3. Neutral displacement.

  4. Directional.

  5. Restricted earth fault.

  6. Over fluxing.

  7. Distance schemes.

  8. Bus bar protection.

  9. Reverse power relays.

  10. Loss of excitation.

  11. Negative phase sequence relays etc.

Based on actuating parameter the protection relay can be categorized as-

  1. Current relays.

  2. Voltage relays.

  3. Frequency relays.

  4. Power relays etc.

Based on application the protection relay can be categorized as-

  1. Primary relay.

  2. Backup relay.

Primary relay or primary protection relay is the first line of power system protection whereas backup relay is operated only when primary relay fails to be operated during a fault. Hence backup relay is slower in action than primary relay. Any relay may fail to be operated due to any of the following reasons,

  1. The protective relay itself is defective.

  2. DC Trip voltage supply to the relay is unavailable.

  3. Trip lead from relay panel to the circuit breaker is disconnected.

  4. The trip coil in the circuit breaker is disconnected or defective.

  5. Current or voltage signals from Current Transformers (CTs) or Potential Transformers (PTs) respectively is unavailable.

As because backup relay operates only when primary relay fails, backup protection relay should not have anything common with primary protection relay.
Some examples of Mechanical Relay are:

  1. Thermal

    • OT trip (Oil Temperature Trip)

    • WT trip (Winding Temperature Trip)

    • Bearing temp trip etc.

  2. Float type

    • Buchholz

    • OSR

    • PRV

    • Water level Controls etc.

  3. Pressure switches.

  4. Mechanical interlocks.

  5. Pole discrepancy relay.

List Different Protective Relays are used for Different Power System Equipment Protection

Now let’s have a look on which different protective relays are used in different power system equipment protection schemes.

Relays for Transmission & Distribution Lines Protection

SL Lines to be protected Relays to be used
1 400 KV
Transmission Line
Main-I: Non switched or Numerical Distance Scheme
Main-II: Non switched or Numerical Distance Scheme
2 220 KV
Transmission Line
Main-I : Non switched distance scheme (Fed from Bus PTs)
Main-II: Switched distance scheme (Fed from line CVTs)
With a changeover facility from bus PT to line CVT and vice-versa.
3 132 KV
Transmission Line
Main Protection : Switched distance scheme (fed from bus PT).
Backup Protection: 3 Nos. directional IDMT O/L Relays and
1 No. Directional IDMT E/L relay.
4 33 KV lines Non-directional IDMT 3 O/L and 1 E/L relays.
5 11 KV lines Non-directional IDMT 2 O/L and 1 E/L relays.

Relays for Transformer Protection

SL Voltage Ratio and
Capacity of Transformer
Relays on HV Side Relays on LV Side Common Relays
1 11/132 KV
Generator Transformer
3 nos Non-Directional O/L Relay
1 no Non-Directional E/L Relay
and/or standby E/F + REF Relay
– – Differential Relay or
Overall differential Relay
Overflux Relay
Buchholz Relay
OLTC Buchholz Relay
PRV Relay
OT
Trip Relay
WT Trip Relay
2 13.8/220 KV
15.75/220 KV
18/400 KV
21/400 KV
Generator Transformer
3 nos Non-Directional O/L Relay
1 no Non-Directional E/L Relay
and/or standby E/F + REF Relay
– – Differential Relay or
Overall differential Relay
Overflux Relay
Buchholz Relay
OLTC Buchholz Relay
PRV Relay
OT
Trip Relay
WT Trip Relay
3 220 /6.6KV
Station Transformer
3 nos Non-Directional O/L Relay
1 no Non-Directional E/L Relay
and/or standby E/F + REF Relay
3 nos Non-Directional O/L Relay Differential Relay
Overflux Relay
Buchholz Relay
OLTC Buchholz Relay
PRV Relay
OT Trip Relay
WT Trip Relay
4 Gen-volt/6.6KV UAT 3 nos Non-Directional O/L Relay 3 nos Non-Directional O/L Relay Differential Relay
Overflux Relay
Buchholz Relay
OLTC Buchholz Relay
PRV Relay
OT Trip Relay
WT Trip Relay
5 132/33/11KV upto 8 MVA 3 nos O/L Relay
1 no E/L Relay
2 nos O/L Relays
1 no E/L Relay
Buchholz Relay
OLTC Buchholz Relay
PRV Relay
OT Trip Relay
WT Trip Relay
6 132/33/11KV above 8 MVA &
below 31.5 MVA
3 nos O/L Relay
1 no Directional E/L Relay
3 nos O/L Relay
1 no E/L Relay
Differential Relay
Buchholz Relay
OLTC Buchholz Relay
PRV Relay
OT Trip Relay
WT Trip Relay
7 132/33KV, 31.5 MVA & above 3 nos O/L Relay
1 no Directional E/L Relay
3 nos O/L Relay
1 no E/L Relay
Differential Relay
Overflux Relay
Buchholz Relay
OLTC Buchholz Relay
PRV Relay
OT Trip Relay
WT Trip Relay
8 220/33 KV, 31.5MVA &
50MVA 220/132KV, 100 MVA
3 nos O/L Relay
1 no Directional E/L Relay
3 nos O/L Relay
1 no Directional E/L Relay
Differential Relay
Overflux Relay
Buchholz Relay
OLTC Buchholz Relay
PRV Relay
OT Trip Relay
WT Trip Relay
9 400/220KV 315MVA 3 nos Directional O/L Relay
(with dir.highset)
1 no Directional E/L relay.
Restricted E/F relay
3 nos Directional O/L Relay for
action
3 nos Directional O/L Relay
(with dir.highset)
1 no Directional E/L relay.
Restricted E/F relay
Differential Relay
Overflux Relay
Buchholz Relay
OLTC Buchholz Relay
PRV Relay
OT Trip Relay
WT Trip Relay
Over Load (Alarm) Relay

Points to be remembered in respect of protection of transformers

  1. No Buchholz relay for transformers below 500 KVA capacity.

  2. Transformers up to 1500 KVA shall have only Horn gap protection.

  3. Transformers above 1500 KVA and upto 8000 KVA of 33/11KV ratio shall have one group control breaker on HV side and individual LV breakers if there is more than one transformer.

  4. Transformers above 8000 KVA shall have individual HV and LV circuit breakers.

  5. The relays indicate above shall be provided on HV and LV.

  6. LAs to be provided on HV and LV for transformers of all capacities and voltage class.

  7. OLTC out of step protection is to be provided where master follower scheme is in operation.

  8. Fans failure and pumps failure alarms to be connected.

  9. Alarms for O.T., W.T., Buchholz (Main tank AND OLTC) should be connected.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Electrical4u

Electrical4U is dedicated to the teaching and sharing of all things related to electrical and electronics engineering.

What is Steady State Stability in Power System?
What is Steady State Stability in Power System?
Definition of Steady State StabilitySteady state stability is defined as the capability of an electric power system to sustain its initial operating condition following a small disturbance, or to converge to a state closely approximating the initial condition when the disturbance persists. This concept holds critical significance in power system planning and design, the development of specialized automatic control devices, the commissioning of new system components, and the adjustment of operati
Edwiin
07/26/2025
What is Voltage Stability in Power Systems?
What is Voltage Stability in Power Systems?
Definition of Voltage StabilityVoltage stability in a power system is defined as the ability to maintain acceptable voltages at all buses under both normal operating conditions and after being subjected to a disturbance. In normal operation, the system’s voltages remain stable; however, when a fault or disturbance occurs, voltage instability may arise, leading to a progressive and uncontrollable voltage decline. Voltage stability is sometimes referred to as "load stability."Voltage instability c
Encyclopedia
07/26/2025
Difference Between Shunt and Series Voltage Regulator
Difference Between Shunt and Series Voltage Regulator
Linear voltage regulators are mainly classified into two types: shunt voltage regulators and series voltage regulators. The key difference between them lies in the connection of the control element: in a shunt voltage regulator, the control element is connected in parallel with the load; in contrast, in a series voltage regulator, the control element is connected in series with the load. These two types of voltage regulator circuits operate on different principles and thus have their own advanta
Edwiin
07/25/2025
What is Dual Trace Oscilloscope?
What is Dual Trace Oscilloscope?
What is Dual Trace Oscilloscope?DefinitionA dual-trace oscilloscope uses a single electron beam to generate two separate traces, each deflected by an independent input source. To produce these two traces, it primarily employs two operating modes—alternate mode and chopped mode—controlled by a switch.Purpose of a Dual-Trace OscilloscopeWhen analyzing or studying multiple electronic circuits, comparing their voltage characteristics is often critical. While one could use multiple oscilloscopes for
Encyclopedia
07/25/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!