• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Differential Protection of a Transformer

Encyclopedia
Field: Encyclopedia
0
China

Differential Protection of a Transformer

Transformers are among the key components in power systems. As static, fully - enclosed, and typically oil - immersed devices, faults on them are relatively infrequent. However, even a rare fault can have severe consequences for a power transformer. Thus, safeguarding power transformers against potential faults is of utmost importance.

Faults on transformers are mainly categorized into two types: external faults and internal faults. External faults are swiftly cleared by the relay system outside the transformer to prevent any harm to the transformer from such faults. For internal faults in this type of transformer, a differential protection system is employed.

Differential protection schemes are predominantly utilized to guard against phase - to - phase and phase - to - earth faults. The differential protection for power transformers is grounded in the Merz - Prize circulating current principle. Such protection is generally applied to transformers with a rating exceeding 2 MVA.

Connection for Transformer Differential Protection

Power transformers are star - connected on one side and delta - connected on the other. The current transformers (CTs) on the star - connected side are delta - connected, while those on the delta - connected side are star - connected. The neutrals of both the current transformer star connection and the power transformer star connection are grounded.

A restraining coil is connected between the secondary windings of the current transformers. This restraining coil regulates the sensitivity of the system. The operating coil is positioned between the tapping point of the restraining coil and the star point of the current transformer secondary windings.插图.jpg

Operation of the Differential Protection System

Under normal circumstances, the operating coil carries no current since the currents on both sides of the power transformer are in balance. However, when an internal fault occurs within the power transformer windings, this balance is disrupted. Consequently, the operating coils of the differential relay carry a current that corresponds to the difference in current between the two sides of the transformer. As a result, the relay trips the main circuit breakers on both sides of the power transformer.

Issues with the Differential Protection System

When a transformer is energized, a transient inrush of magnetizing current flows through it. This current can be as much as 10 times the full - load current and decays over time. This magnetizing current flows in the primary winding of the power transformer, causing a discrepancy in the output of the current transformers. This, in turn, can cause the differential protection of the transformer to operate incorrectly.

To address this issue, a kick fuse is placed across the relay coil. These fuses are of the time - limit type with an inverse characteristic and do not operate during the brief duration of the inrush surge. When a fault occurs, the fuses blow, allowing the fault current to flow through the relay coils and activate the protection system. This problem can also be mitigated by using a relay with an inverse and definite minimum characteristic instead of an instantaneous - type relay.

Give a tip and encourage the author!

Recommended

Analysis of Lightning Protection Measures for Distribution Transformers
Analysis of Lightning Protection Measures for Distribution TransformersTo prevent lightning surge intrusion and ensure the safe operation of distribution transformers, this paper presents applicable lightning protection measures that can effectively enhance their lightning withstand capability.1. Lightning Protection Measures for Distribution Transformers1.1 Install surge arresters on the high-voltage (HV) side of the distribution transformer.According to SDJ7–79 Technical Code for Overvol
12/24/2025
Regulations for Primary Wiring of Distribution Transformers
The primary wiring of transformers shall comply with the following regulations: Supports and Cable Protection Conduits: The construction of supports and cable protection conduits for transformer incoming and outgoing lines shall conform to design document requirements. Supports must be firmly installed with elevation and horizontal deviations within ±5mm. Both supports and protection conduits shall have reliable grounding connections. Rectangular Busbar Bending: When rectangular busbars are used
12/23/2025
Transformer Protection Settings: Zero-Sequence & Overvoltage Guide
1. Zero-Sequence Overcurrent ProtectionThe operating current for zero-sequence overcurrent protection of grounding transformers is typically determined based on the transformer's rated current and the maximum allowable zero-sequence current during system ground faults. The general setting range is approximately 0.1 to 0.3 times the rated current, with operating time usually set between 0.5 to 1 second to quickly clear ground faults.2.Overvoltage ProtectionOvervoltage protection is a critical com
12/17/2025
Electrical Protection: Grounding Transformers and Bus Charging
1. High-Resistance Grounding SystemHigh-resistance grounding can limit ground fault current and appropriately reduce ground overvoltage. However, there is no need to connect a large high-value resistor directly between the generator neutral point and ground. Instead, a small resistor can be used together with a grounding transformer. The primary winding of the grounding transformer is connected between the neutral point and ground, while the secondary winding is connected to a small resistor. Ac
12/17/2025
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.