• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Power factor test on circuit breakers

Edwiin
Field: Power switch
China

Assessing the Integrity of Internal and External Insulation

To ensure the reliability and safety of circuit breakers, it is essential to evaluate both their internal and external insulation. Testing equipment typically has an output voltage of 10 kV and is designed to be portable so that it can be used in all substation environments. While this testing is primarily used for oil circuit breakers (CBs), it can also be applied to SF6 switchgear.

Purpose of Power Factor Tests

Power factor tests are conducted to detect contamination and/or deterioration within the breaker’s insulating system, allowing for corrective actions to maintain the integrity of the breaker. This is achieved by measuring the dielectric loss and capacitance of the insulation and calculating the power factor. An increase in dielectric loss and power factor indicates a rise in contamination levels within the insulating system, which can reveal:

  • Moisture contamination: Resulting from leaks or incomplete cleaning and drying.

  • Deterioration of line-to-ground and contact-grading capacitors.

  • Surface contamination of weather sheds.

  • Deterioration of insulating components such as operating rods, interrupters, and interrupter supports caused by corrosive arc by-products.

  • Impurities, contaminants, and/or particles within the insulating medium.

Test Equipment

The figure below illustrates three types of power factor test sets. These devices assist technicians in accurately assessing the condition of insulation, enabling timely detection of potential issues and facilitating necessary repairs. This helps extend the lifespan of the equipment and enhances overall system reliability.

Note: Although images cannot be directly displayed here, please refer to specific equipment manuals or resources for detailed illustrations of the test setups. Additionally, always follow the technical documentation and manufacturer recommendations for the specific equipment when conducting tests in practical applications.

Give a tip and encourage the author!

Recommended

Main Transformer Accidents and Light Gas Operation Issues
1. Accident Record (March 19, 2019)At 16:13 on March 19, 2019, the monitoring background reported a light gas action of No. 3 main transformer. In accordance with the Code for Operation of Power Transformers (DL/T572-2010), operation and maintenance (O&M) personnel inspected the on-site condition of No. 3 main transformer.On-site confirmation: The WBH non-electrical protection panel of No. 3 main transformer reported a Phase B light gas action of the transformer body, and the reset was ineff
02/05/2026
Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.