• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


High speed earthing switch (HSGS) rated operating sequence according to IEC standard (for>550kv)

Edwiin
Field: Power switch
China

High - Speed Earth Switches (HSES) have two rated operating sequences:

  • C–ti1–O

  • C–ti1–O–ti2–C–ti1–O

where:

  • ti1 represents a time period that is longer than the time needed for secondary arc extinction and for the dielectric recovery of air insulation at the fault location. ti1 is determined by users while taking system stability into account. The recommended value of ti1 is 0.15 s.

  • ti2 is the intermediate time specified by the system protection. ti2 encompasses the closing time of the circuit breakers after the HSES open, the duration of a new line fault, and the breaking time of the circuit breakers. After this ti2 period, the HSES can be reclosed. The recommended value of ti2 is 0.5 s. In this situation, the HSES should be capable of operating without any intentional time delay.

The figure depicts the time chart for the rated operating sequence of C–ti1–O–ti2–C–ti1–O with a circuit breaker (CB) in the grid.

In the figure:

  • Energizing of the closing circuit of the HSESs

  • Current start in HSESs

  • Contact touch of HSESs

  • Energizing of the opening release of the HSESs

  • Contact separation of HSESs

  • Arc extinction in HSESs

  • Fully open position of HSESs

The closing time of the HSES is typically less than 0.2 s.

Give a tip and encourage the author!

Recommended

Main Transformer Accidents and Light Gas Operation Issues
1. Accident Record (March 19, 2019)At 16:13 on March 19, 2019, the monitoring background reported a light gas action of No. 3 main transformer. In accordance with the Code for Operation of Power Transformers (DL/T572-2010), operation and maintenance (O&M) personnel inspected the on-site condition of No. 3 main transformer.On-site confirmation: The WBH non-electrical protection panel of No. 3 main transformer reported a Phase B light gas action of the transformer body, and the reset was ineff
02/05/2026
Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.