Digitalicition example based by IEC 61850 in medium voltage switchgear

Edwiin
Field: Power switch
China

The utilization of Rogowski coils for current measurements, voltage dividers for voltage measurements, and a digital bus for sharing switchgear events and sampled measured values enables the separation of measuring hardware engineering from protection applications. This decoupling enhances flexibility and efficiency in electrical system design and operation.

For the protection functions of each Intelligent Electronic Device (IED), line - to - ground currents are consistently measured separately in every feeder. In incoming feeders, resistive dividers are connected to the cables, supplying the necessary voltage measurements to the IEDs within these feeders.

Outgoing feeder protection schemes often require the use of busbar voltage measurements. For example, in section A, one outgoing feeder is equipped with resistive voltage dividers linked to the section A busbar system. Additionally, a bus coupler in this setup has resistive voltage dividers connected to the section B busbar system.

The IEDs in these feeders not only potentially utilize the measured voltage for their own protection schemes but also publish voltage - sampled measured data to the digital communication network. This allows all other IEDs, whether located in section A or B, to subscribe to this digital voltage measurement for their specific protection requirements.

Finally, switchgear events are shared across all feeders, which is crucial for implementing switchgear control, blocking, and interlocking logic. This sharing of information ensures coordinated and reliable operation of the switchgear, enhancing the overall safety and stability of the electrical system.

Give a tip and encourage the author!

Recommended

Rockwill Powers Cambodia’s Battambang Solar-Storage Project
The Battambang Conch PV + Energy Storage Power Station in Cambodia has successfully completed its grid-connected trial operation. The project utilized medium-voltage switchgear supplied by Rockwill Intelligent Electric Co., Ltd. Despite numerous challenges—including an extremely tight delivery schedule—Rockwill Intelligent delivered high-quality products and exceptional service throughout project execution, earning consistent praise from the client.Located in Battambang, Cambodia, the Battambang
12/24/2025
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso