• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Circuit Breaker Ratings

Edwiin
Field: Power switch
China

The rating of a circuit breaker is determined by the duties it performs. For complete specifications, standard ratings and various tests for switches and circuit breakers should be consulted. In addition to the normal operation of circuit breakers, they are required to perform the following three major duties under short-circuit conditions:

  • Breaking the faulty section of the system, defined as the breaking capacity of the circuit breaker.

  • Making the circuit under the greatest asymmetrical current in the current wave, referring to the making capacity of the circuit breaker.

  • Carrying fault current safely for a short time while another breaker clears the fault, known as the short-time capacity of the circuit breaker.

In addition to the above ratings, circuit breakers should be specified in terms of:

  • Number of poles

  • Rated voltage

  • Rated current

  • Rated frequency

  • Operating duty

Detailed explanations of these terms:
Rated Voltage

The rated maximum voltage of a circuit breaker is the highest RMS voltage (above nominal voltage) for which it is designed, serving as the upper limit for operation. Rated voltage is expressed in kVrms and uses phase-to-phase voltage for three-phase circuits.

Rated Current

The rated normal current of a circuit breaker is the RMS value of the current it can continuously carry at rated frequency and voltage under specified conditions.

Rated Frequency

The frequency at which a circuit breaker is designed to operate, with the standard frequency being 50 Hz.

Operating Duty

The operating duty of a circuit breaker consists of the prescribed number of unit operations at stated intervals. The operating sequence refers to the opening and closing operations of the circuit breaker contacts.

Breaking Capacity

This term denotes the highest short-circuit current a breaker can interrupt under specified conditions of transient recovery voltage and power-frequency voltage, expressed in KA RMS at contact separation. Breaking capacities are categorized into:

  • Symmetrical breaking capacity

  • Asymmetrical breaking capacity

Making Capacity

When a circuit breaker closes under short-circuit conditions, its making capacity is the ability to withstand electromagnetic forces (directly proportional to the square of the peak making current). The making current is the peak value of the maximum current wave (including the DC component) in the first cycle after the breaker closes the circuit.

Short-Circuit Current Withstand Capacity

This is the RMS value of current a breaker can carry in a fully closed state without damage for a specified time interval under prescribed conditions, typically expressed in KA for 1 second or 4 seconds. These ratings are based on thermal limitations. Low-voltage circuit breakers generally lack such short-circuit current ratings, as they are typically equipped with straight-acting series overload trips.

Give a tip and encourage the author!

Recommended

Main Transformer Accidents and Light Gas Operation Issues
1. Accident Record (March 19, 2019)At 16:13 on March 19, 2019, the monitoring background reported a light gas action of No. 3 main transformer. In accordance with the Code for Operation of Power Transformers (DL/T572-2010), operation and maintenance (O&M) personnel inspected the on-site condition of No. 3 main transformer.On-site confirmation: The WBH non-electrical protection panel of No. 3 main transformer reported a Phase B light gas action of the transformer body, and the reset was ineff
02/05/2026
Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.