• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What’s the difference in the circuit breaker for air - insulated vs gas - insulated?

ABB
Field: Manufacturing
China

Insulation Performance:

  • Air - insulated Circuit Breakers: They use air as the insulating medium. The insulation performance of air is relatively limited. In harsh environments such as high humidity and high pollution, the insulation performance is easily affected. They are suitable for medium - and low - voltage applications.

  • Gas - insulated Circuit Breakers: Commonly, gases such as sulfur hexafluoride (SF6) are used. They have excellent insulation performance and can withstand higher voltages, making them suitable for high - voltage scenarios. For example, under the same pressure, the insulation strength of SF6 gas is more than three times that of air.

Arc - Extinguishing Ability:

  • Air - insulated Circuit Breakers: Arc - extinguishing mainly relies on compressed air blowing to cool the arc, and the arc - extinguishing ability is relatively weak.

  • Gas - insulated Circuit Breakers: For SF6 circuit breakers, SF6 gas has a strong arc - extinguishing ability. It can quickly extinguish the arc, and the breaking capacity is strong.

Structure and Volume:

  • Air - insulated Circuit Breakers: The structure is relatively simple. However, to ensure the insulation distance, the volume is usually large.

  • Gas - insulated Circuit Breakers: Due to the good insulation performance of the gas, the required insulation space is small, so the structure is more compact and the volume is smaller.

Environmental Adaptability:

  • Air - insulated Circuit Breakers: They are relatively sensitive to environmental humidity, pollution, etc. In harsh environments, additional protective measures are required to ensure performance. However, they also have an advantage in environmental adaptability and can operate under a variety of environmental conditions.

  • Gas - insulated Circuit Breakers: SF6 and other gas - insulated circuit breakers need to be used in a dry and clean environment to maintain the stability of the gas performance. However, dry - air - insulated switchgear that has emerged in recent years has improved environmental adaptability to a certain extent.

Maintenance and Cost:

  • Air - insulated Circuit Breakers: The manufacturing cost is relatively low, but the contact wear is relatively fast, and the service life is relatively short. The contacts need to be replaced regularly.

  • Gas - insulated Circuit Breakers: The price of SF6 gas is high, and special storage and handling equipment are required, resulting in high initial costs. Regular inspections of gas pressure, leakage, etc. are also needed, so the maintenance cost is relatively high. However, the service life is long, and the long - term comprehensive cost may be reduced due to less maintenance.

Give a tip and encourage the author!

Recommended

Main Transformer Accidents and Light Gas Operation Issues
1. Accident Record (March 19, 2019)At 16:13 on March 19, 2019, the monitoring background reported a light gas action of No. 3 main transformer. In accordance with the Code for Operation of Power Transformers (DL/T572-2010), operation and maintenance (O&M) personnel inspected the on-site condition of No. 3 main transformer.On-site confirmation: The WBH non-electrical protection panel of No. 3 main transformer reported a Phase B light gas action of the transformer body, and the reset was ineff
02/05/2026
Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.