Circuit Breaker Operation (Operating & Tripping Time)

Electrical4u
03/25/2024

Circuit Breaker Operation

The primary function of an electrical circuit breaker is to provide opening and closing of the current carrying contacts. Although it is seems to be very simple. But we should remember, that, one circuit breaker remains at its closed position for maximum period of its life span. Very occasionally it is required to operate a circuit breaker for opening and closing its contacts.

Hence circuit breaker operation must be very reliable without any delay or sluggishness. For achieving this reliability the circuit breaker operating mechanism becomes more complex than it was first thought.

Opening and closing distance stroke between contacts and velocity of moving contacts during operation, are the most important parameters to be considered during designing circuit breaker.

Contact gap, traveling distance of moving contacts and their velocity are determined by types of arc quenching medium, current and voltage rating of a circuit breaker.
A typical circuit breaker operating characteristic curve is shown in the graph below.
Here in the graph, X axis represents time in milli seconds and y axis represents distance in milli meter.

Let’s at time, T0 current starts flowing through the closing coil. After time T1 the moving contact starts traveling towards fixed contact. At time T2 moving contact touches fixed contact. At time T3 the moving contact reaches at its close position. T3 – T2 is overloading period of these two contacts (moving and fixed contact). After time T3 the moving contact bounce back little bit and then again comes to its fixed closed position, after time T4.
Circuit Breaker Operating Characteristic

Now we come to the tripping operation. Let’s at time T5 current starts flowing through trip coil of the circuit breaker. At time T6 moving contact starts traveling backward for opening the contacts. After time T7, the moving contact finally detaches the fixed contact. Time (T7 – T6) is over lapping period.

Now at time T8 the moving contact comes back to its final open position but here it will not be at rest position since there will be some mechanical oscillation of moving contact before coming to its final rest position. At time T9 the moving contact finally comes to its rest position. This holds true for both standard and remote control circuit breaker.

Circuit Breaker Opening Operation Requirement

The circuit breaker is desired to be at open position as fast as possible. It is because of limiting contacts erosion and to interrupt faulty current as rapidly as possible. But total travel distance of the moving contact is not determined only by necessity of interruption of faulty current, but rather the contacts gap needed to withstand the normal dielectric stresses and lightning impulse voltage appears across the contacts when the CB is at open position.

The need for carrying the continuous current and for withstanding a period of arc in circuit breaker, makes it necessary to use two sets of contacts in parallel one the primary contact which is always made of high conductive materials such as copper and the other is arcing contact, made of arc resistance materials such as tungsten or molybdenum, which has much lower conductivity than primary contacts.

During opening circuit breaker operation, the primary contacts open before the arcing contacts. However, due to the difference in the electrical resistance and the inductor of the electrical paths of the primary and arcing contacts, a finite time is required to attain total current commutation, i.e. from primary or main contacts to arcing contact branch.

So when the moving contact starts traveling from closed position to open position the contact gap gradually increases and after some time a critical contact position reaches which indicates the minimum conduct gap required for preventing re-arcing after very next current zero.
The remaining part of the travel is required only for maintaining sufficient dielectric strength between contacts gap and for deceleration purpose.

Circuit Breaker Closing Operation Requirement

During closing operation of circuit breaker the followings are required,

  1. The moving contact must travel towards fixed contact at sufficient speed to prevent pre-arcing phenomenon. As the contact gap reduces, arcing may start before contacts are closed finally.

  2. During closing of contacts, the medium between contacts is replaced, hence sufficient mechanical power to be supplied during this circuit breaker operation to compress dielectric medium in the arcing chamber.

  3. After hitting fixed contact, the moving contact may bounce back, due to repulsive force which is not at all desirable. Hence sufficient mechanical energy is to be supplied to overcome repulsive force due to closing operation on fault.

  4. In spring-spring mechanism, generally tripping or opening spring is charged during closing operation. Hence sufficient mechanical energy also to be supplied to charge the opening spring.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Electrical4u

Electrical4U is dedicated to the teaching and sharing of all things related to electrical and electronics engineering.

What is Steady State Stability in Power System?
What is Steady State Stability in Power System?
Definition of Steady State StabilitySteady state stability is defined as the capability of an electric power system to sustain its initial operating condition following a small disturbance, or to converge to a state closely approximating the initial condition when the disturbance persists. This concept holds critical significance in power system planning and design, the development of specialized automatic control devices, the commissioning of new system components, and the adjustment of operati
Edwiin
07/26/2025
What is Voltage Stability in Power Systems?
What is Voltage Stability in Power Systems?
Definition of Voltage StabilityVoltage stability in a power system is defined as the ability to maintain acceptable voltages at all buses under both normal operating conditions and after being subjected to a disturbance. In normal operation, the system’s voltages remain stable; however, when a fault or disturbance occurs, voltage instability may arise, leading to a progressive and uncontrollable voltage decline. Voltage stability is sometimes referred to as "load stability."Voltage instability c
Encyclopedia
07/26/2025
Difference Between Shunt and Series Voltage Regulator
Difference Between Shunt and Series Voltage Regulator
Linear voltage regulators are mainly classified into two types: shunt voltage regulators and series voltage regulators. The key difference between them lies in the connection of the control element: in a shunt voltage regulator, the control element is connected in parallel with the load; in contrast, in a series voltage regulator, the control element is connected in series with the load. These two types of voltage regulator circuits operate on different principles and thus have their own advanta
Edwiin
07/25/2025
What is Dual Trace Oscilloscope?
What is Dual Trace Oscilloscope?
What is Dual Trace Oscilloscope?DefinitionA dual-trace oscilloscope uses a single electron beam to generate two separate traces, each deflected by an independent input source. To produce these two traces, it primarily employs two operating modes—alternate mode and chopped mode—controlled by a switch.Purpose of a Dual-Trace OscilloscopeWhen analyzing or studying multiple electronic circuits, comparing their voltage characteristics is often critical. While one could use multiple oscilloscopes for
Encyclopedia
07/25/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!