• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What is Overcurrent Relay?

Encyclopedia
Field: Encyclopedia
0
China

 What is Overcurrent Relay?

Definition

An overcurrent relay is defined as a relay that activates only when the current value exceeds the relay's set value. It safeguards the equipment in the power system from fault currents.

Classification Based on Operation Time

Based on the time it takes to operate, the overcurrent relay can be categorized into the following types:

  • Instantaneous Overcurrent Relay

  • Inverse Time Overcurrent Relay

  • Definite Time Overcurrent Relay

  • Inverse Definite Time Overcurrent Relay

  • Very Inverse Definite Time Overcurrent Relay

  • Extremely Inverse Definite Time Overcurrent Relay

Instantaneous Overcurrent Relay

The instantaneous overcurrent relay has no deliberately introduced time delay in its operation. When the current within the relay exceeds the operating value, its contacts close immediately. The time span between the moment the current reaches the pick - up value and the closing of the relay contacts is extremely short.

The most notable advantage of the instantaneous relay is its rapid operating time. It commences operation as soon as the current value surpasses the relay setting. This relay functions only when the impedance between the power source and the relay is lower than the impedance specified for the section.

The key feature of this relay is its operational speed. It protects the system from earth faults and is also utilized to protect the system from circulating currents. The instantaneous overcurrent relay is typically installed in the outgoing feeder.

Inverse - Time Overcurrent Relay

The inverse - time overcurrent relay operates when the magnitude of its operating current is inversely proportional to the magnitude of the energizing quantities. As the current increases, the operating time of the relay decreases, meaning its operation depends on the magnitude of the current.

The characteristic curve of this relay is presented in the figure below. The relay remains inactive when the current value is less than the pick - up value. It is employed for the protection of distribution lines. The inverse - time relay is further classified into three subtypes.

relay.jpegInverse Definite Minimum Time (IDMT) Relay

The Inverse Definite Minimum Time (IDMT) relay is a type of protective relay whose operating time is approximately inversely proportional to the magnitude of the fault current. The operating time of this relay can be adjusted by setting the time delay. The IDMT relay incorporates an electromagnetic core. This is because the electromagnetic core can readily saturate when the current magnitude exceeds the pick - up current. The IDMT relay is widely used for the protection of distribution lines. It strikes a balance between the speed of response and the selectivity required in such power distribution systems.

Very Inverse Relay

The very inverse relay exhibits an inverse time - current characteristic that is more pronounced than that of the IDMT relay. This type of relay finds applications in feeders and long - distance transmission lines. It is particularly useful in locations where the magnitude of the short - circuit current drops rapidly due to the significant distance from the power source. The very inverse relay is designed to sense fault currents regardless of the fault location. This makes it suitable for protecting long - line sections where the impedance varies along the line, and the fault current magnitude can be highly dependent on the distance from the source.

Extremely Inverse Relay

The extremely inverse relay has a time - current characteristic that shows an even more exaggerated inverse relationship compared to the IDMT and very inverse relays. This relay is commonly employed for protecting equipment such as cables and transformers. In situations where the pick - up value of the current exceeds the relay's setting, the extremely inverse relay can operate instantaneously. It provides fast operation even under fault current conditions, which is crucial for protecting equipment from severe over - currents. Additionally, it is often used to detect overheating in machines, as its characteristic can be tuned to respond quickly to abnormal current increases associated with overheating.

Inverse time relays, including the IDMT, very inverse, and extremely inverse relays, are extensively used in distribution networks and power plants. Their ability to provide rapid operation under fault conditions, owing to their unique fault - time characteristics, makes them an essential component in safeguarding power systems from various electrical faults.

Give a tip and encourage the author!

Recommended

Case Studies of Installation and Manufacturing Defects in 110kV HV Circuit Breaker Porcelain Insulators
1. SF6 gas leakage occurred in the ABB LTB 72 D1 72.5 kV circuit breaker.Inspection revealed gas leakage at the fixed contact and cover plate area. This was caused by improper or careless assembly, where the dual O-rings slipped and were misplaced, resulting in gas leakage over time.2. Manufacturing Defects on the Outer Surface of 110kV Circuit Breaker Porcelain InsulatorsAlthough high-voltage circuit breakers typically have their porcelain insulators protected with covering materials during tra
12/16/2025
Overview of Defect Diagnosis Methods for High-Voltage AC Circuit Breakers
1. What are the characteristic parameters of the coil current waveform in high-voltage circuit breaker operating mechanisms? How to extract these characteristic parameters from the original trip coil current signal?Answer: The characteristic parameters of the coil current waveform in high-voltage circuit breaker operating mechanisms may include the following: Steady-state peak current: The maximum steady-state current value in the electromagnet coil waveform, representing the position where the
12/16/2025
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.