Typical alarms in gas insulated switchgear (GIS)

Edwiin
Field: Power switch
China

Gas Leak Indication

A gas density of approximately 90% or lower in each gas compartment and zone indicates the presence of a gas leak. This compromised gas density can gradually undermine the integrity of the insulation and operational performance of the equipment.

Insulation Rating Non - Compliance

When the gas density drops to around 80% or less in every gas compartment and zone, it means that the dielectric ratings of the apparatus can no longer be maintained. This situation poses a significant risk to the electrical insulation properties, potentially leading to electrical failures and safety hazards.

Low Circuit Breaker Operating Mechanism Pressure

A reduction in the pressure of the circuit breaker operating mechanism, whether it is pneumatic, hydraulic, or spring - based, is a critical concern.

When the pressure of the circuit breaker operating mechanism is too low, it indicates that the circuit breaker may no longer be able to open or close successfully. In such cases, the protection scheme is typically designed to prevent any further operation to avoid potential malfunctions or damage. It should be emphasized that, in most puffer - type circuit breakers, the gas not only serves as an insulator but also functions as a damper or cushion for the operating mechanism, highlighting the importance of maintaining proper gas pressure.

Loss of Motor Voltage for Operating Energy Supply

The loss of voltage to the motor of the circuit breaker mechanism, which supplies the necessary operating energy, can severely impact the normal operation of the circuit breaker. Without the proper electrical supply to this motor, the circuit breaker may be unable to perform its essential functions, such as opening or closing the electrical circuit.

Loss of DC Control Voltage for Circuit Breakers

The absence of the DC control voltage or voltages to the circuit breakers can disrupt the control and operation of the circuit breakers. This loss can prevent the circuit breakers from receiving the correct signals to operate, leading to a breakdown in the overall electrical system protection and control.

Loss of DC Control Voltage to the Annunciator

When the DC control voltage to the annunciator in the local control cabinet is lost, it can cause issues with the proper indication and monitoring of the circuit breaker's status. The annunciator plays a crucial role in alerting operators to various operational conditions, and its failure due to voltage loss can lead to delayed or missed detection of potential problems.

Pole Disagreement Operation

Pole disagreement operation occurs when the different poles of the circuit breaker do not operate in unison. This inconsistent operation can result in electrical unbalance, abnormal current flow, and potential damage to the circuit breaker and connected electrical equipment.

Excessive Motor Run - Time

An excessive run - time of the motor that supplies operating energy to the circuit breaker mechanism can be a sign of underlying problems. It may indicate issues such as mechanical jams, excessive friction, or control system malfunctions, which can overheat the motor and reduce its lifespan, as well as potentially affecting the proper operation of the circuit breaker.

Overcurrent in Motor Protection

The overcurrent operation of the protective device for the circuit breaker mechanism's motor is a clear indication of an abnormal electrical condition. This overcurrent can be caused by various factors, such as short circuits, overloads, or faulty components within the motor or its associated circuitry, and it requires immediate attention to prevent damage to the motor and ensure the safe operation of the circuit breaker.

Give a tip and encourage the author!

Recommended

Main Transformer Accidents and Light Gas Operation Issues
1. Accident Record (March 19, 2019)At 16:13 on March 19, 2019, the monitoring background reported a light gas action of No. 3 main transformer. In accordance with the Code for Operation of Power Transformers (DL/T572-2010), operation and maintenance (O&M) personnel inspected the on-site condition of No. 3 main transformer.On-site confirmation: The WBH non-electrical protection panel of No. 3 main transformer reported a Phase B light gas action of the transformer body, and the reset was ineff
02/05/2026
Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.