• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Comparison Between Overhead & Underground Transmission Systems

Edwiin
Field: Power switch
China

Key Differences and Comparison Between Underground and Overhead Power Transmission & Distribution
Public Safety

In terms of public safety, underground systems outperform overhead transmission systems. With all transmission and distribution components buried, underground setups minimize risks from obstacles and external interference. Additionally, they are less susceptible to environmental factors like wind, storms, and heavy rain, making them inherently more secure.

Initial Cost

Underground systems incur significantly higher initial costs than overhead systems. Excavation, conduits, specialized cables, manholes, and other transmission equipment drive expenses, with underground installations costing 5 to 10 times more than overhead counterparts.

Flexibility

Overhead systems offer greater flexibility for modifications. Wires, poles, and transformers are easily accessible, allowing quick adjustments to meet changing load demands. Underground systems, however, rely on permanent manholes and duct lines. Adding capacity or modifying the system requires installing new duct lines, making adjustments far more difficult.

Faults

Underground systems have a low fault risk due to buried cables with robust insulation. Overhead systems, exposed to environmental factors (e.g., severe weather), face higher chances of power faults and external accidents.

Fault Location & Repair

While underground faults are rare, locating and repairing them is challenging due to buried infrastructure. Overhead systems, with exposed conductors, enable rapid fault detection and repair.

Current Carrying Capacity & Voltage Drop

  • Current Capacity: Overhead systems can carry significantly more current than underground systems with the same conductor material and cross - sectional area.

  • Voltage Range: Underground systems are typically used for voltages below 150 kV, while overhead transmission supports extra - high voltages (EHV/UHV), ranging from 380 kV to 800 kV and above.

  • Reactance Characteristics: Underground cables have lower inductive reactance (due to closer spacing) but higher capacitive reactance, increasing charging currents. This limits their suitability for very long - distance transmission.

Interference with Communication Circuits

Overhead systems can interfere with telephone lines, causing unwanted potential increases and noise in communication networks. Underground systems eliminate such interference.

Maintenance Cost

Underground systems have lower routine maintenance costs due to reduced exposure to wind, snow, and lightning. However, fault repairs are time - consuming and expensive. Overhead systems, despite higher fault probabilities, allow faster and cheaper repairs.

Appearance

Underground systems preserve the visual appeal of an area by burying all infrastructure, avoiding interference with buildings. Overhead power lines, by contrast, can detract from the landscape.

Useful Life

Underground systems typically have a lifespan twice that of overhead systems. While an overhead system may last 25 years, an underground setup can operate for approximately 50 years.

Comparison between underground cables and overhead lines

 

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.