• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Shunt Capacitor: What is it? (Compensation & Diagram)

Electrical4u
Field: Basic Electrical
0
China

What Is A Shunt Capacitor

What is a Shunt Capacitor?

A capacitor bank is very essential equipment of an electrical power system. The power required to run all the electrical appliances is the load as useful power is active power. The active power is expressed in kW or MW. The maximum load connected to the electrical power system is mainly inductive in nature such as electrical transformer, induction motors, synchronous motor, electric furnaces, fluorescent lighting are all inductive in nature.

In addition to these, inductance of different lines also contributes inductance to the system.
Because of these inductances, the system
current lags behind system voltage. As the lagging angle between voltage and current increases, the power factor of the system decreases. As the electrical power factor decreases, for same active power demand the system draws more current from source. More current causes, more line losses.

Poor electrical power factor causes poor voltage regulation. So to avoid these difficulties, the electrical power factor of the system to be improved. As a capacitor causes current to lead the voltage, capacitive reactance can be used to cancel the inductive reactance of the system.
The capacitor reactance can be used to cancel the inductive reactance of the system.

The capacitor reactance is generally applied to the system by using static capacitor in shut or series with system. Instead of using a single unit of capacitor per phase of the system, it is quite effective to use a bank of capacitor units, in the view of maintenance and erection. This group or bank of capacitor units is known as capacitor bank.

There are mainly two categories of capacitor bank according to their connection arrangements.

  • Shunt capacitor.

  • Series capacitor.

The Shunt capacitor is very commonly used.

How to determine Rating of Required Capacitor Bank

The size of the Capacitor bank can be determined by the following formula :
Where,
Q is required KVAR.
P is active power in KW.
cosθ is
power factor before compensation.
cosθ’ power factor after compensation.

Location of Capacitor Bank

Theoretically it is always desired to commission a capacitor bank nearer to reactive load. This makes transmission of reactive KVARS is removed from a greater part of the network. Moreover if capacitor and load are connected simultaneously, during disconnection of load, capacitor is also disconnected from rest of the circuit. Hence, there is no question of over compensation. But connecting capacitor with each individual load is not practical in the economical point of view. As the size of loads extremely differs for different consumers. So various size of capacitors are not always readily available. Hence proper compensation can not be possible at each loading point. Again each load is not connected with system for 24 × 7 hours. So the capacitor connected to the load also can not be fully utilized.

Hence, capacitor, is not installed at small load but for medium and large loads, capacitor bank can be installed at consumer own premises. Although the inductive loads of medium and large bulk consumers are compensated, but still there would be considerable amount of VAR demand originated from different uncompensated small loads connected to the system. In addition to that, inductance of line and transformer also contribute VAR to the system. On viewing of these difficulties, instead of connecting capacitor to each load, large capacitor bank is installed at main distribution sub-station or secondary grid sub-station.

Connection of Shunt Capacitor Bank

The capacitor bank can be connected to the system either in delta or in star. In star connection, the neutral point may be grounded or not depending upon protection scheme for capacitor bank adopted. In some cases the capacitor bank is formed by double star formation.

Generally large capacitor bank in electrical substation is connected in star.
The grounded star connected bank has some specific advantages, such as,

  • Reduced recovery voltage on circuit breaker for normal repetitive capacitor switching delay.

  • Better surge protection.

  • Comparatively reduced over voltage phenomenon.

  • Lesser cost of installation.

  • In a solidly grounded system the voltage of all 3-phases of a capacitor bank, are fixed and remain unchanged even during 2 phase operation period.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.