• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Specifications or Rating of Power Capacitor Bank

Electrical4u
Field: Basic Electrical
0
China

What Are The Specifications Or Rating Of Power Capacitor Bank

A capacitor bank has to go through different abnormal system conditions, during its life span. To with stand these abnormalities at optimum manufacturing cost, the capacitor banks are rated with following allowable parameters. A capacitor bank should continue its service with in the following limits.

  • 110 % of normal system peak voltage.

  • 120 % of normal system rms voltage.

  • 135 % of rated KVAR.

  • 180 % of normal rated rms current.

Voltage Rating of Capacitor Bank

A capacitor unit is normally designed for single phase. The capacitor should be capable of smooth operation upto 110% of rated peak phase voltage of the system and also it should be capable of operation 120% of rated rms phase voltage that means, 120% oftimes of peak phase voltage.

KVAR Rating of Capacitor Unit

Capacitor unit are normally rated with its KVAR ratings. Standard capacitor unit available at market, are typically rated with either of following KVAR rating.
50 KVAR, 100 KVAR, 150 KVAR, 200 KVAR, 300 KVAR and 400 KVAR.
The KVAR delivered to the
power system depends upon the system voltage by the following formula.

Temperature Rating of a Capacitor Bank

These are mainly two cause of farming heat on a capacitor bank.

  • Outdoor type capacitor bank are generally installed at open space where sunlight strikes on the capacitor unit directly. Capacitor can also absorb heat from the nearly furnace for which it is installed.

  • Production of heat in the capacitor unit is also initiated from the VAR delivering by the unit.

Hence, for radiation of these heats, there should be sufficient arrangement. The maximum allowable ambient temperatures in which a capacitor bank should be operated are given below in tabular form,

Maximum Ambient Temperature

For better ventilation, there should be enough spacing between capacitor units. Sometime forced air flow can be used to accelerated heat radiation from the bank.

Capacitor Bank Unit or Capacitor Unit

Capacitor bank units or simply called capacitor units are manufactured in either single phase or three phase configuration.

Single Phase Capacitor Unit

Single phase capacitor units are designed either double bushing or single bushing.

Double Bushing Capacitor Unit

Here, the terminal of the both ends of capacitor assembly are come out from the metallic casing of the unit through two bushing. The entire capacitor assembly, this is series parallel combination of required number of capacitive elements is immersed in insulating fluid casing. Hence, there will be an insulated separation between conducting part of the capacitor element assembly go through bushing, there will be no connection between conductor and casing. That is why double bushing capacitor unit is known as dead tank capacitor unit.

Single Bushing Capacitor Unit

In this case casing of the unit is used as second terminal of assembly of capacitor element. Here single bushing is used to terminal one end of the assembly and its other terminal is internally connected to the metallic casing. This is possible because except terminal, all other conducting portion of the capacitor assembly is insulated from the casing.

Three Bushing Capacitor Unit

A three phase capacitor unit has three bushings to terminate 3 phase respectively. There is no neutral terminal in 3 phase capacitor unit.

BIL or Basic Insulation Level of Capacitor Unit

Like other electrical equipments a capacitor bank has also to with stand different voltage conditions, like power frequency over voltages and lightening and switching over voltages.
So
Basic Insulation Level must be specified on every capacitor unit rating plate.

Internal Discharge Device

Capacitor units are normally provided with internal discharge device which ensures the quick discharge of residual voltage to its safe level i.e. 50 V or less, with in the specific time period a capacitor unit is also rated with its discharge period.

Transient Over Current Rating

Power capacitor may undergo over current situating during switching operation. So the capacitor unit must be rated for allowable short circuit current for specified time period.
So, a
capacitor unit should be rated with all the above mentioned parameters.
The example of rating of a typical capacitor unit is given below-
So a power capacitor unit can be rated as follows,

  • Nominal system voltage in KV.

  • System power frequency in Hz.

  • Temperature class with allowable maximum and minimum temperature in oC.

  • Rated voltage per unit in KV.

  • Rated output in KVAR.

  • Rated capacitance in µF.

  • Rated current in Amp.

  • Rated insulation level (Nominal voltage/Impulse voltage).

  • Discharge time/voltage in second/voltage.

  • Fusing arrangement either internally fused or externally fused or fuseless.

  • Number of bushing, double/single/triple bushing.

  • Number of phase. Single phase or three phase.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.