Construction of a Shunt Reactor

Electrical4u
03/25/2024

What Is The Construction Of A Shunt Reactor

Shunt Reactor is used to compensate capacitive reactive power of a long transmission line. The constructional features of a shunt reactor may vary manufacturer to manufacturer but basic of construction is more or less same.

Core of Shunt Reactor

Gapped Core is generally used in shunt reactor. The core is constructed from Cold Rolled Grain Oriented Silicon Steel sheet to reduce hysteresis losses. The sheets are laminated to reduce eddy current losses. Gaps are intentionally provided in the construction by placing spacers of high modulus of electricity between the packets of laminations. Normally the gaps are maintained radially. The laminations are placed in each packet in longitudinal direction. Normally, 5 limb 3 phase structure of core is used. It is shell type construction. The yokes and side limbs are not gapped but the three inner limbs for individual phase is constructed with radial gaps as shown.

Winding of Shunt Reactor

There is nothing special about winding of a reactor. This is mainly made of copper conductors. The conductors are paper insulated. Insulated spacers are provided between turns to maintain the path for oil circulation. This arrangement helps for efficient cooling of the winding.

Cooling System of Reactor

Normally a shunt reactor deals with low current that is why ONAN (Oil Natural Air Natural) cooling is sufficient for shunt reactor even for extra high voltage ratings. The radiator bank is connected with main tank to facilitate faster cooling.

Tank of Reactor

The main tank of larger rated reactor for UHV and EHV system is often of bell tank type. Here, both bottom tank and bell tank are manufactured by steel sheet of suitable thickness. The steel sheets of suitable pieces are welded together to form both of the tanks. The tanks are designed and constructed to withstand full vacuum and positive pressure of one atmosphere. The tanks should be so designed that these can be transported by road and railways.

Conservator of Reactor

Conservator is provided at the top of the tank with main tank to conservator connecting pipe line of suitable diameter. The conservator is generally horizontally aligned cylindrical tank, to provide adequate space to the oil for expansion due to temperature rise. Flexible separator between air and oil or air cell is provided in the conservator for the said purpose. The conservator tank is also equipped with a magnetic oil gauge to monitor the oil level in the reactor. The magnetic oil gauge also gives an alarm through a normally open (NO) DC contact, attached to it when oil level falls below a preset level due to oil leakage or any other reason.
shunt reactor

Pressure Relief Device

Due to huge fault inside the reactor there may be sudden and excessive expansion of oil inside the tank. This huge oil pressure generated in the reactor should be released immediately along with separation of the reactor from the live power system. Pressure Relief Device does the job. This is a spring loaded mechanical device. This is fitted on the roof of the main tank. At the event of actuation, the upward pressure of the oil in tank becomes greater than the downward spring pressure, as a result there will be an opening in the valve disc of the device through which the expanded oil comes out to relief the pressure formed inside the tank. There is a mechanical lever attached to the device which is normally in horizontal position. When the device is actuated, this lever becomes vertical. By observing the alignment of the lever even from ground level one can predict whether the Pressure Relief Device (PRD) has been operated or not. The PRD is accompanied with a trip contact to trip the shunt reactor at the event of actuation of the device.
N B: – PRD or such type of device cannot be reset from remote once it actuated. It can only be reset manually by moving the lever to its original horizontal position.

Buchholz Relay

One Buchholz relay is fitted across the pipe connecting the conservator tank and main tank. This device collects gases generated in the oil and actuates the alarm contact attached to it. It has also a trip contact which is actuated at the event of sudden accumulation of gas in the device or rapid flow of oil (oil surge) through the device.

Silica Gel Breather

When oil becomes hot, it is expanded thus air from conservator or air shell (where air shell is used) comes out. But during contraction oil, air from the atmosphere enters into conservator or air shell (where air shell is used). This process is called breathing of the oil immersed equipment (like transformer or reactor). During breathing, obviously moisture can enter into the equipment if it is not taken care of. An pipe from conservator tank or air shell is fitted with a container filled with silica gel crystal. When air is passed through it, the moisture is absorbed by the silica gel.

Winding Temperature Indicator

Winding temperature indicator is a kind of indicating meter associated with a relay. This consists of a sensor bulb placed in an oil filled pocket on the roof of reactor tank. There are two capillary tubes between sensor bulb and the instrument housing. One capillary tube is connected to the measuring bellow of the instrument. Other capillary tube connected to the compensating bellow fitted in the instrument. The measuring system, i.e. sensor bulb, both capillary tubes and both bellows are filled with a liquid which changes its volume when temperature changes. The pocket in which the sensor bulb is immersed, is surrounded by a heating coil which is fed by a current proportional to the current flowing through the winding of reactor. Gravity operated NO contacts are attached to the pointer system of the instrument to provider high temperature alarm and trip respectively.

Oil Temperature Indicator

Oil temperature indicator consists of a sensor bulb placed in an oil filled pocket on the roof of reactor tank. There are two capillary tubes between sensor bulb and the instrument housing. One capillary tube is connected to the measuring bellow of the instrument. Other capillary tube connected to the compensating bellow fitted in the instrument. The measuring system, i.e. sensor bulb, both capillary tubes and both bellows are filled with a liquid which changes its volume when temperature changes. The pocket in which the sensor bulb is immersed, is fitted at the location of hottest oil.

Bushing

The winding terminals of each phase comes out from the reactor boy through an insulated bushing arrangement. In high voltage shunt reactor, the bushings are oil filled. The oil is sealed inside the bushing that means there is no link between the oil inside the bushing and oil inside the main tank. Oil level gauge is provided on the expansion chamber of the condenser bushings.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Electrical4u

Electrical4U is dedicated to the teaching and sharing of all things related to electrical and electronics engineering.

What is Steady State Stability in Power System?
What is Steady State Stability in Power System?
Definition of Steady State StabilitySteady state stability is defined as the capability of an electric power system to sustain its initial operating condition following a small disturbance, or to converge to a state closely approximating the initial condition when the disturbance persists. This concept holds critical significance in power system planning and design, the development of specialized automatic control devices, the commissioning of new system components, and the adjustment of operati
Edwiin
07/26/2025
What is Voltage Stability in Power Systems?
What is Voltage Stability in Power Systems?
Definition of Voltage StabilityVoltage stability in a power system is defined as the ability to maintain acceptable voltages at all buses under both normal operating conditions and after being subjected to a disturbance. In normal operation, the system’s voltages remain stable; however, when a fault or disturbance occurs, voltage instability may arise, leading to a progressive and uncontrollable voltage decline. Voltage stability is sometimes referred to as "load stability."Voltage instability c
Encyclopedia
07/26/2025
Difference Between Shunt and Series Voltage Regulator
Difference Between Shunt and Series Voltage Regulator
Linear voltage regulators are mainly classified into two types: shunt voltage regulators and series voltage regulators. The key difference between them lies in the connection of the control element: in a shunt voltage regulator, the control element is connected in parallel with the load; in contrast, in a series voltage regulator, the control element is connected in series with the load. These two types of voltage regulator circuits operate on different principles and thus have their own advanta
Edwiin
07/25/2025
What is Dual Trace Oscilloscope?
What is Dual Trace Oscilloscope?
What is Dual Trace Oscilloscope?DefinitionA dual-trace oscilloscope uses a single electron beam to generate two separate traces, each deflected by an independent input source. To produce these two traces, it primarily employs two operating modes—alternate mode and chopped mode—controlled by a switch.Purpose of a Dual-Trace OscilloscopeWhen analyzing or studying multiple electronic circuits, comparing their voltage characteristics is often critical. While one could use multiple oscilloscopes for
Encyclopedia
07/25/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!