• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Testing of Electrical Power Cable | Type Test | Acceptance Test | Routine Test

Electrical4u
Field: Basic Electrical
0
China

What Is Testing Of Electrical Power Cable

  1. The following tests are the type test of electrical power cable.

    Physical tests for insulation and sheath

    1. Tensile strength and elongation at break

    2. Aging in an air oven

    3. Aging in air bomb

    4. Aging in an oxygen bomb

    5. Hot set

    6. Oil resistance

    7. Tear resistance


    8. Insulation resistance

    9. High voltage (water immersion) test

    10. Flammability test (only for SE-3, SE-4)

    11. Water abortion test (for insulation)

    12. Persulphate test (for copper )

    13. Annealing test (for copper)

    14. Tensile test (for Aluminium)

    15. Wrapping test (for Aluminium)

    16. Conductor resistance test (for all)

    17. Test for thickness of insulation (for all)

    18. Measurement of overall diameter (where specified)(for all)


  2. Acceptance test: The following shall constitute acceptance test:

    1. Annealing test (for copper)

    2. Tensile test (for Aluminium )

    3. Wrapping test (for Aluminium )

    4. Conductor resistance test

    5. Test for the thickness of insulation and sheath and overall diameter

    6. Tensile strength and elongation at break of insulation and heath

    7. Hot set test for insulation and sheath

    8. High voltage test

    9. Insulation resistance test

  3. Routine test: The following shall constitute the routine test.

    1. Conductor resistance test

    2. High voltage test

    3. Insulation resistance test

High Voltage Test (Water Immersion Test) :
Approximate 3 meters long core is removed as a sample from the finished cable or cord. The sample then is so immersed in a water bath at room temperature that its ends protrude at least 200 mm above the water level. After 24 hours, an alternating voltage of the required level is applied between
conductor and water. This voltage is raised as per requirement within 10 sec and hold constant at this value for 5 min. If the sample fails in this test, one more sample can be subjected to this test.

Test on completed cables (Acceptance and routine test) :
This test shall be carried out between conductors or between conductor and screen/armor. The test shall be carried out on required voltage the test shall be carried out at room temperature and the time of application shall be 5 min no failure of Insulation shall occur.

Flammability Test :
Period of burning after removal of the flame shall not exceed 60 sec and the unaffected portion from the lower edge of the top clamp shall be at least 50 mm.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.