Tensile Test of Conductors

Electrical4u
Field: Basic Electrical
0
China

What Is The Tensile Test Of Conductors

This test is performed only to confirm tensile strength of aluminum wires used for conductor in electric power cables. This test is significantly performed on conductor material to judge the strength of this material. A cable conductor is often subjected to pull from one end during laying, installing and manufacturing hence it should be strong enough to tolerate the pulling force as well. Hence it becomes necessary to ensure that the conductor material has sufficient tensile strength.

Apparatus required for Tensile Test

  • Tensile Testing Machine: An automatic machine, with two end grips properly designed to hold the conductor with sufficient strength so that the conductor cannot slid by any means during the test. The machine should have sufficient capacity to apply required tension during test.

  • Plane Faced Micrometer which can able to measure accurately even 0.01 mm variation. This is used to measure the diameter of the specimen conductor.

  • Suitable Scale with least scale division 1 mm to measure length of the specimen conductor.

  • Weighing Balance with sensitivity of 0.01g to measure mass of the specimen.

tensile test machineMethod of Tensile Test of Conductors

A specimen of conductor with length little bit longer than gauge length (gauge length is the length of the specimen on which test is carried out) is first taken. To be careful that the minimum length of the entire specimen shall be such that it should have extra length at two ends after its gauge length for holding the same by grips of tensile testing machine. No pre-conditioning of the specimen is required for Tensile test.

Procedure of Tensile Test of Conductors

Before the test is conducted the diameter of the specimen is measured by plane faced micrometer and recorded. In case of shaped solidal conductor, the mass and length of specimen are determined by weigh balance ans measuring scale respectively. Now the test specimen is fixed and fitted in-between the jaws of the machine by means of grips. The load is applied to the specimen and it is increased gradually and uniformly. The rate of separation of jaws of the machine shall not be more than 100 mm per minute. When the Tensile test specimen is fractured, that breaking load is noted down from the dial of the tensile testing machine, and then tension strength is calculated.

Tabulation of Observations of Tensile Test of Conductors

Diameter of Circular Wire in mm

Shaped Solidal Conductor

Cross Sectional Area in mm2

Breaking Load in N


Mass in g

Length in mm



Calculation

Report

Sample No

Aluminum Conductor Grade

Tensile Strength, N/mm2



Observed

Specified

Conclution: Specimen meets/does not meet the requirements of specification.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.